background image

English

11

7.

FIELD WIRING

NOTE

All field wiring and components must be installed by a licensed elec-
trician and must comply with relevant local and national regulations.

Be sure to use a dedicated power circuit. Never use a power supply 
shared by another appliance.

Never install a phase advancing capacitor. As this unit is equipped 
with an inverter, installing a phase advancing capacitor will not only 
deteriorate power factor improvement effect, but also may cause 
capacitor abnormal heating accident due to high-frequency waves.

Only proceed with wiring work after blocking off all power.

Always ground wires in accordance with relevant local and national 
regulations.

This machine includes an inverter device. Connect earth and leave 
charge to eliminate the impact on other devices by reducing noise 
generated from the inverter device and to prevent leaked current 
from being charged in the outer hull of the product.

Do not connect the ground wire to gas pipes, sewage pipes, lightning 
rods, or telephone ground wires.

Gas pipes :

 can explode or catch fire if there is a gas leak.

Sewage pipes :

 no grounding effect is possible if hard plastic piping 

is used.

Telephone ground wires and lightning rods :

 dangerous when 

struck by lightning due to abnormal rise in electrical potential in the 
grounding.

Be sure to install an earth leakage circuit breaker.
This unit uses an inverter, so install the earth leakage circuit breaker 
that be capable of handling high harmonics in order to prevent mal-
functioning of the earth leakage circuit breaker itself.

Earth leakage circuit breaker which are especially for protecting 
ground-faults should be used in conjunction with main switch or fuse 
for use with wiring.

Electrical wiring must be done in accordance with the wiring dia-
grams and the description herein.

Do not operate until refrigerant piping work is completed.
(If operated before complete the piping work, the compressor may 
be broken down.)

Never remove thermistor, sensor or etc. when connecting power wir-
ing and transmission wiring.
(If operated with thermistor, sensor or etc. removed, the compressor 
may be broken down.)

This product have reversed phase protection detector that only 
works when the power is turned on. If there exists blackout or the 
power goes on and off which the product is operating, attach a 
reversed phase protection circuit locally. Running the product in 
reversed phase may break the compressor and other parts.

Attach the power wire securely. Introducing power with a missing N-
phase or with a mistaken N-phase will break the unit.

Never connect the power supply in reversed phase. 
The unit can not operate normally in reversed phase.
If you connect in reversed phase, replace two of the three phases.

Make sure the electrical unbalance ratio is no greater than 2%. If it is 
larger than this, the unit’s lifespan will be reduced.
If the ratio exceeds 4%, the unit will shut down and an malfunction 
code will be displayed on the indoor remote controller.

Connect the wire securely using designated wire and fix it with attached 
clamp without applying external pressure on the terminal parts (terminal 
for power wiring, terminal for transmission wiring and earth terminal).

If there exists the possibility of reversed phase, lose phase, momen-
tary blackout or the power goes on and off while the product is oper-
ating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor 
and other parts.

7-1 Power circuit, safety device and cable

requirements

A power circuit (see the following table) must be provided for connec-
tion of the unit. This circuit must be protected with the required safety 
devices, i.e. a main switch, a slow blow fuse on each phase and an 
earth leakage circuit breaker.

When using residual current operated circuit breakers, be sure to 
use a high-speed type (0.1 second or less) 200mA rated residual 
operating current.

Use copper conductors only.

Use insulated wire for the power cord.

Select the power supply cable type and size in accordance with rel-
evant local and national regulations.

Specifications for local wiring power cord and branch wiring are in 
compliance with local cord.

7-2 Wiring Connection Example for Whole System

(Refer to figure 17)

1.

Power supply

2.

Main switch

3.

Earth leakage circuit breaker

4.

Fuse

5.

Outside unit

6.

Remote controller

7.

Indoor unit

NOTE

Make sure the weak electric wiring (i.e. for the remote controller, between 
units, etc.) and the power wiring do not pass near each other, keeping 
them at least 2 in. apart.
Proximity may cause electrical interference, malfunctions, and breakage.

Be sure to connect the power wiring to the power wiring terminal 
block and secure it as described in “

7-5 Power Wiring Connection 

Procedure

”.

Transmission wiring should be secured as described in “

7-4 Trans-

mission Wiring Connection Procedure

”.

Secure wiring with clamp such as insulation lock ties to avoid contact 
with piping.

Shape the wires to prevent the structure such as the EL. COMPO. 
BOX lid deforming. And close the cover firmly.

All field wiring is to be procured on site.

7-3 Leading wire Procedure

The power wiring and ground wiring are passed out from the power 
wiring hole on the sides, the front (knock hole) or the bottom frame 
(knock hole) .

The transmission wiring is passed out from the wiring hole (knock 
hole) on the front of the unit or from a piping hole.

(Refer to figure 18-1)

1.

Electric wiring diagram
Printed on the back of the electric parts box lid.

2.

Knockout hole

3.

Power line

4.

Transmission line

(Refer to figure 18-2)

1.

Electric box lid

2.

Service lid

3.

[Service precautions] Label location

NOTE

Open the knock holes with a hammer or the like.

After knocking out the holes, we recommend you remove any burrs and 
paint them using the repair paint to prevent rusting. 

(Refer to figure 18)

When passing wiring through the knock holes, remove burrs around 
the knock holes and protect the wiring with protective tape. 

(Refer to 

figure 18)

If small animals might enter the unit, block off any gaps (hatching 
parts in figure 18) with material (field supply).

Phase and

frequency Voltage

Minimum

circuit amp.

Recom-

mended fuses

Transmission 

line selection

RXYQ72P type

φ

 3, 60Hz

460V

20.2A

25A

AWG18-16

RXYQ96P type

φ

 3, 60Hz

460V

20.3A

25A

AWG18-16

RXYQ120P type

φ

 3, 60Hz

460V

20.5A

30A

AWG18-16

RXYQ144P type

φ

 3, 60Hz

460V

40.4A

25A+25A

AWG18-16

RXYQ168P type

φ

 3, 60Hz

460V

40.5A

25A+25A

AWG18-16

RXYQ192P type

φ

 3, 60Hz

460V

40.7A

25A+30A

AWG18-16

RXYQ216P type

φ

 3, 60Hz

460V

40.8A

25A+30A

AWG18-16

RXYQ240P type

φ

 3, 60Hz

460V

41.0A

30A+30A

AWG18-16

01_EN_3P215731-2.fm  Page 11  Tuesday, December 4, 2007  12:04 PM

Summary of Contents for RXYQ120PYDN

Page 1: ...INSTALLATION MANUAL System air conditioner RXYQ72PYDN RXYQ96PYDN RXYQ120PYDN RXYQ144PYDN RXYQ168PYDN RXYQ192PYDN RXYQ216PYDN RXYQ240PYDN English Fran ais Espa ol...

Page 2: ...8 11 3 4 Pattern 3 2 1 2 1 60 3 1 4 2 5 2 in 40 4 0 40 6 0 60 60 figure 1 figure 3 figure 2 4 1 2 3 1 1 2 3 7 8 3 7 8 3 7 8 5 3 7 8 3 7 8 3 7 8 1 2 3 4 5 figure 4 figure 6 figure 5 A B 1 4 3 2 30 1 8...

Page 3: ...4 1 5 2 B 1 2 1 1 1 1 5 16 1 16 2 16 3 6 2 3 4 4 C D 7 8 3 4 6 7 1 1 2 3 4 5 2 1 4 3 2 1 3 1 1 2 6 1 2 7 5 TOIN DUNIT F1 F2 TOOUT DUNIT F1 F2 TOMULTIUNIT Q1 Q2 A1P TOMULTIUNIT Q1 Q2 2 4 A1P 8 F1 F2 F1...

Page 4: ...re 30 figure 32 figure 28 figure 24 1 2 3 4 5 6 7 8 9 10 12 11 1 2 3 4 5 6 7 8 9 10 13 15 15 16 F17 11 12 19 20 14 18 1 2 1 2 3 1 2 3 4 5 1 2 2 3 5 6 4 1 2 3 4 10 13 11 5 6 7 8 9 12 15 16 17 18 14 1 2...

Page 5: ...ired to take adequate measures Meaning of danger warning caution and note symbols DANGER Indicates an imminently hazardous situa tion which if not avoided will result in death or serious injury WARNIN...

Page 6: ...e may occur Do not use a charging cylinder Using a charging cylinder may cause the refrigerant to deteriorate The refrigerant R410A requires strict cautions for keeping the system clean dry and tight...

Page 7: ...he storage location of the accessories is shown in figure 1 NOTE Do not throw away any of the accessories until installation is complete They are needed for installation work Refer to figure 1 1 Clamp...

Page 8: ...HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the carrier claims agent When handling the unit take into account the following 1 Fragile...

Page 9: ...s when brazing the pipe joints Residue can clog pipes and break equipment 6 4 Connecting the refrigerant piping 1 Direction to bring out the pipes The local inter unit piping can be connected either f...

Page 10: ...anual 1 About outside unit multi connection piping kit Install the joint horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 16 1 Do not install v...

Page 11: ...stall the REFNET header so it splits horizontally Refer to figure 15 1 Horizontal surface 2 B arrow view Prohibited pattern Oil remains in the stopping outside unit Change to pattern 1 or pattern 2 Fr...

Page 12: ...0 ft Example 6 a b h 540 ft 8 a i j 540 ft Example 8 a i 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length of REFNET joint to be 1 6 ft th...

Page 13: ...t total capacity index 72 72 111 111 Number of outside unit 2 units Connecting piping kit name BHFP22P100U Refrigerant branch kit name KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Example for indoor...

Page 14: ...249 0 121 0 040 0 175 0 081 0 015 HEAT PUMP SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT RXYQ72 120PYDN RXYQ144 192PYDN RXYQ216 240PYDN 2 2 lb 3 3 lb REFRIGERANT AMOUNT FOR EXCEEDING CONNECTION CAPACI...

Page 15: ...ing and earth terminal If there exists the possibility of reversed phase lose phase momen tary blackout or the power goes on and off while the product is oper ating attach a reversed phase protection...

Page 16: ...d of the master unit The outside unit that connected transmission wiring to indoor unit is the master unit The others are sub unit 7 5 Power Wiring Connection Procedure Be sure to connect the power su...

Page 17: ...shipped the unit contains the refrigerant so use caution when attaching the charge hose Air tight test Pressurize the liquid pipe suction gas pipe HP LP gas pipe and equalizer pipe from the service po...

Page 18: ...d it may require additional charging For charging the additional refrigerant follow the procedure in this chapter And then carry out the check operation 11 1 Before working About the refrigerant tank...

Page 19: ...oor and outside units are turned on H2P will be lit on and the compressor will not operate Check the LED display indicate as shown below In order to ensure uniform refrigerant distribution it may take...

Page 20: ...cedure During Automatic refrigerant charging operation the system will select charging mode cooling mode or heating mode by the tem perature condition as follows When charging in cooling mode the syst...

Page 21: ...ion valve and the valve are closed when charging is finished However the valve will opened when ather operation Check operation nomal operation etc If you leave the tank connected the refrigerant will...

Page 22: ...possible if the outdoor temperature is 75 F or higher Refer to the Operation manual If a knocking sound can be heard in the liquid compression of the com pressor stop the unit immediately and then ene...

Page 23: ...y to comply 1 Calculate the amount of refrigerant lb charged to each system sep arately NOTE Where a single refrigerant facility is divided into 2 entirely indepen dent refrigerant systems then use th...

Page 24: ...20 English NOTES...

Page 25: ...3P215731 2 EM07A038 0712 FS 1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com HT...

Reviews: