background image

English

17

In case of cooling mode

(7) Push the TEST button (BS4) once within 5 minutes after procedure 

(5) (*4) and close the all front panels (*5).
After that, open the valve A immediately (See figure 31) (*6) and 
watch the remote controller display of indoor unit.

(8) If the remote controller display shows “PE” code (*7), ready to close 

the valve A.
And go to procedure (9).
If the remote controller display shows other code, close the valve A 
immediately and refer to [Remote controller cooling mode malfunc-
tion code]

Beware the fan running when open the front panel.
The fan may continue rotation after the system stop the operation.

(9) When the compressor stop working (the fan may continue rotation.), 

close the valve A immediately (*8).
And check the LED displays are as below and the remote controller 
display shows “P9” code.

After checking, push the MODE button (BS1) once and the charging 
is complete.

In case of heating mode

(7) Push the TEST button (BS4) once within 5 minutes after procedure 

(5) (*4) and close the all front panels.
After that, open the valve A immediately (See figure 31) (*6) and 
check the charged amount by meauring device.
During operation, if the remote controller display shows “P2” or “P8” 
code, close the valve A immediately and refer to [Remote controller 
heating mode malfunction code].

Beware the fan running when open the front panel.
The fan may continue rotation after the system stop the operation.

(8) When the required amount of refrigerant is charged, close the valve 

A (See figure 30) (*8) and push the RETURN button (BS3) once. And 
then go to procedure (9).

(9) Push the MODE button (BS1) once, and the charging is complete.

Notes (*1)~(*9)

(*1) Lead the refrigerant charge hose etc from the pipe intake. 

All front panels must be closed at the procedure (7).

(*2)

If you perform the refrigerant charging operation within the refrig-
erant system that have the power off unit, the operation cannot fin-
ish properly.
Check the number of outside and indoor units that is powered.
For checking, see [How to check how many units are connected] 
in chapter 11-1.

To energize the crankcase heater, make sure to turn on for 
6 hours before starting operation.

(*3) It takes about 2~10 minutes for getting stability of refrigerant state.

If the additional refrigerant is little and operation is started before 
getting stability, the system can not judge the charging amount pre-
cisely and it cause over charge.

(*4) If the TEST button (BS4) is not pushed within 5 minutes, “P2” code 

will displayed in the remote controller. In this case, refer [Remote 
controller cooling (or heating) mode malfunction code].

(*5) If the front panel is opened during the operation, the system cannot 

operate properly.

(*6) If you leave the system without connecting the refrigerant tank or 

opening the valve A for 30 minutes or more, the system stop oper-
ation and “P2” code are displayed in remote controller.
In this case, refer [Remote controller cooling (or heating) mode mal-
function code].

(*7) Depending on the situation of operation such as the charging 

amount is little, the “PE” code may not be displayed and the “P9” 
code may be displayed.

(*8) Always close the valve A and take the tank off.

The refrigerant charge port of this unit have electric expansion valve 
and the valve are closed when charging is finished. However, the 
valve will opened when ather operation (Check operation, nomal 
operation, etc.). If you leave the tank connected, the refrigerant will 
charged and it cause over charge.

[Remote controller cooling mode malfunction code]

[Remote controller heating mode malfunction code]

6.

After completing the additional refrigerant charging, record the charging 
amount on the accessory “REQUEST FOR THE INDICATON” label 
(Installation records) and adhere it to the back side of the front panel. 
Also, record the factory charged refrigerant amount, additional refriger-
ant amount in the field and total refrigerant amount of the system to 
“ADDITIONAL REF. CHARGE” label and adhere in the proximity of the 
refrigerant charge port.
About “ADDITIONAL REF. CHARGE” label, refer to [Important informa-
tion regarding the refrigerant used] in 

“1-2 Special notice of product”

.

11-2-2 Procedure of check operation

Check operation perform the following work. Do the check operation 
following below.
Otherwise, malfunction code “U3” will be displayed in the remote 
controller and nomal operation can not be carried out.

„

Check of shutoff valve opening

„

Check of miswiring

„

Judgment of piping length

„

Check of refrigerant overcharge

NOTE

Check operation can not carried out at outdoor temp. less than 23°F.
Perform the check operation at day or time that outdoor temp. is 23°F 
or more.

[Check Operation Procedure]

(1) Close the EL. COMPO. BOX lid and all front panels except as the 

side of the EL. COMPO. BOX and turn on the power to the outside 
unit and all connected BS, indoor units. (Be sure to turn the power on 
at least 6 hours before operation in order to have power running to 
the crank case heater.)

(2) Make the onsite settings as needed using the push button (BS1-

BS5) on the outside unit PC-board (A1P) with the power on. (See 

“12 Onsite Settings”

)

H1P H2P H3P H4P H5P H6P H7P

i

j

j

i

i

i

i

Code

The work contents

PE

Charging is almost finished. Ready to close the valve A.

PA

PH

The refrigerant tank is empty. Close the valve A and replace 
empty tank to the new tank. After changing the tank, open the 
valve A again.

Beware the fan running. The outside unit does not 
stop operation.

P8

Close the valve A immediately, and restart the operation from 
procedure (3).

P2

Operation is interrupted. Close the 
valve A immedeately and check the 
below items.

Check if gas pipe or liquid pipe 
shutoff valve is opened.

Check the refrigerant tank is con-
nected and the valve A was opend.

Check if the air inlet and outlet of 
the indoor unit are not closed by 
an obstruction.

After correcting the 
abnormality, restart 
the operation from 
procedure (3).

Operation is stoped abnormally. Close 
the valve A immediately. Confirm the mal-
function code and correct the abnormality 
following the [Remote controller displays 
malfunction code] in chapter 11-2-2.

P9

Charging is finished. Close the valve A and take the refriger-
ant tank off.

Code

The work contents

P8

Close the valve A immediately and push the TEST button (BS4) 
once. And restart from procedure (7) of “In case of heating mode”.

P2

Operation is interrupted. Close the valve A immedeately and 
check the below items.

Check if gas pipe or liquid pipe shutoff valve is opened.

Check the refrigerant tank is connected and the valve A 
was opend.

Check if the air inlet and outlet of the indoor unit are not 
closed by an obstruction.

01_EN_3P215731-2.fm  Page 17  Tuesday, December 4, 2007  12:04 PM

Summary of Contents for RXYQ120PYDN

Page 1: ...INSTALLATION MANUAL System air conditioner RXYQ72PYDN RXYQ96PYDN RXYQ120PYDN RXYQ144PYDN RXYQ168PYDN RXYQ192PYDN RXYQ216PYDN RXYQ240PYDN English Fran ais Espa ol...

Page 2: ...8 11 3 4 Pattern 3 2 1 2 1 60 3 1 4 2 5 2 in 40 4 0 40 6 0 60 60 figure 1 figure 3 figure 2 4 1 2 3 1 1 2 3 7 8 3 7 8 3 7 8 5 3 7 8 3 7 8 3 7 8 1 2 3 4 5 figure 4 figure 6 figure 5 A B 1 4 3 2 30 1 8...

Page 3: ...4 1 5 2 B 1 2 1 1 1 1 5 16 1 16 2 16 3 6 2 3 4 4 C D 7 8 3 4 6 7 1 1 2 3 4 5 2 1 4 3 2 1 3 1 1 2 6 1 2 7 5 TOIN DUNIT F1 F2 TOOUT DUNIT F1 F2 TOMULTIUNIT Q1 Q2 A1P TOMULTIUNIT Q1 Q2 2 4 A1P 8 F1 F2 F1...

Page 4: ...re 30 figure 32 figure 28 figure 24 1 2 3 4 5 6 7 8 9 10 12 11 1 2 3 4 5 6 7 8 9 10 13 15 15 16 F17 11 12 19 20 14 18 1 2 1 2 3 1 2 3 4 5 1 2 2 3 5 6 4 1 2 3 4 10 13 11 5 6 7 8 9 12 15 16 17 18 14 1 2...

Page 5: ...ired to take adequate measures Meaning of danger warning caution and note symbols DANGER Indicates an imminently hazardous situa tion which if not avoided will result in death or serious injury WARNIN...

Page 6: ...e may occur Do not use a charging cylinder Using a charging cylinder may cause the refrigerant to deteriorate The refrigerant R410A requires strict cautions for keeping the system clean dry and tight...

Page 7: ...he storage location of the accessories is shown in figure 1 NOTE Do not throw away any of the accessories until installation is complete They are needed for installation work Refer to figure 1 1 Clamp...

Page 8: ...HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the carrier claims agent When handling the unit take into account the following 1 Fragile...

Page 9: ...s when brazing the pipe joints Residue can clog pipes and break equipment 6 4 Connecting the refrigerant piping 1 Direction to bring out the pipes The local inter unit piping can be connected either f...

Page 10: ...anual 1 About outside unit multi connection piping kit Install the joint horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 16 1 Do not install v...

Page 11: ...stall the REFNET header so it splits horizontally Refer to figure 15 1 Horizontal surface 2 B arrow view Prohibited pattern Oil remains in the stopping outside unit Change to pattern 1 or pattern 2 Fr...

Page 12: ...0 ft Example 6 a b h 540 ft 8 a i j 540 ft Example 8 a i 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length of REFNET joint to be 1 6 ft th...

Page 13: ...t total capacity index 72 72 111 111 Number of outside unit 2 units Connecting piping kit name BHFP22P100U Refrigerant branch kit name KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Example for indoor...

Page 14: ...249 0 121 0 040 0 175 0 081 0 015 HEAT PUMP SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT RXYQ72 120PYDN RXYQ144 192PYDN RXYQ216 240PYDN 2 2 lb 3 3 lb REFRIGERANT AMOUNT FOR EXCEEDING CONNECTION CAPACI...

Page 15: ...ing and earth terminal If there exists the possibility of reversed phase lose phase momen tary blackout or the power goes on and off while the product is oper ating attach a reversed phase protection...

Page 16: ...d of the master unit The outside unit that connected transmission wiring to indoor unit is the master unit The others are sub unit 7 5 Power Wiring Connection Procedure Be sure to connect the power su...

Page 17: ...shipped the unit contains the refrigerant so use caution when attaching the charge hose Air tight test Pressurize the liquid pipe suction gas pipe HP LP gas pipe and equalizer pipe from the service po...

Page 18: ...d it may require additional charging For charging the additional refrigerant follow the procedure in this chapter And then carry out the check operation 11 1 Before working About the refrigerant tank...

Page 19: ...oor and outside units are turned on H2P will be lit on and the compressor will not operate Check the LED display indicate as shown below In order to ensure uniform refrigerant distribution it may take...

Page 20: ...cedure During Automatic refrigerant charging operation the system will select charging mode cooling mode or heating mode by the tem perature condition as follows When charging in cooling mode the syst...

Page 21: ...ion valve and the valve are closed when charging is finished However the valve will opened when ather operation Check operation nomal operation etc If you leave the tank connected the refrigerant will...

Page 22: ...possible if the outdoor temperature is 75 F or higher Refer to the Operation manual If a knocking sound can be heard in the liquid compression of the com pressor stop the unit immediately and then ene...

Page 23: ...y to comply 1 Calculate the amount of refrigerant lb charged to each system sep arately NOTE Where a single refrigerant facility is divided into 2 entirely indepen dent refrigerant systems then use th...

Page 24: ...20 English NOTES...

Page 25: ...3P215731 2 EM07A038 0712 FS 1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com HT...

Reviews: