background image

18

English

(3) Perform the check operation following the Check Operation Method 

of the [Service Precautions] label (lower) on the EL. COMPO. BOX 
lid. (See figure 32) The system operation for about 40~60 minutes 
and automatically stops the check operation.
If the malfunction code is not displayed in the remote controller after 
the system stop, check operation is completed. Normal operation will 
be possible after 5 minutes. If the malfunction code is displayed in the 
remote controller, correct the malfunction following [Remote control-
ler displays malfunction code] and perform the check operation again.

(Refer to figure 32)

1.

EL. COMPO.BOX (1) lid

2.

EL. COMPO.BOX (2) lid

3.

[Service Precaution] label (upper)

4.

[Service Precaution] label (lower)

NOTE

For interrupting the check operation, push RETURN button (BS3).

[Remote controller displays malfunction code]

NOTE

If any malfunction codes other than the above are displayed, check the 
service manual for how to respond.

12. ONSITE SETTINGS

NOTE

In the case of a multi system, all onsite settings should be made on the 
master unit. Settings made on sub units are invalid.
The outside unit to which the indoor unit transmission wire are con-
nected is the master unit, and all other units are sub units.

Use the push button switches (BS1 through BS5) on the outside unit 
PC-board (A1P) to make the necessary onsite settings.
See the “Service Precautions” label (upper) on the EL. CONPO. BOX lid 
for details on the positions and operating method of the push button 
switches and on the onsite setting.
Make sure to record the setting on the accessory “REQUEST FOR THE 
INDICATION” label.

WARNING

Electric Shock Warning

Use an insulated rod to operate the push buttons via the inspection door 
of EL. COMPO. BOX lid. 
There is a risk of electric shock if you touch any live parts, since this 
operation must be performed with the power on.

13. TEST RUN

13-1 Before test run

Make sure the following works are completed in accordance with the 
installation manual.

„

Piping work

„

Wiring work

„

Air tight test

„

Vacuum drying

„

Additional refrigerant charge

„

Check operation

Check that all work for the BS, indoor unit are finished and there are 
no danger to operate.

13-2 Test Run

After all works are completed, operate the unit normally and check the 
following.
(1) Make sure the indoor and outside units are operating normally.
(2) Operate each indoor unit one by one and make sure the correspond-

ing outside unit is also operating.

(3) Check to see if cold (or hot) air is coming out from the indoor unit.
(4) Push the fan direction and strength buttons on the remote controller 

to see if they operate properly.

NOTE

Heating is not possible if the outdoor temperature is 75°F or higher. 
Refer to the Operation manual.

If a knocking sound can be heard in the liquid compression of the com-
pressor, stop the unit immediately and then energize the crank case 
heater for a sufficient length of time before restarting the operation.

Once stopping, the compressor will not restart in about 5 minutes 
even if the On/Off button of the remote controller is pushed.

When the system operation is stopped by the remote controller, the out-
side units may continue operating for further 5 minutes at maximum.

The outside unit fan may rotate at low speeds if the Night-time low 
noise setting or the External low noise level setting is made, but this 
is not a malfunction.

If the check operation was not performed at first istallation, the malfunc-
tion code “U3” will be displayed in the remote controller. Perform the 
check operation following 

“11-2-2 Procedure of Check Operation”

.

13-3 Checks After Test Run

Perform the following checks after the test run is complete.

Record the contents of field setting.

Record them on the accessory “REQUEST FOR THE INDICA-
TION” label.
And attach the label on the back side of the front panel.

Record the installation date.

Record the installation date on the accessory “REQUEST FOR 
THE INDICATION” label in accordance with the IEC60335-2-40.
And attach the label on the back side of the front panel.

NOTE

After the test run, when handing the unit over to the customer, make 
sure the EL.COMPO.BOX lid, the inspection door, and the unit casing 
are all attached.

Malfunc-
tion code

Installation error

Remedial action

E3, E4
F3, F6
UF

The shutoff valve of the outside 
unit is left closed.

Open the shutoff valve.

U1

The phases of the power to 
the outside unit is reversed.

Exchange two of the three phases (L1, 
L2, L3) to make a proper connection.

U1
U4
LC

No power is supplied to an 
outside, BS or indoor unit 
(including phase interruption).

Make sure the power source wire is 
properly connected to the outside , BS or 
indoor unit and revise if necessary.

UF

There is conflict on the con-
nection of transmission wir-
ing in the system.

Check if the refrigerant piping line and 
the transmission wiring are consistent 
with each other.

E3
F6
UF

Refrigerant overcharge.

Recalculate the additional amount refrig-
erant from the piping length and correct 
the refrigerant charge level by recovering 
any excessive refrigerant with a refriger-
ant recovery machine.

E4
F3

Insufficient refrigerant.

Check if the additional refrigerant 
charge has been finished correctly.

Recalculate the additional amount 
refrigerant from the piping length and 
add the adequate amount.

U7, U4
UF, UH

Field wiring is connected to "TO 
MULTI UNIT (Q1,Q2)" terminal 
on the outside unit PC-board 
(A1P) when the system is one 
outdoor system.

Remove the line from the “TO MULTI UNIT 
(Q1, Q2)” terminal.

01_EN_3P215731-2.fm  Page 18  Tuesday, December 4, 2007  12:04 PM

Summary of Contents for RXYQ120PYDN

Page 1: ...INSTALLATION MANUAL System air conditioner RXYQ72PYDN RXYQ96PYDN RXYQ120PYDN RXYQ144PYDN RXYQ168PYDN RXYQ192PYDN RXYQ216PYDN RXYQ240PYDN English Fran ais Espa ol...

Page 2: ...8 11 3 4 Pattern 3 2 1 2 1 60 3 1 4 2 5 2 in 40 4 0 40 6 0 60 60 figure 1 figure 3 figure 2 4 1 2 3 1 1 2 3 7 8 3 7 8 3 7 8 5 3 7 8 3 7 8 3 7 8 1 2 3 4 5 figure 4 figure 6 figure 5 A B 1 4 3 2 30 1 8...

Page 3: ...4 1 5 2 B 1 2 1 1 1 1 5 16 1 16 2 16 3 6 2 3 4 4 C D 7 8 3 4 6 7 1 1 2 3 4 5 2 1 4 3 2 1 3 1 1 2 6 1 2 7 5 TOIN DUNIT F1 F2 TOOUT DUNIT F1 F2 TOMULTIUNIT Q1 Q2 A1P TOMULTIUNIT Q1 Q2 2 4 A1P 8 F1 F2 F1...

Page 4: ...re 30 figure 32 figure 28 figure 24 1 2 3 4 5 6 7 8 9 10 12 11 1 2 3 4 5 6 7 8 9 10 13 15 15 16 F17 11 12 19 20 14 18 1 2 1 2 3 1 2 3 4 5 1 2 2 3 5 6 4 1 2 3 4 10 13 11 5 6 7 8 9 12 15 16 17 18 14 1 2...

Page 5: ...ired to take adequate measures Meaning of danger warning caution and note symbols DANGER Indicates an imminently hazardous situa tion which if not avoided will result in death or serious injury WARNIN...

Page 6: ...e may occur Do not use a charging cylinder Using a charging cylinder may cause the refrigerant to deteriorate The refrigerant R410A requires strict cautions for keeping the system clean dry and tight...

Page 7: ...he storage location of the accessories is shown in figure 1 NOTE Do not throw away any of the accessories until installation is complete They are needed for installation work Refer to figure 1 1 Clamp...

Page 8: ...HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the carrier claims agent When handling the unit take into account the following 1 Fragile...

Page 9: ...s when brazing the pipe joints Residue can clog pipes and break equipment 6 4 Connecting the refrigerant piping 1 Direction to bring out the pipes The local inter unit piping can be connected either f...

Page 10: ...anual 1 About outside unit multi connection piping kit Install the joint horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 16 1 Do not install v...

Page 11: ...stall the REFNET header so it splits horizontally Refer to figure 15 1 Horizontal surface 2 B arrow view Prohibited pattern Oil remains in the stopping outside unit Change to pattern 1 or pattern 2 Fr...

Page 12: ...0 ft Example 6 a b h 540 ft 8 a i j 540 ft Example 8 a i 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length of REFNET joint to be 1 6 ft th...

Page 13: ...t total capacity index 72 72 111 111 Number of outside unit 2 units Connecting piping kit name BHFP22P100U Refrigerant branch kit name KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Example for indoor...

Page 14: ...249 0 121 0 040 0 175 0 081 0 015 HEAT PUMP SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT RXYQ72 120PYDN RXYQ144 192PYDN RXYQ216 240PYDN 2 2 lb 3 3 lb REFRIGERANT AMOUNT FOR EXCEEDING CONNECTION CAPACI...

Page 15: ...ing and earth terminal If there exists the possibility of reversed phase lose phase momen tary blackout or the power goes on and off while the product is oper ating attach a reversed phase protection...

Page 16: ...d of the master unit The outside unit that connected transmission wiring to indoor unit is the master unit The others are sub unit 7 5 Power Wiring Connection Procedure Be sure to connect the power su...

Page 17: ...shipped the unit contains the refrigerant so use caution when attaching the charge hose Air tight test Pressurize the liquid pipe suction gas pipe HP LP gas pipe and equalizer pipe from the service po...

Page 18: ...d it may require additional charging For charging the additional refrigerant follow the procedure in this chapter And then carry out the check operation 11 1 Before working About the refrigerant tank...

Page 19: ...oor and outside units are turned on H2P will be lit on and the compressor will not operate Check the LED display indicate as shown below In order to ensure uniform refrigerant distribution it may take...

Page 20: ...cedure During Automatic refrigerant charging operation the system will select charging mode cooling mode or heating mode by the tem perature condition as follows When charging in cooling mode the syst...

Page 21: ...ion valve and the valve are closed when charging is finished However the valve will opened when ather operation Check operation nomal operation etc If you leave the tank connected the refrigerant will...

Page 22: ...possible if the outdoor temperature is 75 F or higher Refer to the Operation manual If a knocking sound can be heard in the liquid compression of the com pressor stop the unit immediately and then ene...

Page 23: ...y to comply 1 Calculate the amount of refrigerant lb charged to each system sep arately NOTE Where a single refrigerant facility is divided into 2 entirely indepen dent refrigerant systems then use th...

Page 24: ...20 English NOTES...

Page 25: ...3P215731 2 EM07A038 0712 FS 1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com HT...

Reviews: