Protection Control
SiUS39-601
50
Function
4.2
Low Pressure Protection Control
This low pressure protection control is used to protect compressors against the transient decrease
of low pressure.
[In cooling operation]
[In heating operation]
Low pressure not limited
Pe<50 psi
Low pressure standby
Low pressure limited
All STD compressors
stop.
Master unit:52 Hz + OFF
Slave unit:Stop
Pe<36 psi
Pe>58 psi
Pe<10 psi
Pe: LP pressure sensor detection
value for master unit
When occurring 3 times within 30 min.,
the malfunction code “ E4 ” is output.
Pe<23 psi
Pe<19 psi
Pe >36 psi
INV upper limit frequency = 210 Hz
Pe<10 psi
&
Low pressure not limited
Low pressure standby
Low pressure limited
124 Hz + OFF
INV upper limit frequency: 1-step /
20 sec up from current compressor
frequency
52 Hz + OFF
Pe: LP pressure sensor detection
value for each outdoor unit
Pe>28 psi
Pe<23 psi
When occurring 3 times within 30 min.,
the malfunction code “E4” is output.
Summary of Contents for RXYQ72
Page 115: ...Field Setting SiUS39 601 104 Test Operation...
Page 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting...
Page 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M...
Page 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A...
Page 249: ...Example of Connection SiUS39 601 238 Appendix...
Page 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 601 244 Appendix...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A...
Page 269: ...SiUS39 601 iv Index...