background image

16

English

The refrigerant charge port of this product have electric expansion valve.
The valve will be closed at end of refrigerant charging. However the valve 
will be opened on operation after refrigerant charging (check operation, 
nomal operation, etc.).
If the tank is left with the valve open, the amount of refrigerant which is 
properly charged may be off the point.

Make sure to perform the check operation after installation. Other-
wise, the malfunction code “U3” will be displayed and normal opera-
tion cannot be performed.
And the failure of “Check of miswiring” may also cause abnormal 
operation. Performance may drop due to the failure of “Judgment of 
piping length”.

Check operation must be performed for each refrigerant piping system.
Checking is impossible if plural systems are being done at once.

The individual problems of indoor units can not be checked.
About these problems check by test run after the check operation is 
completed. (See chapter 13)

The check operation cannot be performed in recovery or other ser-
vice modes.

11-2-1 Procedure of Adding Refrigerant charging
1.

Make sure the following works are complete in accordance with the 
installation manual.

„

Piping work

„

Wiring work

„

Air tight test

„

Vacuum drying

„

Installation work for BS, indoor unit

2.

Calculate the “additional charging amount” using “How to calculate the 
additional refrigerant to be charged” in 

“6-5 Example of connection”

.

3.

Open the valve B (

See the figure 30

. The valve A,C and the liquid 

pipe, suction gas pipe, HP/LP gas pipe, equalizer pipe shutoff valves 
must be left closed), and charge the refrigerant of the “additional 
charging amount” from the liquid side shutout valve service port.

(Refer to figure 30)

1.

Measuring device

2.

R410A tank (with siphon)

3.

Charge hose

4.

High side equalizer pipe shutoff valve

5.

Gas pipe shutoff valve

6.

Low side equalizer pipe shutoff valve

7.

Liquid pipe shutoff valve

8.

Refrigerant charge port

9.

Valve A

10.

Valve B

11.

Valve C

12.

Outside unit A

13.

Outside unit B

14.

Indoor unit

15.

Field pipings

16.

Refrigerant flow

17.

Shutoff valve

18.

Service port

4.

If the “additional charging amount” was charged fully, close the valve 
B and go to step 6.
If the “additional charging amount” was not charged fully, close the 
valve B and go to step 5.

5.

Perform the refrigerant charging following [Automatic refrigerant 
charging operation procedure] as shown below. And charge the 
remaining refrigerant of the “additional charging amount”.

NOTE

For performing the automatic refrigerant charging operation, the push 
button on the PC-bord (A1) of outside unit are used. (See figure 29.)
And the refrigerant are charged from the refrigerant charge port via 
the valve A. (See figure 31.) For operating the push button and open-
ing or closing the valves, follow the procedure.

During Automatic refrigerant charging operation, the system will 
select charging mode (cooling mode or heating mode) by the tem-
perature condition as follows.

When charging in cooling mode, the system will stop operation when 
the required amount of refrigerant is charged.
During charging in heating mode, a person must manually close 
valve A and stop operation.
Beforehand, check the remaining refrigerant that is needed to 
charge based on the “additional charging amount” in step 2 and the 
charged amount in step 3.

The refrigerant will be charged about 66 lb in one  hour at outdoor 
temp. 86°F DB (about 26 lb at outdoor temp. 32°F DB).

During Automatic refrigerant charging operation, you can stop the 
operation forcedly by pushing MODE button (BS1).

(Refer to figure 31)

1.

Measuring device

2.

R410A tank (with siphon)

3.

Charge hose

4.

High side equalizer pipe shutoff valve

5.

Gas pipe shutoff valve

6.

Low side equalizer pipe shutoff valve

7.

Liquid pipe shutoff valve

8.

Refrigerant charge port

9.

Valve A

10.

Valve B

11.

Valve C

12.

Outside unit A

13.

Outside unit B

14.

Indoor unit

15.

Field pipings

16.

Refrigerant flow when charging

17.

Shutoff valve

18.

Service port

19.

The refrigerant will be charged about 66 lb in one hour at out-
door temp. 86°FDB (26 lb at 32°FDB). (According to outdoor 
temp. or the refrigerant amount in the tank, the charging rate 
may speed up). If you need to speed up in case of multi sys-
tem, connect the refrigerant tanks to each outside unit.

[Automatic refirgerant charging operation procedure]

NOTE

The marks of LED mean as follows.

h

 : OFF

i

 : ON

j

 : Blinking

 : OFF, ON or Brinking

(1) Open the liquid pipe and gas pipe shutoff valves. (The valve A~C 

must be closed. See figure 31.)

(2)

Close the EL. COMPO. BOX (1) lid and all front panel except on the 
EL. COMPO. BOX (1) side. (*1) And turn the power to the outdoor 
unit and all connected indoor units. (*2)

After H2P stop blinking (about 12 minutes after turning on the 
power), check H2P is OFF.
If H2P is ON, check the malfunction code in the remote controller of 
indoor unit and correct the malfunction in accordance with [Remote 
controller display malfunction code] in chapter 11-2-2.

(3) Check the LED. And push the MODE button (BS1) once if the LED 

displays is not as below.

(4) Push the TEST button (BS4) once. (The LED displays will change as 

below.)

(5) Hold the TEST button (BS4) down for 5 seconds or more.

(The LED displays will change as below and fan of outside unit will 
start rotation.)

(6) When the compressor start working and the LED displays change 

any state in below (*3), go to “In case of cooling mode” or “In case of 
heating mode” in accordance with the LED displays.

Outdoor temp. : 32˚F DB ~  109˚F DB
Indoor temp. :

50˚F DB ~  90˚F DB

Less than above range

Cooling mode

Heating mode

H1P H2P H3P H4P H5P H6P H7P

h

h

i

h

h

h

h

H1P H2P H3P H4P H5P H6P H7P

i

i

i

i

i

i

i

H1P H2P H3P H4P H5P H6P H7P

h

j

h

h

h

H1P H2P H3P H4P H5P H6P H7P

j

j

j

h

i

h

i

Go to “In case of 
cooling mode”

j

j

h

h

i

h

i

Go to “In case of 
heating mode”

01_EN_3P215731-2.fm  Page 16  Tuesday, December 4, 2007  12:04 PM

Summary of Contents for RXYQ120PYDN

Page 1: ...INSTALLATION MANUAL System air conditioner RXYQ72PYDN RXYQ96PYDN RXYQ120PYDN RXYQ144PYDN RXYQ168PYDN RXYQ192PYDN RXYQ216PYDN RXYQ240PYDN English Fran ais Espa ol...

Page 2: ...8 11 3 4 Pattern 3 2 1 2 1 60 3 1 4 2 5 2 in 40 4 0 40 6 0 60 60 figure 1 figure 3 figure 2 4 1 2 3 1 1 2 3 7 8 3 7 8 3 7 8 5 3 7 8 3 7 8 3 7 8 1 2 3 4 5 figure 4 figure 6 figure 5 A B 1 4 3 2 30 1 8...

Page 3: ...4 1 5 2 B 1 2 1 1 1 1 5 16 1 16 2 16 3 6 2 3 4 4 C D 7 8 3 4 6 7 1 1 2 3 4 5 2 1 4 3 2 1 3 1 1 2 6 1 2 7 5 TOIN DUNIT F1 F2 TOOUT DUNIT F1 F2 TOMULTIUNIT Q1 Q2 A1P TOMULTIUNIT Q1 Q2 2 4 A1P 8 F1 F2 F1...

Page 4: ...re 30 figure 32 figure 28 figure 24 1 2 3 4 5 6 7 8 9 10 12 11 1 2 3 4 5 6 7 8 9 10 13 15 15 16 F17 11 12 19 20 14 18 1 2 1 2 3 1 2 3 4 5 1 2 2 3 5 6 4 1 2 3 4 10 13 11 5 6 7 8 9 12 15 16 17 18 14 1 2...

Page 5: ...ired to take adequate measures Meaning of danger warning caution and note symbols DANGER Indicates an imminently hazardous situa tion which if not avoided will result in death or serious injury WARNIN...

Page 6: ...e may occur Do not use a charging cylinder Using a charging cylinder may cause the refrigerant to deteriorate The refrigerant R410A requires strict cautions for keeping the system clean dry and tight...

Page 7: ...he storage location of the accessories is shown in figure 1 NOTE Do not throw away any of the accessories until installation is complete They are needed for installation work Refer to figure 1 1 Clamp...

Page 8: ...HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the carrier claims agent When handling the unit take into account the following 1 Fragile...

Page 9: ...s when brazing the pipe joints Residue can clog pipes and break equipment 6 4 Connecting the refrigerant piping 1 Direction to bring out the pipes The local inter unit piping can be connected either f...

Page 10: ...anual 1 About outside unit multi connection piping kit Install the joint horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 16 1 Do not install v...

Page 11: ...stall the REFNET header so it splits horizontally Refer to figure 15 1 Horizontal surface 2 B arrow view Prohibited pattern Oil remains in the stopping outside unit Change to pattern 1 or pattern 2 Fr...

Page 12: ...0 ft Example 6 a b h 540 ft 8 a i j 540 ft Example 8 a i 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length of REFNET joint to be 1 6 ft th...

Page 13: ...t total capacity index 72 72 111 111 Number of outside unit 2 units Connecting piping kit name BHFP22P100U Refrigerant branch kit name KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Example for indoor...

Page 14: ...249 0 121 0 040 0 175 0 081 0 015 HEAT PUMP SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT RXYQ72 120PYDN RXYQ144 192PYDN RXYQ216 240PYDN 2 2 lb 3 3 lb REFRIGERANT AMOUNT FOR EXCEEDING CONNECTION CAPACI...

Page 15: ...ing and earth terminal If there exists the possibility of reversed phase lose phase momen tary blackout or the power goes on and off while the product is oper ating attach a reversed phase protection...

Page 16: ...d of the master unit The outside unit that connected transmission wiring to indoor unit is the master unit The others are sub unit 7 5 Power Wiring Connection Procedure Be sure to connect the power su...

Page 17: ...shipped the unit contains the refrigerant so use caution when attaching the charge hose Air tight test Pressurize the liquid pipe suction gas pipe HP LP gas pipe and equalizer pipe from the service po...

Page 18: ...d it may require additional charging For charging the additional refrigerant follow the procedure in this chapter And then carry out the check operation 11 1 Before working About the refrigerant tank...

Page 19: ...oor and outside units are turned on H2P will be lit on and the compressor will not operate Check the LED display indicate as shown below In order to ensure uniform refrigerant distribution it may take...

Page 20: ...cedure During Automatic refrigerant charging operation the system will select charging mode cooling mode or heating mode by the tem perature condition as follows When charging in cooling mode the syst...

Page 21: ...ion valve and the valve are closed when charging is finished However the valve will opened when ather operation Check operation nomal operation etc If you leave the tank connected the refrigerant will...

Page 22: ...possible if the outdoor temperature is 75 F or higher Refer to the Operation manual If a knocking sound can be heard in the liquid compression of the com pressor stop the unit immediately and then ene...

Page 23: ...y to comply 1 Calculate the amount of refrigerant lb charged to each system sep arately NOTE Where a single refrigerant facility is divided into 2 entirely indepen dent refrigerant systems then use th...

Page 24: ...20 English NOTES...

Page 25: ...3P215731 2 EM07A038 0712 FS 1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com HT...

Reviews: