background image

17

English

[Automatic refirgerant charging operation procedure]

NOTE

The marks of LED mean as follows.

h

 : OFF

i

 : ON

j

 : Blinking

 : OFF, ON or Brinking

(1) Open the liquid pipe and gas pipe shutoff valves. (The valve A~C 

must be closed. See figure 31.)

(2)

Close the EL. COMPO. BOX (1) lid and all front panel except on the 
EL. COMPO. BOX (1) side. (*1) And turn the power to the outdoor 
unit and all connected indoor units. (*2)

After H2P stop blinking (about 12 minutes after turning on the 
power), check H2P is OFF.
If H2P is ON, check the malfunction code in the remote controller of 
indoor unit and correct the malfunction in accordance with [Remote 
controller display malfunction code] in chapter 11-2-2.

(3) Check the LED. And push the MODE button (BS1) once if the LED 

displays is not as below.

(4) Push the TEST button (BS4) once. (The LED displays will change as 

below.)

(5) Hold the TEST button (BS4) down for 5 seconds or more.

(The LED displays will change as below and fan of outside unit will 
start rotation.)

(6) When the compressor start working and the LED displays change 

any state in below (*3), go to “In case of cooling mode” or “In case of 
heating mode” in accordance with the LED displays.

In case of cooling mode

(7) Push the TEST button (BS4) once within 5 minutes after procedure 

(5) (*4) and close the all front panels (*5).
After that, open the valve A immediately (See figure 31) (*6) and 
watch the remote controller display of indoor unit.

(8) If the remote controller display shows “PE” code (*7), ready to close the 

valve A.
And go to procedure (9).
If the remote controller display shows other code, close the valve A imme-
diately and refer to [Remote controller cooling mode malfunction code]

Beware the fan running when open the front panel.
The fan may continue rotation after the system stop the operation.

(9) When the compressor stop working (the fan may continue rotation.), 

close the valve A immediately (*8).
And check the LED displays are as below and the remote controller 
display shows “P9” code.

After checking, push the MODE button (BS1) once and the charging 
is complete.

In case of heating mode

(7) Push the TEST button (BS4) once within 5 minutes after procedure 

(5) (*4) and close the all front panels.
After that, open the valve A immediately (See figure 31) (*6) and 
check the charged amount by meauring device.
During operation, if the remote controller display shows “P2” or “P8” 
code, close the valve A immediately and refer to [Remote controller 
heating mode malfunction code].

Beware the fan running when open the front panel.
The fan may continue rotation after the system stop the operation.

(8) When the required amount of refrigerant is charged, close the valve 

A (See figure 30) (*8) and push the RETURN button (BS3) once. And 
then go to procedure (9).

(9) Push the MODE button (BS1) once, and the charging is complete.

Notes (*1)~(*9)

(*1) Lead the refrigerant charge hose etc from the pipe intake. 

All front panels must be closed at the procedure (7).

(*2)

If you perform the refrigerant charging operation within the refrig-
erant system that have the power off unit, the operation cannot fin-
ish properly.
Check the number of outside and indoor units that is powered.
For checking, see [How to check how many units are connected] 
in chapter 11-1.

To energize the crankcase heater, make sure to turn on for 
6 hours before starting operation.

(*3) It takes about 2~10 minutes for getting stability of refrigerant state.

If the additional refrigerant is little and operation is started before 
getting stability, the system can not judge the charging amount pre-
cisely and it cause over charge.

(*4) If the TEST button (BS4) is not pushed within 5 minutes, “P2” code 

will displayed in the remote controller. In this case, refer [Remote 
controller cooling (or heating) mode malfunction code].

(*5) If the front panel is opened during the operation, the system cannot 

operate properly.

(*6) If you leave the system without connecting the refrigerant tank or 

opening the valve A for 30 minutes or more, the system stop oper-
ation and “P2” code are displayed in remote controller.
In this case, refer [Remote controller cooling (or heating) mode mal-
function code].

(*7) Depending on the situation of operation such as the charging 

amount is little, the “PE” code may not be displayed and the “P9” 
code may be displayed.

(*8) Always close the valve A and take the tank off.

The refrigerant charge port of this unit have electric expansion valve 
and the valve are closed when charging is finished. However, the 
valve will opened when ather operation (Check operation, nomal 
operation, etc.). If you leave the tank connected, the refrigerant will 
charged and it cause over charge.

[Remote controller cooling mode malfunction code]

[Remote controller heating mode malfunction code]

H1P H2P H3P H4P H5P H6P H7P

h

h

i

h

h

h

h

H1P H2P H3P H4P H5P H6P H7P

i

i

i

i

i

i

i

H1P H2P H3P H4P H5P H6P H7P

h

j

h

h

h

H1P H2P H3P H4P H5P H6P H7P

j

j

j

h

i

h

i

Go to “In case of 
cooling mode”

j

j

h

h

i

h

i

Go to “In case of 
heating mode”

H1P H2P H3P H4P H5P H6P H7P

i

j

j

i

i

i

i

Code

The work contents

PE

Charging is almost finished. Ready to close the valve A.

PA

PH

The refrigerant tank is empty. Close the valve A and replace 
empty tank to the new tank. After changing the tank, open the 
valve A again.

Beware the fan running. The outside unit does not 
stop operation.

P8

Close the valve A immediately, and restart the operation from 
procedure (3).

P2

Operation is interrupted. Close the 
valve A immedeately and check the 
below items.

Check if gas pipe or liquid pipe 
shutoff valve is opened.

Check the refrigerant tank is con-
nected and the valve A was opend.

Check if the air inlet and outlet of 
the indoor unit are not closed by 
an obstruction.

After correcting the 
abnormality, restart 
the operation from 
procedure (3).

Operation is stoped abnormally. Close 
the valve A immediately. Confirm the 
malfunction code and correct the 
abnormality following the [Remote 
controller displays malfunction code] 
in chapter 11-2-2.

P9

Charging is finished. Close the valve A and take the refriger-
ant tank off.

Code

The work contents

P8

Close the valve A immediately and push the TEST button (BS4) 
once. And restart from procedure (7) of “In case of heating mode”.

P2

Operation is interrupted. Close the valve A immedeately and 
check the below items.

Check if gas pipe or liquid pipe shutoff valve is opened.

Check the refrigerant tank is connected and the valve A 
was opend.

Check if the air inlet and outlet of the indoor unit are not 
closed by an obstruction.

Summary of Contents for RXYQ72PAYD

Page 1: ...ALLATION MANUAL System air conditioner English Fran ais Espa ol RXYQ72PAYD RXYQ96PAYD RXYQ108PAYD RXYQ144PAYD RXYQ168PAYD RXYQ192PAYD RXYQ72PATJ RXYQ96PATJ RXYQ108PATJ RXYQ144PATJ RXYQ168PATJ RXYQ192P...

Page 2: ...8 3 7 8 11 3 4 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 When installed in serial 1 4 3 4 3 4 3 4 3 1 2 1 1 1 7 7 8 11 3 4 Pattern 3 2 1 60 3 1 4 2 5 2 in 40 4 0...

Page 3: ...e 19 1 2 3 5 4 6 11 12 5 8 9 6 10 13 7 7 7 7 7 1 1 1 1 5 13 1 13 2 13 3 6 2 3 4 4 C D 7 8 A 3 4 1 5 2 B 1 2 1 2 3 4 5 1 3 4 2 1 2 3 3 4 6 7 1 1 2 3 4 5 2 5 6 1 1 2 9 8 TOIN DUNIT F1 F2 TOOUT DUNIT F1...

Page 4: ...20 figure 21 figure 22 figure 24 figure 25 1 2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 1 A1P 2 3 1 2 3 4 5 1 2 3 4 8 9 10 4 11 L1 L2 L3 12 5 6 7 1 2 3 4 5 6 7 8 9 10 12 11 1 2 3 4 5 6 7 8 9 10 13 15 15 16 F17 1...

Page 5: ...ure 31 figure 26 figure 29 figure 30 figure 32 figure 27 figure 28 1 2 1 2 3 1 2 3 4 5 1 2 2 3 5 6 4 1 2 3 4 10 13 11 5 6 7 8 9 12 15 16 17 18 14 1 2 3 4 11 12 13 9 14 10 5 6 7 8 9 15 16 17 18 19 3 4...

Page 6: ...in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if...

Page 7: ...at can be connected Normal operation is not possible when connected to other units Remote controller wireless kit transmitting distance can be shorter than expected in rooms with electronic fluorescen...

Page 8: ...elect an optimum kit refer to 6 REFRIGERANT PIPING Outside unit multi connection piping kit Refrigerant branching kit Make sure that any separately purchased accessories are designed for use with R410...

Page 9: ...e the rear intake grille to prevent snow from accumulating on the fins 4 INSPECTING AND HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the...

Page 10: ...ants when brazing the pipe joints Residue can clog pipes and break equipment 6 4 Connecting the refrigerant piping 1 Direction to bring out the pipes The local inter unit piping can be connected eithe...

Page 11: ...manual 1 About outside unit multi connection piping kit Install the joint horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 13 1 Do not install...

Page 12: ...stall the REFNET header so it splits horizontally Refer to figure 15 1 Horizontal surface 2 B arrow view Prohibited pattern Oil remains in the stopping outside unit Change to pattern 1 or pattern 2 Fr...

Page 13: ...540 ft Example 8 a b c d e o 540 ft Example 6 a b h 540 ft 8 a i j 540 ft Example 8 a i 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length...

Page 14: ...unit total capacity index x 72 72 x 111 111 x Number of outside unit 2 units Connecting piping kit name BHFP22P100U Refrigerant branch kit name KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Example f...

Page 15: ...iping size at 1 4 0 249 0 121 0 040 0 175 0 081 0 015 HEAT PUMP SYSTEM MODEL NAME MODEL NAME THE AMOUNT OF REFRIGERANT RXYQ72 108PAYD RXYQ72 108PATJ RXYQ144 192PAYD RXYQ144 192PATJ 2 2 lb REFRIGERANT...

Page 16: ...it with attached clamp without applying external pressure on the terminal parts terminal for power wiring terminal for transmission wiring and earth terminal If there exists the possibility of reverse...

Page 17: ...cessory clamp 1 3 Vinyl tube accessory Outside the units the transmission wiring must be finished simulta neously with the local refrigerant piping and wound with tape field supply as shown in figure...

Page 18: ...s for the airtightness test Absolutely do not open the shutoff valve until the main power ciruit insulation measurement has been completed measuring after the shutoff valve is opened will cause the in...

Page 19: ...ole with blocking material procured on site after completion of 11 ADDITIONAL REFRIGERANT CHARGE AND CHECK OPERATION Refer to figure 30 Refer to figure 26 1 Insulation material 2 Caulking etc Refer to...

Page 20: ...BS1 5 6 Lift the protruding part to open the inspection door 72PA type 96PA type 108PA type Liquid pipe shutoff valve 3 8 The 108PA type corresponds to the 1 2 diameter onsite piping using the access...

Page 21: ...ing Installation work for indoor unit 2 Calculate the additional charging amount using How to calculate the additional refrigerant to be charged in 6 5 Example of connection 3 Open the valve B See the...

Page 22: ...hecking see How to check how many units are connected in chapter 11 1 To energize the crankcase heater make sure to turn on for 6 hours before starting operation 3 It takes about 2 10 minutes for gett...

Page 23: ...There is a risk of electric shock if you touch any live parts since this operation must be performed with the power on 13 TEST RUN 13 1 Before test run Make sure the following works are completed in...

Page 24: ...t from the system Pay a special attention to the place such as a basement etc where refrigerant can stay since refrigerant is heavier than air Procedure for checking maximum concentration Check the ma...

Page 25: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P215731 6M EM09A060A 1002 FS...

Reviews: