Troubleshooting by Indication on the Remote Controller
Troubleshooting
155
2.28
“
J7
”
Malfunction of Receiver Outlet Liquid Pipe
Thermistor (R6T)
Remote
Controller
Display
J7
Applicable
Models
RXYQ72M, 96M
Method of
Malfunction
Detection
Malfunction is detected according to the temperature detected by receiver outlet liquid pipe
thermistor.
Malfunction
Decision
Conditions
When the receiver outlet liquid pipe thermistor is short circuited or open.
Supposed
Causes
Faulty receiver outlet liquid pipe thermistor (R6T)
Faulty outdoor unit PC board
Troubleshooting
∗
1: Refer to thermistor resistance / temperature characteristics table on P239.
(V3075)
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the
resistance
measured after
removing the thermistor
(R6T) from outdoor unit PC
board normal?
(3.5 k
Ω
to
360 k
Ω
)
∗
1
Replace outdoor unit PC board
(A1P).
Connect thermistor and operate
unit again.
NO
NO
Replace thermistor (R6T).
YES
YES
Is
the connector
for receiver
outlet liquid pipe thermistor
connected to X37A on
outdoor unit PC
board (A1P)?
Caution
Summary of Contents for RXYQ72
Page 115: ...Field Setting SiUS39 601 104 Test Operation...
Page 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting...
Page 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M...
Page 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A...
Page 249: ...Example of Connection SiUS39 601 238 Appendix...
Page 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 601 244 Appendix...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A...
Page 269: ...SiUS39 601 iv Index...