Field Setting
SiUS39-601
82
Test Operation
Setting by pushbutton switches
The following settings are made by pushbutton switches on PC board.
There are the following three setting modes.
c
Setting mode 1 (H1P off)
Initial status (when normal) : Used to select the cool/heat setting. Also indicates during “abnormal”,
“low noise control” and “demand control”.
d
Setting mode 2 (H1P on)
Used to modify the operating status and to set program addresses, etc. Usually used in servicing
the system.
e
Monitor mode (H1P blinks)
Used to check the program made in Setting mode 2.
Mode changing procedure
Mode changing procedure
BS1
MODE
BS2
SET
BS3
RETURN
BS4
TEST
BS5
RESET
(V2760)
Setting mode 1
Monitor mode
H1P
Push the BS1(MODE button)
one time.
Blinking
MODE
MODE
Off
H1P
Setting mode 2
MODE
On
H1P
Push and hold the BS1
(MODE button) for 5 seconds.
Push the BS1(MODE button) one time.
(Normal)
(V2761)
Using the MODE button, the modes can be changed as follows.
Check item selection
(SET button)
Contents display
Monitor mode
Setting mode 1
(Initial condition)
Press BS3
(RETURN button).
Press BS3
(RETURN button).
Setting item selection
(SET button)
Setting mode 2
(Set): Select mode with BS2 (SET button) in each selection step.
Setting condition
selection (SET button)
Setting condition
(Contents) display
Press BS3
(RETURN button).
Press BS3
(RETURN button).
Press BS3
(RETURN button).
Press BS1
(MODE button).
Press BS1
(MODE button).
Press BS1(MODE button).
Press BS1 (MODE button) for more than 5 sec.
(V2762)
Summary of Contents for RXYQ72
Page 115: ...Field Setting SiUS39 601 104 Test Operation...
Page 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting...
Page 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M...
Page 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A...
Page 249: ...Example of Connection SiUS39 601 238 Appendix...
Page 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 601 244 Appendix...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A...
Page 269: ...SiUS39 601 iv Index...