3

A. Clean and dry

Foreign materials (including mineral oils such as SUNISO oil or 
moisture) should be prevented from getting mixed into the system.

B. Tight

Take care to keep the system tight when installing.
R410A does not contain any chlorine, does not destroy the ozone 
layer, and does not reduce the earth’s protection against harmful 
ultraviolet radiation.
R410A can contribute slightly to the greenhouse effect if it is 
released.

Since R410A is a mixed refrigerant, the required additional refrigerant 
must be charged in its liquid state. If the refrigerant is charged in a state 
of gas, its composition changes and the system will not work properly.

[DESIGN PRESSURE]

Since design pressure is 478 psi, the wall thickness of pipes should be 
more carefully selected in accordance with the relevant local and 
national regulations.

1-3 Disposal requirements

Dismantling of the unit,  treatment of the refrigerant, oil and eventual 
other parts, should be done in accordance with the relevant local and 
national regulations.

2.

INTRODUCTION

RXYQ-P series are designed for outdoor installation and used for 
cooling and heating applications.

The indoor units that combined with RXYQ-P system for air condi-
tioning are Daikin VRV series indoor units that compatible with 
R410A. To learn which indoor units are compatible with R410A, refer 
to the product catalogs. To combine with other refrigerant indoor unit 
will cause malfunction.

2-1 Combination

The system name and that independent units are as follows.

The system name

〉             〈

Independent units

RXYQ72PYDN .............. RXYQ72PYDN
RXYQ96PYDN .............. RXYQ96PYDN
RXYQ120PYDN ............ RXYQ120PYDN
RXYQ144PYDN ............ RXYQ72PYDN

RXYQ72PYDN

RXYQ168PYDN ............ RXYQ72PYDN

RXYQ96PYDN

RXYQ192PYDN ............ RXYQ72PYDN

RXYQ120PYDN

RXYQ216PYDN ............ RXYQ96PYDN

RXYQ120PYDN

RXYQ240PYDN ............ RXYQ120PYDN

RXYQ120PYDN

The indoor units can be installed in the following range.

Outside unit

〉                  〈

Total capacity index of indoor units

RXYQ72PYDN .............. 36 ~ 93.5
RXYQ96PYDN .............. 48 ~ 124.5
RXYQ120PYDN ............ 60 ~ 156
RXYQ144PYDN ............ 72 ~ 187
RXYQ168PYDN ............ 84 ~ 218
RXYQ192PYDN ............ 96 ~ 249.5
RXYQ216PYDN ............ 108 ~ 280.5
RXYQ240PYDN ............ 120 ~ 312

For installing the 2 units multi system, Outside unit multi connection 
piping kit "BHFP22P100U" are required.

If the total capacity of the connected indoor units exceeds the capac-
ity of the outside unit, cooling and heating performance may drop 
when running the indoor units. See the capacity table in the Engi-
neering Data Book for details.

2-2 Standard supplied accessories

Confirm the following accessories are included. The storage location of 
the accessories is shown in figure 1.

NOTE

Do not throw away any of the accessories until installation is complete. 
They are needed for installation work.

(Refer to figure 1)

1.

Clamps, Manuals, etc.

2.

Accessory pipes

2-3 Option accessory

To install the outside units, the following optional parts are also required. 
To select an optimum kit, refer to “

6. REFRIGERANT PIPING

”.

Outside unit multi connection piping kit

Refrigerant branching kit 

Make sure that any separately purchased accessories are designed for 
use with R410A.

2-4 Technical and Electrical specifications

Refer to the Engineering Data Book for the complete list of specifications.

2-5 Main components

For main components and function of the main components, refer to the 
Engineering Data Book.

3.

SELECTION OF LOCATION

Select a location for installation that meets the following conditions and 
get the customer’s permission.

1.

Select the location of the unit in such a way that neither the dis-
charged air nor the sound generated by the unit disturb anyone.

2.

The foundation is strong enough to support the weight of the unit and 
the floor is flat to prevent vibration and noise generation.

3.

The piping length between the outside unit and the indoor unit may 
not exceed the allowable piping length.
(Refer to

  “6. REFRIGERANT PIPING”

)

4.

Locations where the unit’s suction vent and outlet vent do not gener-
ally face the wind.
Wind blowing directly into the suction or outlet vents will interfere with 
the unit’s operation.
If necessary, install some kind of obstruction to block the wind.

5.

The space around the unit is adequate for servicing and the mini-
mum space for air inlet and air outlet is available.
(See the 

“Installation Space Examples”

 for the minimum space 

requirements.)

Number of outside units connected

2 units

Kit name

BHFP22P100U

REFNET header KHRP26M22H KHRP26M33H KHRP26M72H

REFNET joint

KHRP26M22T

KHRP26M33T

KHRP26M72TU KHRP26M73TU

Shape

Liquid side
accessory
pipe (1)

High side
equalizer
accessory
pipe (1)

High side
equalizer
accessory
pipe (2)

Low side
equalizer
accessory
pipe (1)

Low side
equalizer
accessory
pipe (2)

L type
accessory
joint (1)

L type
accessory
joint (2)

Liquid side
accessory
pipe (2)

Gas side accessory pipe (1)

Gas side accessory
pipe (2)

1 pc.

1 pc.

1 pc.

72P type

Quantity

Shape

Name

Name

2 pcs.

96P type

72P type

96P type

120P type

120P type

1 pc.

1 pc.

1 pc.

1 pc.

Quantity

1 pc.

1 pc.

1 pc.

1 pc.

1 pc.

1 pc.

φ

3/4

φ

7/8

O.D 

φ

1

I.D 

φ

1

φ

1

φ

1-1/8

φ

7/8

φ

1

φ

3/4

φ

1

φ

3/4

2 pcs.

1 pc.

1 pc. about each item

Clamp(1)

(Large)

9 pcs.

Clamp(2)

(Small)

Quantity

Clamp(3)

Name

Manuals, etc.

Shape

 Operation manual

 Installation manual

 "REQUEST FOR THE INDICATON" 

label (Installation records)

 "ADDITIONAL REF. CHARGE" label

01_EN_3P215731-2.fm  Page 3  Tuesday, December 4, 2007  12:04 PM

Summary of Contents for RXYQ120PYDN

Page 1: ...INSTALLATION MANUAL System air conditioner RXYQ72PYDN RXYQ96PYDN RXYQ120PYDN RXYQ144PYDN RXYQ168PYDN RXYQ192PYDN RXYQ216PYDN RXYQ240PYDN English Fran ais Espa ol...

Page 2: ...8 11 3 4 Pattern 3 2 1 2 1 60 3 1 4 2 5 2 in 40 4 0 40 6 0 60 60 figure 1 figure 3 figure 2 4 1 2 3 1 1 2 3 7 8 3 7 8 3 7 8 5 3 7 8 3 7 8 3 7 8 1 2 3 4 5 figure 4 figure 6 figure 5 A B 1 4 3 2 30 1 8...

Page 3: ...4 1 5 2 B 1 2 1 1 1 1 5 16 1 16 2 16 3 6 2 3 4 4 C D 7 8 3 4 6 7 1 1 2 3 4 5 2 1 4 3 2 1 3 1 1 2 6 1 2 7 5 TOIN DUNIT F1 F2 TOOUT DUNIT F1 F2 TOMULTIUNIT Q1 Q2 A1P TOMULTIUNIT Q1 Q2 2 4 A1P 8 F1 F2 F1...

Page 4: ...re 30 figure 32 figure 28 figure 24 1 2 3 4 5 6 7 8 9 10 12 11 1 2 3 4 5 6 7 8 9 10 13 15 15 16 F17 11 12 19 20 14 18 1 2 1 2 3 1 2 3 4 5 1 2 2 3 5 6 4 1 2 3 4 10 13 11 5 6 7 8 9 12 15 16 17 18 14 1 2...

Page 5: ...ired to take adequate measures Meaning of danger warning caution and note symbols DANGER Indicates an imminently hazardous situa tion which if not avoided will result in death or serious injury WARNIN...

Page 6: ...e may occur Do not use a charging cylinder Using a charging cylinder may cause the refrigerant to deteriorate The refrigerant R410A requires strict cautions for keeping the system clean dry and tight...

Page 7: ...he storage location of the accessories is shown in figure 1 NOTE Do not throw away any of the accessories until installation is complete They are needed for installation work Refer to figure 1 1 Clamp...

Page 8: ...HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the carrier claims agent When handling the unit take into account the following 1 Fragile...

Page 9: ...s when brazing the pipe joints Residue can clog pipes and break equipment 6 4 Connecting the refrigerant piping 1 Direction to bring out the pipes The local inter unit piping can be connected either f...

Page 10: ...anual 1 About outside unit multi connection piping kit Install the joint horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 16 1 Do not install v...

Page 11: ...stall the REFNET header so it splits horizontally Refer to figure 15 1 Horizontal surface 2 B arrow view Prohibited pattern Oil remains in the stopping outside unit Change to pattern 1 or pattern 2 Fr...

Page 12: ...0 ft Example 6 a b h 540 ft 8 a i j 540 ft Example 8 a i 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length of REFNET joint to be 1 6 ft th...

Page 13: ...t total capacity index 72 72 111 111 Number of outside unit 2 units Connecting piping kit name BHFP22P100U Refrigerant branch kit name KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Example for indoor...

Page 14: ...249 0 121 0 040 0 175 0 081 0 015 HEAT PUMP SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT RXYQ72 120PYDN RXYQ144 192PYDN RXYQ216 240PYDN 2 2 lb 3 3 lb REFRIGERANT AMOUNT FOR EXCEEDING CONNECTION CAPACI...

Page 15: ...ing and earth terminal If there exists the possibility of reversed phase lose phase momen tary blackout or the power goes on and off while the product is oper ating attach a reversed phase protection...

Page 16: ...d of the master unit The outside unit that connected transmission wiring to indoor unit is the master unit The others are sub unit 7 5 Power Wiring Connection Procedure Be sure to connect the power su...

Page 17: ...shipped the unit contains the refrigerant so use caution when attaching the charge hose Air tight test Pressurize the liquid pipe suction gas pipe HP LP gas pipe and equalizer pipe from the service po...

Page 18: ...d it may require additional charging For charging the additional refrigerant follow the procedure in this chapter And then carry out the check operation 11 1 Before working About the refrigerant tank...

Page 19: ...oor and outside units are turned on H2P will be lit on and the compressor will not operate Check the LED display indicate as shown below In order to ensure uniform refrigerant distribution it may take...

Page 20: ...cedure During Automatic refrigerant charging operation the system will select charging mode cooling mode or heating mode by the tem perature condition as follows When charging in cooling mode the syst...

Page 21: ...ion valve and the valve are closed when charging is finished However the valve will opened when ather operation Check operation nomal operation etc If you leave the tank connected the refrigerant will...

Page 22: ...possible if the outdoor temperature is 75 F or higher Refer to the Operation manual If a knocking sound can be heard in the liquid compression of the com pressor stop the unit immediately and then ene...

Page 23: ...y to comply 1 Calculate the amount of refrigerant lb charged to each system sep arately NOTE Where a single refrigerant facility is divided into 2 entirely indepen dent refrigerant systems then use th...

Page 24: ...20 English NOTES...

Page 25: ...3P215731 2 EM07A038 0712 FS 1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com HT...

Reviews: