background image

12

English

7-4 Transmission Wiring Connection Procedure

Referring to figure 19 connect the transmission wiring between out-
side unit and indoor unit, outside unit and outside unit of other sys-
tem, outside unit and outside unit of same system.

(Refer to figure 19)

1.

Master unit (*)

2.

Sub unit (*)

3.

Outside unit A

4.

Outside unit B

5.

Never connect the power wire.

6.

To outside unit of other system

7.

Use duplex wires (No polarity)

8.

Indoor unit

(*) : The Outside unit that connect the transmission wiring to BS 

unit is Master unit of the multi system.
And the other units are Sub unit. (In this figure, Outside unit 
A is the Master unit.)
Check operation in installation work, Onsite settings and so 
on are done by operating the PC-board (A1P) of Master unit.

NOTE

Do not connect the power wiring to terminals for the transmission 
wiring. Doing so would destroy the entire system.

When connecting wires to the terminal block on the PC-board, too 
much heat or tightening could damage the PC-board. Attach with care.
See the table below for the tightening torque of the transmission wiring 
terminals.

Transmission wiring (About the symbol 

 ~ 

see figure 19

should be done within the following limitations.
If they are exceeded, transmission problems may occur.

 Between outside unit and BS (or indoor) unit

Between BS unit and indoor unit
Between outside unit and outside unit of other systems

Max. wiring length

: 3280 ft

Max. total wiring length

: 6560 ft

Max. no. of branches

: 16

[Note] 
No branch is allowed after branch (

See figure 20

)

Max. no. of outside units of other system 
that can be connected

: 10

(Refer to figure 20)

1.

Branch

2.

Branch after branch

 Between outside unit and outside unit of  same system

Max. wiring length

: 100 ft

The transmission wiring inside the EL.COMPO.BOX should be 
secured using the clamp (1) as shown in figure 21.

(Refer to figure 21)

1.

In the EL.COMPO.BOX

2.

Retain to the EL.COMPO.BOX with the accessory clamp (1).

Outside the units, the transmission wiring must be finished simulta-
neously with the local refrigerant piping, and wound with tape (field 
supply) as shown in figure 22.

(Refer to figure 22)

1.

Liquid pipe

2.

Gas pipe

3.

Transmission wiring

4.

Insulation material

5.

Finishing tape

For multi system:
1. Transmission wiring between outside units in the same piping sys-

tem must be connected to terminals Q1 and Q2 (TO MULTI UNIT).
Connecting the wires to the F1, F2 (TO OUT/D UNIT) terminals 
results in system malfunction.

2. Wiring to other systems should be connected to terminals F1 and 

F2 (TO OUT/D UNIT) on the PC-board of the master unit. The 
outside unit that connected transmission wiring to indoor unit is 
the master unit. The others are sub unit.

7-5 Power Wiring Connection Procedure

Be sure to connect the power supply wiring to the power supply ter-
minal block and hold it in place using the included clamp as shown in 
the figure 23.

The L1, L2, L3 and N phases of the power wiring should be secured 
separately to the hook using the included clamp (1).

The ground wiring should be bound to the power wiring using the 
included clamp (1) to prevent outside force from being applied to the 
terminal area.

(Refer to figure 23)

1.

Power supply (3 ~ 460V 60Hz)

2.

Earth leakage circuit breaker

3.

Branch switch, Overcurrent breaker

4.

Ground wire

5.

Attach insulation sleeves

6.

Power supply terminal block

7.

Ground terminal

8.

Clamp (1) (accessory)

CAUTION

Be sure to use crimp-style terminal with insulating sleeves for con-
nections. (See the figure below.)

For wiring, use the designated power wire and connect firmly, then 
secure to prevent outside pressure being exerted on the terminal board.

Use an appropriate screwdriver for tightening the terminal screws. A 
screwdriver with a small head will strip the head and make proper 
tightening impossible.

Over-tightening the terminal screws may break them.
See the following table for the tightening torque of the terminal screws.

When pulling the ground wire out, wire it so that it comes through the 
cut out section of the cup washer. (See the figure below.) An improper 
ground connection may prevent a good ground from being achieved.

When two wires are connected to a single terminal, connect them so 
that the rear sides of the crimp contacts face each other. Also, make 
sure the thinner wire is on top, securing the two wires simultaneously 
to the resin hook using the included clamp (1).

7-6 Procedure for Wiring Inside Units

Referring to figure 24, secure and wire the power and transmission 
wiring using the included clamp (1), (2), and (3).

Wire so that the ground wiring does not come into contact with the 
compressor lead wiring.
If they touch, this may have an adverse effect on other devices.

The transmission wiring must be at least 2 in. away from the power wiring.

Make sure all wiring do not contact to the pipes (hatching parts in the 
figure 24).

(Refer to figure 24)

1.

Retain with accessory clamp (3).

2.

Electric conduit

3.

When routing out the power/ground wires from the left side.

Screw size

Tightening torque (ft · lbf)

M3.5 (A1P)

0.59 ~ 0.71

1

2

1

2

Screw size

Tightening torque (ft · lbf)

M8 Power terminal, ground terminal

4.06 ~ 5.38

Power wire

Crimp-style terminal

Insulating sleeve

Crimp-style terminal

Cup washer

Cut out section 

Terminal 
block

Crip style 
terminal

Wire : narrow

Wire : thick

Resin hook

01_EN_3P215731-2.fm  Page 12  Tuesday, December 4, 2007  12:04 PM

Summary of Contents for RXYQ120PYDN

Page 1: ...INSTALLATION MANUAL System air conditioner RXYQ72PYDN RXYQ96PYDN RXYQ120PYDN RXYQ144PYDN RXYQ168PYDN RXYQ192PYDN RXYQ216PYDN RXYQ240PYDN English Fran ais Espa ol...

Page 2: ...8 11 3 4 Pattern 3 2 1 2 1 60 3 1 4 2 5 2 in 40 4 0 40 6 0 60 60 figure 1 figure 3 figure 2 4 1 2 3 1 1 2 3 7 8 3 7 8 3 7 8 5 3 7 8 3 7 8 3 7 8 1 2 3 4 5 figure 4 figure 6 figure 5 A B 1 4 3 2 30 1 8...

Page 3: ...4 1 5 2 B 1 2 1 1 1 1 5 16 1 16 2 16 3 6 2 3 4 4 C D 7 8 3 4 6 7 1 1 2 3 4 5 2 1 4 3 2 1 3 1 1 2 6 1 2 7 5 TOIN DUNIT F1 F2 TOOUT DUNIT F1 F2 TOMULTIUNIT Q1 Q2 A1P TOMULTIUNIT Q1 Q2 2 4 A1P 8 F1 F2 F1...

Page 4: ...re 30 figure 32 figure 28 figure 24 1 2 3 4 5 6 7 8 9 10 12 11 1 2 3 4 5 6 7 8 9 10 13 15 15 16 F17 11 12 19 20 14 18 1 2 1 2 3 1 2 3 4 5 1 2 2 3 5 6 4 1 2 3 4 10 13 11 5 6 7 8 9 12 15 16 17 18 14 1 2...

Page 5: ...ired to take adequate measures Meaning of danger warning caution and note symbols DANGER Indicates an imminently hazardous situa tion which if not avoided will result in death or serious injury WARNIN...

Page 6: ...e may occur Do not use a charging cylinder Using a charging cylinder may cause the refrigerant to deteriorate The refrigerant R410A requires strict cautions for keeping the system clean dry and tight...

Page 7: ...he storage location of the accessories is shown in figure 1 NOTE Do not throw away any of the accessories until installation is complete They are needed for installation work Refer to figure 1 1 Clamp...

Page 8: ...HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the carrier claims agent When handling the unit take into account the following 1 Fragile...

Page 9: ...s when brazing the pipe joints Residue can clog pipes and break equipment 6 4 Connecting the refrigerant piping 1 Direction to bring out the pipes The local inter unit piping can be connected either f...

Page 10: ...anual 1 About outside unit multi connection piping kit Install the joint horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 16 1 Do not install v...

Page 11: ...stall the REFNET header so it splits horizontally Refer to figure 15 1 Horizontal surface 2 B arrow view Prohibited pattern Oil remains in the stopping outside unit Change to pattern 1 or pattern 2 Fr...

Page 12: ...0 ft Example 6 a b h 540 ft 8 a i j 540 ft Example 8 a i 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length of REFNET joint to be 1 6 ft th...

Page 13: ...t total capacity index 72 72 111 111 Number of outside unit 2 units Connecting piping kit name BHFP22P100U Refrigerant branch kit name KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Example for indoor...

Page 14: ...249 0 121 0 040 0 175 0 081 0 015 HEAT PUMP SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT RXYQ72 120PYDN RXYQ144 192PYDN RXYQ216 240PYDN 2 2 lb 3 3 lb REFRIGERANT AMOUNT FOR EXCEEDING CONNECTION CAPACI...

Page 15: ...ing and earth terminal If there exists the possibility of reversed phase lose phase momen tary blackout or the power goes on and off while the product is oper ating attach a reversed phase protection...

Page 16: ...d of the master unit The outside unit that connected transmission wiring to indoor unit is the master unit The others are sub unit 7 5 Power Wiring Connection Procedure Be sure to connect the power su...

Page 17: ...shipped the unit contains the refrigerant so use caution when attaching the charge hose Air tight test Pressurize the liquid pipe suction gas pipe HP LP gas pipe and equalizer pipe from the service po...

Page 18: ...d it may require additional charging For charging the additional refrigerant follow the procedure in this chapter And then carry out the check operation 11 1 Before working About the refrigerant tank...

Page 19: ...oor and outside units are turned on H2P will be lit on and the compressor will not operate Check the LED display indicate as shown below In order to ensure uniform refrigerant distribution it may take...

Page 20: ...cedure During Automatic refrigerant charging operation the system will select charging mode cooling mode or heating mode by the tem perature condition as follows When charging in cooling mode the syst...

Page 21: ...ion valve and the valve are closed when charging is finished However the valve will opened when ather operation Check operation nomal operation etc If you leave the tank connected the refrigerant will...

Page 22: ...possible if the outdoor temperature is 75 F or higher Refer to the Operation manual If a knocking sound can be heard in the liquid compression of the com pressor stop the unit immediately and then ene...

Page 23: ...y to comply 1 Calculate the amount of refrigerant lb charged to each system sep arately NOTE Where a single refrigerant facility is divided into 2 entirely indepen dent refrigerant systems then use th...

Page 24: ...20 English NOTES...

Page 25: ...3P215731 2 EM07A038 0712 FS 1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com HT...

Reviews: