14. CAUTION FOR REFRIGERANT LEAKS

(Points to note in connection with refrigerant leaks)

Introduction

The installer and system specialist shall secure safety against 
leakage according to local regulations or standards. The following 
standards may be applicable if local regulations are not available.

The VRV System, like other air conditioning systems, uses R410A as 
refrigerant. R410A itself is an entirely safe non-toxic, non-combustible 
refrigerant. Nevertheless care must be taken to ensure that air condi-
tioning facilities are installed in a room which is sufficiently large. This 
assures that the maximum concentration level of refrigerant gas is not 
exceeded, in the unlikely event of major leak in the system and this in 
accordance to the local applicable regulations and standards.

Maximum concentration level

The maximum charge of refrigerant and the calculation of the maximum 
concentration of refrigerant is directly related to the humanly occupied 
space in to which it could leak.
The unit of measurement of the concentration is lb/ft

3

 ( the weight in lb 

of the refrigerant gas in 1 ft

3

 volume of the occupied space).

Compliance to the local applicable regulations and standards for the 
maximum allowable concentration level is required.

1.

direction of the refrigerant flow

2.

room where refrigerant leak has occurred (outflow of all the 
refrigerant from the system)

Pay a special attention to the place, such as a basement, etc. 
where refrigerant can stay, since refrigerant is heavier than air.

Procedure for checking maximum concentration

Check the maximum concentration level in accordance with steps 1 to 4 
below and take whatever action is necessary to comply.

1.

Calculate the amount of refrigerant (lb) charged to each system sep-
arately.

NOTE

Where a single refrigerant facility is divided into 2 entirely indepen-
dent refrigerant systems then use the amount of refrigerant with 
which each separate system is charged.

2.

Calculate the smallest room volume (ft

)

Incase like the following, calculate the volume of (A), (B) as a single 
room or as the smallest room.

A.

Where there are no smaller room divisions

B.

Where there is a room division but there is an opening 

between the rooms sufficiently large to permit a free flow of air 
back and forth.

1.

opening between rooms

2.

partition 

(Where there is an opening without a door or where there are openings 
above and below the door which are each equivalent in size to 0.15% or 
more of the floor area.)

3.

Calculating the refrigerant density using the results of the calcula-
tions in steps 1 and 2 above.

If the result of the above calculation exceeds the maximum concen-
tration level then make similar calculations for the second then third 
smallest room and so until the result falls short of the maximum con-
centration.

4.

Dealing with the situations where the result exceeds the maximum 
concentration level.
Where the installation of a facility results in a concentration in excess 
of the maximum concentration level then it will be necessary to 
revise the system. Please consult your Daikin supplier.

amount of refriger-
ant in a single unit 
system (amount of 
refrigerant with 
which the system 
is charged before 
leaving the factory)

+

additional charging 
amount (amount of 
refrigerant added 
locally in accordance 
with the length or 
diameter of the refrig-
erant piping)

=

total amount 
of refrigerant 
(lb) in the 
system

2

1

total volume of refrigerant in the 
refrigerant system

maximum concen-
tration level (lb/ft

3

)

size (ft

) of smallest room in which 

there is an indoor unit installed

1

2

01_EN_3P215731-2.fm  Page 19  Tuesday, December 4, 2007  12:04 PM

Summary of Contents for RXYQ120PYDN

Page 1: ...INSTALLATION MANUAL System air conditioner RXYQ72PYDN RXYQ96PYDN RXYQ120PYDN RXYQ144PYDN RXYQ168PYDN RXYQ192PYDN RXYQ216PYDN RXYQ240PYDN English Fran ais Espa ol...

Page 2: ...8 11 3 4 Pattern 3 2 1 2 1 60 3 1 4 2 5 2 in 40 4 0 40 6 0 60 60 figure 1 figure 3 figure 2 4 1 2 3 1 1 2 3 7 8 3 7 8 3 7 8 5 3 7 8 3 7 8 3 7 8 1 2 3 4 5 figure 4 figure 6 figure 5 A B 1 4 3 2 30 1 8...

Page 3: ...4 1 5 2 B 1 2 1 1 1 1 5 16 1 16 2 16 3 6 2 3 4 4 C D 7 8 3 4 6 7 1 1 2 3 4 5 2 1 4 3 2 1 3 1 1 2 6 1 2 7 5 TOIN DUNIT F1 F2 TOOUT DUNIT F1 F2 TOMULTIUNIT Q1 Q2 A1P TOMULTIUNIT Q1 Q2 2 4 A1P 8 F1 F2 F1...

Page 4: ...re 30 figure 32 figure 28 figure 24 1 2 3 4 5 6 7 8 9 10 12 11 1 2 3 4 5 6 7 8 9 10 13 15 15 16 F17 11 12 19 20 14 18 1 2 1 2 3 1 2 3 4 5 1 2 2 3 5 6 4 1 2 3 4 10 13 11 5 6 7 8 9 12 15 16 17 18 14 1 2...

Page 5: ...ired to take adequate measures Meaning of danger warning caution and note symbols DANGER Indicates an imminently hazardous situa tion which if not avoided will result in death or serious injury WARNIN...

Page 6: ...e may occur Do not use a charging cylinder Using a charging cylinder may cause the refrigerant to deteriorate The refrigerant R410A requires strict cautions for keeping the system clean dry and tight...

Page 7: ...he storage location of the accessories is shown in figure 1 NOTE Do not throw away any of the accessories until installation is complete They are needed for installation work Refer to figure 1 1 Clamp...

Page 8: ...HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the carrier claims agent When handling the unit take into account the following 1 Fragile...

Page 9: ...s when brazing the pipe joints Residue can clog pipes and break equipment 6 4 Connecting the refrigerant piping 1 Direction to bring out the pipes The local inter unit piping can be connected either f...

Page 10: ...anual 1 About outside unit multi connection piping kit Install the joint horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 16 1 Do not install v...

Page 11: ...stall the REFNET header so it splits horizontally Refer to figure 15 1 Horizontal surface 2 B arrow view Prohibited pattern Oil remains in the stopping outside unit Change to pattern 1 or pattern 2 Fr...

Page 12: ...0 ft Example 6 a b h 540 ft 8 a i j 540 ft Example 8 a i 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length of REFNET joint to be 1 6 ft th...

Page 13: ...t total capacity index 72 72 111 111 Number of outside unit 2 units Connecting piping kit name BHFP22P100U Refrigerant branch kit name KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Example for indoor...

Page 14: ...249 0 121 0 040 0 175 0 081 0 015 HEAT PUMP SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT RXYQ72 120PYDN RXYQ144 192PYDN RXYQ216 240PYDN 2 2 lb 3 3 lb REFRIGERANT AMOUNT FOR EXCEEDING CONNECTION CAPACI...

Page 15: ...ing and earth terminal If there exists the possibility of reversed phase lose phase momen tary blackout or the power goes on and off while the product is oper ating attach a reversed phase protection...

Page 16: ...d of the master unit The outside unit that connected transmission wiring to indoor unit is the master unit The others are sub unit 7 5 Power Wiring Connection Procedure Be sure to connect the power su...

Page 17: ...shipped the unit contains the refrigerant so use caution when attaching the charge hose Air tight test Pressurize the liquid pipe suction gas pipe HP LP gas pipe and equalizer pipe from the service po...

Page 18: ...d it may require additional charging For charging the additional refrigerant follow the procedure in this chapter And then carry out the check operation 11 1 Before working About the refrigerant tank...

Page 19: ...oor and outside units are turned on H2P will be lit on and the compressor will not operate Check the LED display indicate as shown below In order to ensure uniform refrigerant distribution it may take...

Page 20: ...cedure During Automatic refrigerant charging operation the system will select charging mode cooling mode or heating mode by the tem perature condition as follows When charging in cooling mode the syst...

Page 21: ...ion valve and the valve are closed when charging is finished However the valve will opened when ather operation Check operation nomal operation etc If you leave the tank connected the refrigerant will...

Page 22: ...possible if the outdoor temperature is 75 F or higher Refer to the Operation manual If a knocking sound can be heard in the liquid compression of the com pressor stop the unit immediately and then ene...

Page 23: ...y to comply 1 Calculate the amount of refrigerant lb charged to each system sep arately NOTE Where a single refrigerant facility is divided into 2 entirely indepen dent refrigerant systems then use th...

Page 24: ...20 English NOTES...

Page 25: ...3P215731 2 EM07A038 0712 FS 1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com HT...

Reviews: