SiUS39-601
Specifications
Specifications
19
Wall Mounted Type
Notes:
★
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB, 67°FWB
Outdoor temperature: 95°FDB
Equivalent ref. piping length: 25ft (Horizontal)
★
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
Equivalent ref. piping length: 25ft (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
★
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
Model
FXAQ07MVJU
FXAQ09MVJU
FXAQ12MVJU
★
1 Cooling Capacity
Btu/h
7,500
9,500
12,000
★
2 Heating Capacity
Btu/h
8,500
10,500
13,500
Casing Color
White (3.0Y8.5/0.5)
White (3.0Y8.5/0.5)
White (3.0Y8.5/0.5)
Dimensions: (H×W×D)
in
11–3/8×31–1/4×9
11–3/8×31–1/4×9
11–3/8×31–1/4×9
Coil (Cross
Fin Coil)
Rows × Stages × FPI
2×14×17
2×14×17
2×14×17
Face Area
ft²
1.73
1.73
1.73
Fan
Model
QCL9661M
QCL9661M
QCL9661M
Type
Cross Flow Fan
Cross Flow Fan
Cross Flow Fan
Motor Output
HP
0.054
0.054
0.054
Air Flow Rate (H/L)
cfm
260/160
280/175
300/180
Drive
Direct Drive
Direct Drive
Direct Drive
Temperature Control
Microprocessor Thermostat for Cooling
and Heating
Microprocessor Thermostat for Cooling
and Heating
Microprocessor Thermostat for Cooling
and Heating
Sound Absorbing Thermal Insulation Material
Foamed Polystyrene /
Foamed Polyethylene
Foamed Polystyrene /
Foamed Polyethylene
Foamed Polystyrene /
Foamed Polyethylene
Air Filter
Resin Net (Washable)
Resin Net (Washable)
Resin Net (Washable)
Piping
Connections
Liquid Pipes
in
φ
1/4 (Flare Connection)
φ
1/4 (Flare Connection)
φ
1/4 (Flare Connection)
Gas Pipes
in
φ
1/2 (Flare Connection)
φ
1/2 (Flare Connection)
φ
1/2 (Flare Connection)
Drain Pipe
in
VP13
(External Dia. 11/16 Internal Dia. 1/2)
VP13
(External Dia. 11/16 Internal Dia. 1/2)
VP13
(External Dia. 11/16 Internal Dia. 1/2)
Machine Weight (Mass)
Lbs
25
25
25
★
4 Sound Level (H)
dBA
36
37
38
Safety Devices
Fuse
Fuse
Fuse
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Connectable outdoor unit
R-410A Series
R-410A Series
R-410A Series
Standard Accessories
Operation Manual, Installation Manual,
Installation Panel, Paper Pattern for
Installation, Insulation Tube, Clamps,
Screws.
Operation Manual, Installation Manual,
Installation Panel, Paper Pattern for
Installation, Insulation Tube, Clamps,
Screws.
Operation Manual, Installation Manual,
Installation Panel, Paper Pattern for
Installation, Insulation Tube, Clamps,
Screws.
Drawing No.
C:3D046038A
Summary of Contents for RXYQ72
Page 115: ...Field Setting SiUS39 601 104 Test Operation...
Page 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting...
Page 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M...
Page 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A...
Page 249: ...Example of Connection SiUS39 601 238 Appendix...
Page 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 601 244 Appendix...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A...
Page 269: ...SiUS39 601 iv Index...