background image

English

14

<Air tight test>

Pressurize the liquid pipe, gas pipe, and equalizer pipe from the ser-
vice ports of each shutoff valve to 550 psi (do not pressurize more 
than 550 psi). If the pressure does not drop within 24 hours, the sys-
tem passes the test.
If there is a pressure drop, check for leaks, make repairs and perform 
the airtight test again.

<Vacuum drying>

Evacuate the system from the liquid pipe, gas pipe, and equalizer 
pipe shutoff valve service ports by using a vacuum pump for more 
than 2 hours and bring the system to –14.6 psi or less. After keeping 
the system under that condition for more than 1 hour, check if the 
vacuum gauge rises or not. If it rises, the system may either contain 
moisture inside or have leaks.

NOTE

If moisture might enter the piping, follow belows.
(I.e., if doing work during the rainy season, if the actual work takes 
long enough that condensation may form on the inside of the 
pipes, if rain might enter the pipes during work, etc.)

After evacuating the system for 2 hours, pressurize the system to 7.25 
psi (vacuum break) with nitrogen gas and evacuate the system again 
using the vacuum pump for 1 hour to –14.6 psi or less (vacuum drying). 
If the system cannot be evacuated to –14.6 psi within 2 hours, repeat 
the operation of vacuum break and vacuum drying.
Then, after leaving the system in vacuum for 1 hour, confirm that the 
vacuum gauge does not rise.

9.

PIPE INSULATION

Insulation of pipes should be done after performing “

8. AIR TIGHT 

TEST AND VACUUM DRYING

”.

Always insulate the liquid piping, the gas piping, the equalizer pipe 
(between the outside units for the outdoor multi system) and these 
pipe connections.
Failing to insulate the pipes may cause leaking or burns.
And be sure to use the insulation which can withstand such temper-
atures of 248°F or more for the equalizer pipe and the gas piping.

Reinforce the insulation on the refrigerant piping according to the 
installation environment. Condensation might form on the surface of 
the insulation. Refer to the below.

„

Ambient temperature : 86°F, humidity : 75% to 80% RH : min. 
thickness : 9/16 in..

„

If the ambient temperature exceeds 86°F and the humidity 80% 
RH, then the min. thickness is 3/4 in..
See the Engineering data book for detail.

If there is a possibility that condensation on the shutoff valve might 
drip down into the indoor unit through gaps in the insulation and pip-
ing because the outside unit is located higher than the indoor unit, 
etc., this must be prevented by caulking the connections, etc. 

(Refer to figure 26)

The piping lead-out hole lid should be attached after opening a 
knock hole. 

(Refer to figure 27)

If small animals and the like might enter the unit through the piping 
lead-out hole, close the hole with blocking material (procured on site) 
after completion of “

11. ADDITIONAL REFRIGERANT CHARGE 

AND CHECK OPERATION

”. 

(Refer to figure 30)

(Refer to figure 26)

1.

Insulation material

2.

Caulking, etc.

(Refer to figure 27)

1.

Piping lead-out hole lid

2.

Open a knock hole at “

”. 

3.

Block  “

”.

NOTE

After knocking out the holes, we recommend you remove burrs in the 
knock holes (

See figure 27

) and paint the edges and areas around 

the edges using the repair paint.

10. CHECKING OF DEVICE AND INSTALLA-

TION CONDITIONS

Be sure to check the followings.

For those doing electrical work

1.

Make sure there is no faulty transmission wiring or loosing of a nut.
See “

7-4 Transmission Wiring Connection Procedure

”.

2.

Make sure there is no faulty power wiring or loosing of a nut.
See “

7-5 Power Wiring Connection Procedure

”.

3.

Has the insulation of the main power circuit deteriorated?
Measure the insulation and check the insulation is above regular 
value in accordance with relevant local and national regulations.

For those doing pipe work

1.

Make sure piping size is correct. 
See “

6-1 Selection of piping material and Refrigerant branching kit

”.

2.

Make sure insulation work is done. 
See “

9. PIPE INSULATION”

.

3.

Make sure there is no faulty refrigerant piping.
See “

6. REFRIGERANT PIPING

”.

11. ADDITIONAL REFRIGERANT CHARGE 

AND CHECK OPERATION

The outside unit is charged with refrigerant when shipped from the factory, 
but depending on the size and length of the piping when installed, it may 
require additional charging.
For charging the additional refrigerant, follow the procedure in this chapter.
And then carry out the check operation.

11-1 Before working

[About the refrigerant tank]

Check whether the tank has a siphon pipe before charging and place 
the tank so that the refrigerant is charged in liquid form.
(See the figure below.)

NOTE

Always use the proper refrigerant (R410A). If charged with the refrig-
erant containing an improper material, it may cause an explosion or 
accident.

R410A is a mixed refrigerant, so charging it as a gas will cause the 
refrigerant composition to change, which may prevent normal oper-
ation.

[Shutoff valve operation procedure]

When operating the shutoff valve, follow the procedure instructed below.

NOTE

Do not open the shutoff valve until 

“10. CHECKING OF DEVICE 

AND INSTALLATION CONDITIONS”

 are completed. If the shutoff 

valve is left open without turning on the power, it may cause refriger-
ant to buildup in the compressor, leading insulation degradation.

Be sure to use the correct tools.
The shutoff valve is not a back-seat type. If forced it to open, it might 
break the valve body.

When using a service port, use the charge hose.

After tightening the cap, make sure no refrigerant gas is leaking.

With siphon pipe

Other tanks

Stand the tank upright and charge.
(The siphon pipe goes all the way inside, 
so the tank does not need be put 
upside-down charge in liquid form.)

Stand the tank upside-down and charge.

Summary of Contents for RXYQ72PAYD

Page 1: ...ALLATION MANUAL System air conditioner English Fran ais Espa ol RXYQ72PAYD RXYQ96PAYD RXYQ108PAYD RXYQ144PAYD RXYQ168PAYD RXYQ192PAYD RXYQ72PATJ RXYQ96PATJ RXYQ108PATJ RXYQ144PATJ RXYQ168PATJ RXYQ192P...

Page 2: ...8 3 7 8 11 3 4 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 7 7 8 11 3 4 Pattern 3 2 1 60 3 1 4 2 5 2 in 40 4 0...

Page 3: ...e 19 1 2 3 5 4 6 11 12 5 8 9 6 10 13 7 7 7 7 7 1 1 1 1 5 13 1 13 2 13 3 6 2 3 4 4 C D 7 8 A 3 4 1 5 2 B 1 2 1 2 3 4 5 1 3 4 2 1 2 3 3 4 6 7 1 1 2 3 4 5 2 5 6 1 1 2 9 8 TOIN DUNIT F1 F2 TOOUT DUNIT F1...

Page 4: ...20 figure 21 figure 22 figure 24 figure 25 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1 A1P 2 3 1 2 3 4 5 1 2 3 4 8 9 10 4 11 L1 L2 L3 12 5 6 7 1 2 3 4 5 6 7 8 9 10 12 11 1 2 3 4 5 6 7 8 9 10 13 15 15 16 F17 1...

Page 5: ...ure 31 figure 26 figure 29 figure 30 figure 32 figure 27 figure 28 1 2 1 2 3 1 2 3 4 5 1 2 2 3 5 6 4 1 2 3 4 10 13 11 5 6 7 8 9 12 15 16 17 18 14 1 2 3 4 11 12 13 9 14 10 5 6 7 8 9 15 16 17 18 19 3 4...

Page 6: ...in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if...

Page 7: ...at can be connected Normal operation is not possible when connected to other units Remote controller wireless kit transmitting distance can be shorter than expected in rooms with electronic fluorescen...

Page 8: ...elect an optimum kit refer to 6 REFRIGERANT PIPING Outside unit multi connection piping kit Refrigerant branching kit Make sure that any separately purchased accessories are designed for use with R410...

Page 9: ...e the rear intake grille to prevent snow from accumulating on the fins 4 INSPECTING AND HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the...

Page 10: ...ants when brazing the pipe joints Residue can clog pipes and break equipment 6 4 Connecting the refrigerant piping 1 Direction to bring out the pipes The local inter unit piping can be connected eithe...

Page 11: ...manual 1 About outside unit multi connection piping kit Install the joint horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 13 1 Do not install...

Page 12: ...stall the REFNET header so it splits horizontally Refer to figure 15 1 Horizontal surface 2 B arrow view Prohibited pattern Oil remains in the stopping outside unit Change to pattern 1 or pattern 2 Fr...

Page 13: ...540 ft Example 8 a b c d e o 540 ft Example 6 a b h 540 ft 8 a i j 540 ft Example 8 a i 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length...

Page 14: ...unit total capacity index x 72 72 x 111 111 x Number of outside unit 2 units Connecting piping kit name BHFP22P100U Refrigerant branch kit name KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Example f...

Page 15: ...iping size at 1 4 0 249 0 121 0 040 0 175 0 081 0 015 HEAT PUMP SYSTEM MODEL NAME MODEL NAME THE AMOUNT OF REFRIGERANT RXYQ72 108PAYD RXYQ72 108PATJ RXYQ144 192PAYD RXYQ144 192PATJ 2 2 lb REFRIGERANT...

Page 16: ...it with attached clamp without applying external pressure on the terminal parts terminal for power wiring terminal for transmission wiring and earth terminal If there exists the possibility of reverse...

Page 17: ...cessory clamp 1 3 Vinyl tube accessory Outside the units the transmission wiring must be finished simulta neously with the local refrigerant piping and wound with tape field supply as shown in figure...

Page 18: ...s for the airtightness test Absolutely do not open the shutoff valve until the main power ciruit insulation measurement has been completed measuring after the shutoff valve is opened will cause the in...

Page 19: ...ole with blocking material procured on site after completion of 11 ADDITIONAL REFRIGERANT CHARGE AND CHECK OPERATION Refer to figure 30 Refer to figure 26 1 Insulation material 2 Caulking etc Refer to...

Page 20: ...BS1 5 6 Lift the protruding part to open the inspection door 72PA type 96PA type 108PA type Liquid pipe shutoff valve 3 8 The 108PA type corresponds to the 1 2 diameter onsite piping using the access...

Page 21: ...ing Installation work for indoor unit 2 Calculate the additional charging amount using How to calculate the additional refrigerant to be charged in 6 5 Example of connection 3 Open the valve B See the...

Page 22: ...hecking see How to check how many units are connected in chapter 11 1 To energize the crankcase heater make sure to turn on for 6 hours before starting operation 3 It takes about 2 10 minutes for gett...

Page 23: ...There is a risk of electric shock if you touch any live parts since this operation must be performed with the power on 13 TEST RUN 13 1 Before test run Make sure the following works are completed in...

Page 24: ...t from the system Pay a special attention to the place such as a basement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the ma...

Page 25: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P215731 6M EM09A060A 1002 FS...

Reviews: