background image

English

9

Outside unit multi connection piping kit and

Refrigerant branch kit selection

Pipe size selection

 Refrigerant branch kits can only be used with R410A.

 When multi outdoor system are installed, be sure to use the 

special separately sold Outside unit multi connection piping 

kit. (BHFP22P100U).

(For how to select the proper kit, follow the table at right.)

 Never use BHFP26M90U, BHFP22M90U for M type of this 

series or T joint (field supplyed).

How to select the REFNET joint

Piping between outside unit(*2) and refrigerant branch kit (partA)

How to select the REFNET header

When using REFNET joint at the first branch counted from the outside unit side,

choose from the following table in accordance with the outside unit capacity type.

(Example :REFNET jointA)  

Choose from the following table in accordance with the outside units system

capacity type.

Piping between outside unit multi connection piping kit and outside unit (part B)

Choose from the following table in accordance with the capacity type

of the outside unit connected.

Choose form the following table in accordance with the total capacity index of all

the indoor units conncted below the REFNET header. 

How to select the outside unit multi connection piping kit

(This is required when the system is multi outside unit system.)

Choose from the following table in accordance with the number of outside units.

Choose the REFNET joints other than the first branch from the following table in a accordance

with the total capacity index of all the indoor units connected below the REFNET joint.   

Outside unit capacity type

RXYQ72 · 96P type

RXYQ120 ~ 216P type

RXYQ240P type

Indoor unit total capacity index

× < 72

72 

 × < 111

111 

 ×

Refrigerant branch kit name 

KHRP26M33T 

KHRP26M72TU  

KHRP26M73TU 

Refrigerant branch kit name 

KHRP26M22T

KHRP26M33T

KHRP26M72TU 

Indoor unit total capacity index

× < 72

72 

 × < 111

111 

≤ 

×

Number of outside unit

2 units

Connecting piping kit name

BHFP22P100U 

Refrigerant branch kit name 

KHRP26M22H or KHRP26M33H

KHRP26M33H

KHRP26M72H

Example for indoor units

connected downstream

Example REFNET joint C : Indoor units  5 + 6 + 7 + 8

Example REFNET joint B : Indoor units 7 + 8

Example REFNET header : Indoor units 1 + 2 + 3 + 4 + 5 + 6 

Example REFNET header :

indoor units 1 + 2 + 3 + 4 + 5 + 6 + 7 + 8

The thickness and material shall be selected in 

accordance with local code.

For an outside unit installation, make

the settings in accordance with the

following figure.

Outside unit

High side equalizer pipe (part C)

Piping between outside unit

multi connection piping kit

and outside unit (part B)

Piping between outside unit multi

connection piping kits

Piping between outside unit and

refrigerant branch kit (part A)

Outside unit

capacity type

RXYQ72P type

RXYQ96P type

RXYQ120P type

RXYQ144P type

RXYQ168P type

RXYQ192 · 216P type

RXYQ240P type

Piping size (O. D.)

Piping size (O. D.)

Gas pipe

φ

3/4

φ

7/8

φ

1-1/8

φ

1-3/8

Liquid pipe

φ

3/8

φ

1/2

φ

5/8

Outside unit

capacity type

RXYQ72P type

RXYQ96P type

RXYQ120P type

Gas pipe

φ

3/4

φ

7/8

φ

1-1/8

Liquid pipe

φ

3/4

φ

1/2

Piping between refrigerant branch kits

Choose from the following table in accordance with the total capacity type

of all the indoor units connected downstream.

Piping between refrigerant branch kit and indoor unit.

High side Equalizer pipe (part C)(outside multi system only)

Match to the size of the connection pipng on the indoor unit.

*1 Connection piping must not exceed the refrigerant Piping size between outside

unit and refrigerant branch kit (part A)

Indoor capacity index

× < 54

54 

 × < 72

72 

 × < 111

111 

 × < 162

162 

 ×

Indoor unit capacity type

07 · 09 · 12 · 18

24 · 30 · 36 · 48

Gas pipe

φ

1/2

φ

5/8

Liquid pipe

φ

1/4

φ

3/8

Piping size (O. D.)

φ

3/4

 (unit : in.)

 (unit : in.)

Piping size (O. D.)

 (unit : in.)

Piping size (O. D.)

 (unit : in.)

 (unit : in.)

Low side Equalizer pipe (part D)(outside multi system only)

Piping size (O. D.)

φ

3/4

 (unit : in.)

Gas pipe

φ

5/8

φ

3/4

φ

7/8

φ

1-1/8

Liquid pipe

φ

3/8

φ

1/2

φ

5/8

Low side equalizer pipe (part D)

01_EN_3P215731-2.fm  Page 9  Tuesday, December 4, 2007  12:04 PM

Summary of Contents for RXYQ120PYDN

Page 1: ...INSTALLATION MANUAL System air conditioner RXYQ72PYDN RXYQ96PYDN RXYQ120PYDN RXYQ144PYDN RXYQ168PYDN RXYQ192PYDN RXYQ216PYDN RXYQ240PYDN English Fran ais Espa ol...

Page 2: ...8 11 3 4 Pattern 3 2 1 2 1 60 3 1 4 2 5 2 in 40 4 0 40 6 0 60 60 figure 1 figure 3 figure 2 4 1 2 3 1 1 2 3 7 8 3 7 8 3 7 8 5 3 7 8 3 7 8 3 7 8 1 2 3 4 5 figure 4 figure 6 figure 5 A B 1 4 3 2 30 1 8...

Page 3: ...4 1 5 2 B 1 2 1 1 1 1 5 16 1 16 2 16 3 6 2 3 4 4 C D 7 8 3 4 6 7 1 1 2 3 4 5 2 1 4 3 2 1 3 1 1 2 6 1 2 7 5 TOIN DUNIT F1 F2 TOOUT DUNIT F1 F2 TOMULTIUNIT Q1 Q2 A1P TOMULTIUNIT Q1 Q2 2 4 A1P 8 F1 F2 F1...

Page 4: ...re 30 figure 32 figure 28 figure 24 1 2 3 4 5 6 7 8 9 10 12 11 1 2 3 4 5 6 7 8 9 10 13 15 15 16 F17 11 12 19 20 14 18 1 2 1 2 3 1 2 3 4 5 1 2 2 3 5 6 4 1 2 3 4 10 13 11 5 6 7 8 9 12 15 16 17 18 14 1 2...

Page 5: ...ired to take adequate measures Meaning of danger warning caution and note symbols DANGER Indicates an imminently hazardous situa tion which if not avoided will result in death or serious injury WARNIN...

Page 6: ...e may occur Do not use a charging cylinder Using a charging cylinder may cause the refrigerant to deteriorate The refrigerant R410A requires strict cautions for keeping the system clean dry and tight...

Page 7: ...he storage location of the accessories is shown in figure 1 NOTE Do not throw away any of the accessories until installation is complete They are needed for installation work Refer to figure 1 1 Clamp...

Page 8: ...HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the carrier claims agent When handling the unit take into account the following 1 Fragile...

Page 9: ...s when brazing the pipe joints Residue can clog pipes and break equipment 6 4 Connecting the refrigerant piping 1 Direction to bring out the pipes The local inter unit piping can be connected either f...

Page 10: ...anual 1 About outside unit multi connection piping kit Install the joint horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 16 1 Do not install v...

Page 11: ...stall the REFNET header so it splits horizontally Refer to figure 15 1 Horizontal surface 2 B arrow view Prohibited pattern Oil remains in the stopping outside unit Change to pattern 1 or pattern 2 Fr...

Page 12: ...0 ft Example 6 a b h 540 ft 8 a i j 540 ft Example 8 a i 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length of REFNET joint to be 1 6 ft th...

Page 13: ...t total capacity index 72 72 111 111 Number of outside unit 2 units Connecting piping kit name BHFP22P100U Refrigerant branch kit name KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Example for indoor...

Page 14: ...249 0 121 0 040 0 175 0 081 0 015 HEAT PUMP SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT RXYQ72 120PYDN RXYQ144 192PYDN RXYQ216 240PYDN 2 2 lb 3 3 lb REFRIGERANT AMOUNT FOR EXCEEDING CONNECTION CAPACI...

Page 15: ...ing and earth terminal If there exists the possibility of reversed phase lose phase momen tary blackout or the power goes on and off while the product is oper ating attach a reversed phase protection...

Page 16: ...d of the master unit The outside unit that connected transmission wiring to indoor unit is the master unit The others are sub unit 7 5 Power Wiring Connection Procedure Be sure to connect the power su...

Page 17: ...shipped the unit contains the refrigerant so use caution when attaching the charge hose Air tight test Pressurize the liquid pipe suction gas pipe HP LP gas pipe and equalizer pipe from the service po...

Page 18: ...d it may require additional charging For charging the additional refrigerant follow the procedure in this chapter And then carry out the check operation 11 1 Before working About the refrigerant tank...

Page 19: ...oor and outside units are turned on H2P will be lit on and the compressor will not operate Check the LED display indicate as shown below In order to ensure uniform refrigerant distribution it may take...

Page 20: ...cedure During Automatic refrigerant charging operation the system will select charging mode cooling mode or heating mode by the tem perature condition as follows When charging in cooling mode the syst...

Page 21: ...ion valve and the valve are closed when charging is finished However the valve will opened when ather operation Check operation nomal operation etc If you leave the tank connected the refrigerant will...

Page 22: ...possible if the outdoor temperature is 75 F or higher Refer to the Operation manual If a knocking sound can be heard in the liquid compression of the com pressor stop the unit immediately and then ene...

Page 23: ...y to comply 1 Calculate the amount of refrigerant lb charged to each system sep arately NOTE Where a single refrigerant facility is divided into 2 entirely indepen dent refrigerant systems then use th...

Page 24: ...20 English NOTES...

Page 25: ...3P215731 2 EM07A038 0712 FS 1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com HT...

Reviews: