SiUS39-601
Field Setting
Test Operation
75
Air Flow Adjustment - Ceiling height
Make the following setting according to the ceiling height. The setting position No. is set to “01” at
the factory.
In the Case of FXAQ07~24, FXHQ12~36
In the Case of FXFQ12~36
Air Flow Direction Setting
Set the air flow direction of indoor units as given in the table below. (Set when optional air outlet
blocking pad has been installed.) The second code No. is factory set to “01.”
Setting Table
Setting of Air Flow Direction Adjustment Range
Make the following air flow direction setting according to the respective purpose.
Setting Table
Air Flow Rate Switching at Discharge Grille for Field Air Flow Rate Switching
When the optional parts (high performance filter, etc.) is installed, sets to change fan speed for
securing air flow rate.
Follow the instruction manual for the optional parts to enter the setting numbers.
Mode No.
Setting Switch
No.
Setting Position
No.
Setting
13(23)
0
01
Wall-mounted type: Standard
02
Wall-mounted type: Slight increase
03
Wall-mounted type: Normal increase
Mode
No.
First
code
No.
Second
code
No.
Setting
Ceiling height
4-way Outlets
3-way Outlets
2-way Outlets
13 (23)
0
01
Standard (N)
Lower than 2.7 m Lower than 3.0 m Lower than 3.5 m
02
High Ceiling (H)
Lower than 3.0 m Lower than 3.3 m Lower than 3.8 m
03
Higher Ceiling (S) Lower than 3.5 m Lower than 3.5 m
—
Mode No.
First Code No.
Second Code
No.
Setting
13 (23)
1
01
F : 4-direction air flow
02
T : 3-direction air flow
03
W : 2-direction air flow
Mode No.
First Code No.
Second Code No.
Setting
13 (23)
4
01
Upward (Draft prevention)
02
Standard
03
Downward (Ceiling soiling
prevention)
Summary of Contents for RXYQ72
Page 115: ...Field Setting SiUS39 601 104 Test Operation...
Page 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting...
Page 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M...
Page 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A...
Page 249: ...Example of Connection SiUS39 601 238 Appendix...
Page 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 601 244 Appendix...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A...
Page 269: ...SiUS39 601 iv Index...