background image

English

15

2.

Securely tighten the valve until the shaft contacts the main body seal.

3.

Make sure to tighten the cap securely.
(For the tightening torque, refer to the item <Tightening Torque>.)

<Tightening torque>

[How to Check How Many Units are Connected]

It is possible to find out how many indoor or outside unit in the system are turned on by operating the push button on the PC-board (A1P) of outside 
unit (In case of multi system master unit).
Follow the procedure below to check how many indoor or outside units are turned on.

NOTE

Press the “MODE button” (BS1) if you get confused while operating.
This returns to 

Setting Mode 1 

(H1P : OFF, default).

11-2 Procedure of Adding Refrigerant charging and 

check operation

WARNING

Electric Shock Warning

Make sure to close the EL. COMPO. BOX lid before turning on the 
power.

Perform the setting on the PC-board (A1P) of the outside unit and 
check the LED display after the power is on via the inspection door 
which is in the EL. COMPO. BOX lid.

(Refer to figure 29)

1.

EL. COMPO. BOX

2.

Inspection door

3.

EL. COMPO. BOX lid

4.

LED (H1~8P)

5.

Push button(BS1~5)

6.

Lift the protruding part to open the inspection door.

Use an insulated rod to operate the push buttons via the EL. 
COMPO. BOX’s inspection door.
There is a risk of electric shock if you touch any live parts, since this 
operation must be performed with the power on.

CAUTION

Make sure to use the protect tool (protective groves and goggles) 
when charging the refrigerant.

Due to a danger of liquid hammer, the refrigerant must not be charged 
over the allowable maximum amount when charging the refrigerant.

Do not perform the refrigerant charging operation under working for 
the BS and indoor unit.

When opening the front panel, make sure to take caution to the fan 
rotation during the working.
After the outside unit stops operating, the fan may keep rotation for a 
while.

NOTE

If operation is performed within 12 minutes after the BS, indoor and 
outside units are turned on, H2P will be lit on and the compressor will 
not operate.

Check the LED display indicate as shown below.

In order to ensure uniform refrigerant distribution, it may take up to 
around 10 minutes for the compressor to start up after the unit start-
ing operating. This is not a malfunction.

The refrigerant charge port is connected to the piping inside the unit.
When the unit is shipped from the factory, the unit’s internal piping is 
already charged with refrigerant, so be careful when connecting the 
charge hose.

After adding the refrigerant, make sure to close the lid of the refrig-
erant charging port.
The tightening torque for the lid is 8.48 to 10.3 ft · lbf.

See [Shutoff valve operation procedure] in chapter 11-1 for details 
on how to handle shutoff valves.

When done or when pausing the refrigerant charging operation, close 
the valve of the refrigerant tank immediately.

Shutoff 
valve size

Tightening torque ft · lbf (Turn clockwise to close)

Shaft (valve body)

Cap (valve lid) Service port

φ 

3/8

3.98 - 4.87

Hexagonal 

wrench 4mm

9.95 - 12.17

8.48 - 10.3

φ 

1/2

5.97 - 7.30

13.3 - 16.2

φ 

3/4

19.9 - 24.3

Hexagonal 

wrench 8mm

16.6 - 20.3

φ 

1

(LED display: 

h

 ...OFF  

i

 ...ON  

j

 ...Blinking  

 ...Uncertain)

LED display

H1P

H2P

H3P

H4P

H5P

H6P

H7P

(1) Press the MODE button (BS1) once at 

Setting Mode 1

 (H1P : off), and set the MON-

ITOR MODE (H1P : Blinking).

j

h

h

h

h

h

h

(2) Press the SET button (BS2) the number of times until the 

LED display matches that at right.

For checking the number of 
outside units : eight times

j

h

h

i

h

h

h

For checking the number 
of indoor units : five times

j

h

h

h

i

h

i

(3) Press the RETURN button (BS3) and read the number of units from the display of 

H2P through H7P.
[Reading Method]
The display of H2P through H7P should be read as a binary number, with 

j

 standing 

for “1” and 

h

 standing for “0”.

j

j

h

j

h

j

j

h

(4) Press the MODE button (BS1) once. This returns to 

Setting Mode 1 

(H1P : OFF, default).

h

h

i

h

h

h

h

Ex: For the LED display at right, this would be “0 1 0 1 1 0 ”, 
which would mean 22 units are connected.

Note: “000000” indicates 64 units.

32 × 

0

 + 16 × 

1

 + 8 × 

0

 + 4 × 

1

 + 2 × 

1

 + 1 × 

0

 = 22 units

H1P H2P H3P H4P H5P H6P H7P

h

h

i

h

h

h

h

01_EN_3P215731-2.fm  Page 15  Tuesday, December 4, 2007  12:04 PM

Summary of Contents for RXYQ120PYDN

Page 1: ...INSTALLATION MANUAL System air conditioner RXYQ72PYDN RXYQ96PYDN RXYQ120PYDN RXYQ144PYDN RXYQ168PYDN RXYQ192PYDN RXYQ216PYDN RXYQ240PYDN English Fran ais Espa ol...

Page 2: ...8 11 3 4 Pattern 3 2 1 2 1 60 3 1 4 2 5 2 in 40 4 0 40 6 0 60 60 figure 1 figure 3 figure 2 4 1 2 3 1 1 2 3 7 8 3 7 8 3 7 8 5 3 7 8 3 7 8 3 7 8 1 2 3 4 5 figure 4 figure 6 figure 5 A B 1 4 3 2 30 1 8...

Page 3: ...4 1 5 2 B 1 2 1 1 1 1 5 16 1 16 2 16 3 6 2 3 4 4 C D 7 8 3 4 6 7 1 1 2 3 4 5 2 1 4 3 2 1 3 1 1 2 6 1 2 7 5 TOIN DUNIT F1 F2 TOOUT DUNIT F1 F2 TOMULTIUNIT Q1 Q2 A1P TOMULTIUNIT Q1 Q2 2 4 A1P 8 F1 F2 F1...

Page 4: ...re 30 figure 32 figure 28 figure 24 1 2 3 4 5 6 7 8 9 10 12 11 1 2 3 4 5 6 7 8 9 10 13 15 15 16 F17 11 12 19 20 14 18 1 2 1 2 3 1 2 3 4 5 1 2 2 3 5 6 4 1 2 3 4 10 13 11 5 6 7 8 9 12 15 16 17 18 14 1 2...

Page 5: ...ired to take adequate measures Meaning of danger warning caution and note symbols DANGER Indicates an imminently hazardous situa tion which if not avoided will result in death or serious injury WARNIN...

Page 6: ...e may occur Do not use a charging cylinder Using a charging cylinder may cause the refrigerant to deteriorate The refrigerant R410A requires strict cautions for keeping the system clean dry and tight...

Page 7: ...he storage location of the accessories is shown in figure 1 NOTE Do not throw away any of the accessories until installation is complete They are needed for installation work Refer to figure 1 1 Clamp...

Page 8: ...HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the carrier claims agent When handling the unit take into account the following 1 Fragile...

Page 9: ...s when brazing the pipe joints Residue can clog pipes and break equipment 6 4 Connecting the refrigerant piping 1 Direction to bring out the pipes The local inter unit piping can be connected either f...

Page 10: ...anual 1 About outside unit multi connection piping kit Install the joint horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 16 1 Do not install v...

Page 11: ...stall the REFNET header so it splits horizontally Refer to figure 15 1 Horizontal surface 2 B arrow view Prohibited pattern Oil remains in the stopping outside unit Change to pattern 1 or pattern 2 Fr...

Page 12: ...0 ft Example 6 a b h 540 ft 8 a i j 540 ft Example 8 a i 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length of REFNET joint to be 1 6 ft th...

Page 13: ...t total capacity index 72 72 111 111 Number of outside unit 2 units Connecting piping kit name BHFP22P100U Refrigerant branch kit name KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Example for indoor...

Page 14: ...249 0 121 0 040 0 175 0 081 0 015 HEAT PUMP SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT RXYQ72 120PYDN RXYQ144 192PYDN RXYQ216 240PYDN 2 2 lb 3 3 lb REFRIGERANT AMOUNT FOR EXCEEDING CONNECTION CAPACI...

Page 15: ...ing and earth terminal If there exists the possibility of reversed phase lose phase momen tary blackout or the power goes on and off while the product is oper ating attach a reversed phase protection...

Page 16: ...d of the master unit The outside unit that connected transmission wiring to indoor unit is the master unit The others are sub unit 7 5 Power Wiring Connection Procedure Be sure to connect the power su...

Page 17: ...shipped the unit contains the refrigerant so use caution when attaching the charge hose Air tight test Pressurize the liquid pipe suction gas pipe HP LP gas pipe and equalizer pipe from the service po...

Page 18: ...d it may require additional charging For charging the additional refrigerant follow the procedure in this chapter And then carry out the check operation 11 1 Before working About the refrigerant tank...

Page 19: ...oor and outside units are turned on H2P will be lit on and the compressor will not operate Check the LED display indicate as shown below In order to ensure uniform refrigerant distribution it may take...

Page 20: ...cedure During Automatic refrigerant charging operation the system will select charging mode cooling mode or heating mode by the tem perature condition as follows When charging in cooling mode the syst...

Page 21: ...ion valve and the valve are closed when charging is finished However the valve will opened when ather operation Check operation nomal operation etc If you leave the tank connected the refrigerant will...

Page 22: ...possible if the outdoor temperature is 75 F or higher Refer to the Operation manual If a knocking sound can be heard in the liquid compression of the com pressor stop the unit immediately and then ene...

Page 23: ...y to comply 1 Calculate the amount of refrigerant lb charged to each system sep arately NOTE Where a single refrigerant facility is divided into 2 entirely indepen dent refrigerant systems then use th...

Page 24: ...20 English NOTES...

Page 25: ...3P215731 2 EM07A038 0712 FS 1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com HT...