SiUS39-601
Basic Control
Function
39
2.4
Cooling Operation Fan Control
In cooling operation with low outdoor air temperature, this control is used to provide the adequate
amount of circulation air with liquid pressure secured by high pressure control using outdoor unit
fan.
STEP8
STEP7
STEP6
STEP5
STEP4
STEP3
STEP2
STEP1
STEP9
Pc<406 psi
Pc>450 psi
Pc: HP pressure sensor detection value
Pc<478 psi
Pc<261 psi
Pc<391 psi
Pc<261 psi
Pc<391 psi
Pc<261 psi
Pc<391 psi
Pc<261 psi
Pc<391 psi
Pc<261 psi
Pc<391 psi
Pc<261 psi
Pc<391 psi
Pc<333 psi
Pc<391 psi
Fan Steps
RXYQ
72M, 96M
STEP1
0rpm
STEP2
300rpm
STEP3
325rpm
STEP4
355rpm
STEP5
400rpm
STEP6
500rpm
STEP7
630rpm
STEP8
880rpm
STEP9
920rpm