Troubleshooting by Indication on the Remote Controller
Troubleshooting
143
Troubleshooting
Note:
Refer check 8, 9 and 12 to P.214
~
215.
Check No. 12
Check on pulse input of
position signal of fan inverter
PCB
YES
Check No. 8
Check on connector of fan
motor (Power supply cable)
YES
Is the LED
(HAP) on fan inverter
PCB blinking?
NO
Check No. 9
Check on connector of fan
motor (Signal wire)
YES
Are the
resistance values
between phases of
U, V, W balanced?
Is there any short
circuiting between
phases of
U, V, W?
NO
Is the
resistance value
between Vcc and UVW,
and GND and UVW
balanced?
NO
Replace the fan inverter
PCB.
Replace the fan motor of
outdoor unit.
Replace the fan motor of
outdoor unit.
Replace the fan inverter
PCB.
(V3077)
1A
Summary of Contents for RXYQ72
Page 115: ...Field Setting SiUS39 601 104 Test Operation...
Page 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting...
Page 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M...
Page 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A...
Page 249: ...Example of Connection SiUS39 601 238 Appendix...
Page 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 601 244 Appendix...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A...
Page 269: ...SiUS39 601 iv Index...