Field Setting
SiUS39-601
84
Test Operation
No.
Setting item
Description
0
EMG (Emergency
operation 1)
Operates by Standard compressor only when inverter
compressor malfunctions. Temporary operation until the
compressor is replaced. Since the comfortability is
extremely deteriorated, immediately replace the
compressor.
1
Cool/heat unified
address
Sets address for cool/heat unified operation.
2
Low noise/demand
address
Address for low noise/demand operation
5
Indoor unit forced
fan H
Allows forced operation of indoor unit fan while unit is
stopped. (H tap)
6
Indoor unit forced
operation
Allows forced operation of indoor unit.
8
Te setting
Target evaporation temperature for cooling
9
Tc setting
Target condensation temperature for heating
10
Defrost changeover
setting
Changes the temperature condition for defrost and sets to
quick defrost or slow defrost.
11
Sequential operation
setting
Sets sequential operation
12
External low noise
setting / Demand
setting
Reception of external low noise or demand signal
13
AIRNET address
Set address for AIRNET.
18
High static pressure
setting
Make this setting in the case of operating in high static
pressure mode with diffuser duct mounted.
19
Emergency
operation
(STD compressor
operation prohibited)
Used to operate system only with inverter compressor when
STD compressor malfunctions. This is a temporary
operation extremely impairing comfortable environment.
Therefore, prompt replacement of the compressor is
required.
20
Additional refrigerant
charge operation
setting
Carries out additional refrigerant charge operation.
21
Refrigerant recovery /
vacuuming mode
setting
Sets to refrigerant collection mode.
22
Night-time low noise
setting
Sets automatic nighttime low noise operation in a simple
way.
The operating time is based on “Starting set” and “Ending
set”.
25
Low noise setting
Sets low noise level when the low noise signal is input from
outside.
26
Night-time low noise
control starting
setting
Sets starting time of nighttime low noise operation.
(Nighttime low noise setting is also required.)
27
Night-time low noise
control ending
setting
Sets ending time of nighttime low noise operation.
(Nighttime low noise setting is also required.)
28
Power transistor
check mode
∗
Check after
disconnection of
compressor wires
Used for trouble diagnosis of DC compressor. Since the
waveform of inverter is output without wiring to the
compressor, it is convenient to probe whether the trouble
comes from the compressor or PC board.
29
Capacity
precedence setting
If the capacity control is required, the low noise control is
automatically released by this setting during carrying out
low noise operation and nighttime low noise operation.
30
Demand setting 1
Changes target value of power consumption when demand
control 1 is input.
32
Normal demand
setting
Normally enables demand control 1 without external input.
(Effective to prevent a problem that circuit breaker of small
capacity is shut down due to large load.
b. “Setting mode 2”
<Selection of setting items>
<Selection of setting conditions>
Push and hold the MODE button
(BS1) for 5 seconds and set to
“Setting mode 2”.
Push the SET button (BS2) and set
the LED display to a setting item
shown in the table on the right.
↓
Push the RETURN button (BS3) and
decide the item. (The present setting
condition is blinked.)
Push the SET button (BS2) and set
to the setting condition you want.
↓
Push the RETURN button (BS3) and
decide the condition.
Push the RETURN button (BS3) and
set to the initial status of “Setting
mode 2”.
∗
If you become unsure of how to
proceed, push the MODE button
(BS1) and return to setting mode 1.
(V2764)
Summary of Contents for RXYQ72
Page 115: ...Field Setting SiUS39 601 104 Test Operation...
Page 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting...
Page 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M...
Page 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A...
Page 249: ...Example of Connection SiUS39 601 238 Appendix...
Page 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 601 244 Appendix...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A...
Page 269: ...SiUS39 601 iv Index...