SiUS39-601
Basic Control
Function
33
2.
Basic Control
2.1
Normal Operation
Cooling Operation
Heating Operation
★
Heating operation is not functional at an outdoor air temperature of 75
°
F or more.
Actuator
Operation
Remarks
Compressor
Compressor PI control
Used for high pressure protection control, low
pressure protection control, discharge pipe
temperature protection control, and compressor
operating frequency upper limit control with inverter
protection control.
Outdoor unit fan
Cooling fan control
Four way valve
OFF
Main motorized valve (EV1)
0 pls
Subcooling motorized valve (EV2)
PI control
Hot gas bypass valve (SVP)
OFF
This valve turns on with low pressure protection
control.
Oil equalization valve (SVO)
ON
In the case of multi-outdoor-unit system, this valve
repeats ON/OFF operation at regular intervals of
time.
Receiver gas charging valve (SVL)
OFF
This valve turns on when outdoor temperature is low.
Receiver gas discharging valve (SVG)
OFF
Non-operating unit gas discharging valve
(SVSG)
OFF
Non-operating unit liquid pipe stop valve
(SVSL)
ON
Actuator
Operation
Remarks
Compressor
Compressor PI control
Used for high pressure protection control, low
pressure protection control, discharge pipe
temperature protection control, and compressor
operating frequency upper limit control with inverter
protection control.
Outdoor unit fan
STEP8 or 9
Four way valve
ON
Main motorized valve (EV1)
PI control
Subcooling motorized valve (EV2)
0 pls
Hot gas bypass valve (SVP)
OFF
This valve turns on with low pressure protection
control.
Oil equalization valve (SVO)
ON
In the case of multi-outdoor-unit system, this valve
repeats ON/OFF operation at regular intervals of
time.
Receiver gas charging valve (SVL)
OFF
Receiver gas discharging valve (SVG)
OFF
Non-operating unit gas discharging valve
(SVSG)
OFF
Non-operating unit liquid pipe stop valve
(SVSL)
ON
Summary of Contents for RXYQ72
Page 115: ...Field Setting SiUS39 601 104 Test Operation...
Page 227: ...Troubleshooting OP Unified ON OFF Controller SiUS39 601 216 Troubleshooting...
Page 231: ...Piping Diagrams SiUS39 601 220 Appendix 1 Piping Diagrams 1 1 Outdoor Unit RXYQ72M 96M...
Page 236: ...SiUS39 601 Wiring Diagrams for Reference Appendix 225 RXYQ144 168 192MTJU C 3D050353A...
Page 249: ...Example of Connection SiUS39 601 238 Appendix...
Page 255: ...Method of Replacing The Inverter s Power Transistors and Diode Modules SiUS39 601 244 Appendix...
Page 265: ...Precautions for New Refrigerant R 410A SiUS39 601 254 Precautions for New Refrigerant R 410A...
Page 269: ...SiUS39 601 iv Index...