background image

English

5

6.

REFRIGERANT PIPING

NOTE

All field piping must be installed by a licensed refrigeration technician 
and must comply with relevant local and national regulations.

After piping work is complete, do not under any circumstances open 
the shutoff valve until 

“7. FIELD WIRING”

 and 

“10. CHECKING OF 

DEVICE AND INSTALLATION CONDITIONS”

 are complete.

Do not use flux when brazing the refrigerant piping. Use the phosphor 
copper brazing filler metal (B-Cu93P-710/795 : ISO 3677) which does 
not require flux.
(Flux has extremely negative effect on refrigerant piping systems. For 
instance, if the chlorine based flux is used, it will cause pipe corrosion or, 
in particular, if the flux contains fluorine, it will damage the refrigerant oil.)

6-1 Selection of piping material and Refrigerant 

branching kit

Use only pipes which are clean inside and outside and which do not 
accumulate harmful sulfur, oxidants, dirt, cutting oils, moisture, or 
other contamination. (Foreign materials inside pipes including oils 
for fabrication must be 9 mg/10 ft or less.)

Use the following items for the refrigerant piping.

Material 

: Jointless phosphor-deoxidized copper pipe

Size 

: See 

“6-5 Example of connection”

 to determine the cor-

rect size.

Thickness 

: Select a thickness for the refrigerant piping which 

complies with national and local laws.

For piping work, follow the maximum tolerated length, difference in 
height, and length after a branch indicated in the “

6-5 Example of 

connection

”.

Outside unit multi connection piping kit and refrigerant branching kit 
(sold separately) are needed for connection of piping between out-
side units (in case of multi system) and piping branches.
Use only separately sold items selected specifically according to the 
outside unit multi connection piping kit, the refrigerant branching kit 
selection in the “

6-5 Example of connection

”.

6-2 Protection against contamination 

when installing pipes

Protect the piping to prevent moisture, dirt, dust, etc. from enter-
ing the piping.

NOTE

Exercise special caution to prevent dirt or dust when passing piping 
through holes in walls and when passing pipe edges to the exterior.

6-3 Pipe connection

Be sure to perform nitrogen permutation or nitrogen blow when 
brazing. 

(Refer to figure 8)

Brazing without performing nitrogen permutation or nitrogen blow 
into the piping will create large quantities of oxidized film on the 
inside of the pipes, adversely affecting valves and compressors in 
the refrigerating system and preventing normal operation.

(Refer to figure 8)

1.

Refrigerant pipe

2.

Location to be brazed

3.

Nitrogen

4.

Taping

5.

Handy valve

6.

Regulator

The pressure regulator for the nitrogen released when doing the 
brazing should be set to about 2.9 psi (Enough to feel a slight 
breeze on your cheek).

NOTE

Do not use anti-oxidants when brazing the pipe joints.
Residue can clog pipes and break equipment.

6-4 Connecting the refrigerant piping
1.

Direction to bring out the pipes
The local inter unit piping can be connected either forward or to the 
sides (taken out through the bottom) as shown in the figure 10. 
When passing out through the bottom, use the knock hole in the bot-
tom frame.

(Refer to figure 10)

1.

Left-side connection

2.

Front connection

3.

Right-side connection

Precautions when knocking out knock holes

Open knock hole (large, small) in the base frame by drilling the 4 
concave around it with a 6mm bit. 

(Refer to figure 11)

(Refer to figure 11)

1.

Knock hole (large : for liquid pipe, suction gas pipe and low 
side equalizer pipe)

2.

Knock hole (small : for high side equalizer pipe)

3.

Drill

4.

Concave section (4 points)

Be sure to avoid damaging the casing.

After knocking out the holes, we recommend you to remove any 
burrs and paint them using the repair paint to prevent rusting.

When passing electrical wiring through the knock holes, protect the wir-
ing with a conduit or bushings, making sure not to damage the wiring.

2.

Removing Pinch Piping

When connecting refrigerant piping to an outside unit, remove the 
pinch piping using the procedure in the figure 12.

(Refer to figure 12)

About handling of shutoff valves, refer to [Shutoff valve operation 
procedure] in 

“11-1 Before working”

.

CAUTION

After removing the gass, remove the pinch piping.
Any gas remaining inside may blow off the pinch piping when you 
dissolve the brazing, causing damage.

(Refer to figure 12)

1.

Pich piping (4 pieces)

2.

Do not remove the relay piping.

3.

Pinch piping

4.

Procedure 1 : Confirm the shutoff valve is closed.

5.

Procedure 2 : Connect a charge hose to the service port of 
shutoff valve and remove the gas in the pinch piping.

6.

Procedure 3 : After removing the gas in the pinch piping, dis-
solve the brazing using a burner and remove the pinch piping.

3.

Connecting refrigerant piping to outside units

Figure 13 shows the example of connecting refrigerant piping to out-
side units.

The local inter unit piping next accesorry pipes are field supplyed.

About the detail of connecting pipes between outside units on out-
side unit multi system, refer to the 

"4. Precautions when connect-

ing piping between outside units"

 and the installation manual 

attached to the outside unit multi connection piping kit.

(Refer to figure 13-1)

1.

When connected to the front

2.

When connected at lateral side (bottom)

3.

Remove the shutoff valve cover to connect.

4.

Remove the knock hole on the bottom frame and route the 
piping under the bottom frame.

5.

Liquid pipe shutoff valve

6.

Low side equalizer pipe shutoff valve

7.

Gas pipe shutoff valve

8.

High side equalizer pipe shutoff valve

9.

Brazing

10.

Liquid side accessory pipe (1)

11.

Low side equalizer accessory pipe (1)

12.

Gas side accessory pipe (1)

Place

Installation period

Protection method

Outdoor

More than a month

Pinch the pipe

Less than a month

Pinch or tape the pipe

Indoor

Regardless of the period

01_EN_3P215731-2.fm  Page 5  Tuesday, December 4, 2007  12:04 PM

Summary of Contents for RXYQ120PYDN

Page 1: ...INSTALLATION MANUAL System air conditioner RXYQ72PYDN RXYQ96PYDN RXYQ120PYDN RXYQ144PYDN RXYQ168PYDN RXYQ192PYDN RXYQ216PYDN RXYQ240PYDN English Fran ais Espa ol...

Page 2: ...8 11 3 4 Pattern 3 2 1 2 1 60 3 1 4 2 5 2 in 40 4 0 40 6 0 60 60 figure 1 figure 3 figure 2 4 1 2 3 1 1 2 3 7 8 3 7 8 3 7 8 5 3 7 8 3 7 8 3 7 8 1 2 3 4 5 figure 4 figure 6 figure 5 A B 1 4 3 2 30 1 8...

Page 3: ...4 1 5 2 B 1 2 1 1 1 1 5 16 1 16 2 16 3 6 2 3 4 4 C D 7 8 3 4 6 7 1 1 2 3 4 5 2 1 4 3 2 1 3 1 1 2 6 1 2 7 5 TOIN DUNIT F1 F2 TOOUT DUNIT F1 F2 TOMULTIUNIT Q1 Q2 A1P TOMULTIUNIT Q1 Q2 2 4 A1P 8 F1 F2 F1...

Page 4: ...re 30 figure 32 figure 28 figure 24 1 2 3 4 5 6 7 8 9 10 12 11 1 2 3 4 5 6 7 8 9 10 13 15 15 16 F17 11 12 19 20 14 18 1 2 1 2 3 1 2 3 4 5 1 2 2 3 5 6 4 1 2 3 4 10 13 11 5 6 7 8 9 12 15 16 17 18 14 1 2...

Page 5: ...ired to take adequate measures Meaning of danger warning caution and note symbols DANGER Indicates an imminently hazardous situa tion which if not avoided will result in death or serious injury WARNIN...

Page 6: ...e may occur Do not use a charging cylinder Using a charging cylinder may cause the refrigerant to deteriorate The refrigerant R410A requires strict cautions for keeping the system clean dry and tight...

Page 7: ...he storage location of the accessories is shown in figure 1 NOTE Do not throw away any of the accessories until installation is complete They are needed for installation work Refer to figure 1 1 Clamp...

Page 8: ...HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the carrier claims agent When handling the unit take into account the following 1 Fragile...

Page 9: ...s when brazing the pipe joints Residue can clog pipes and break equipment 6 4 Connecting the refrigerant piping 1 Direction to bring out the pipes The local inter unit piping can be connected either f...

Page 10: ...anual 1 About outside unit multi connection piping kit Install the joint horizontally so that the attached warning label faces strait up and the tilt is within 15 Refer to figure 16 1 Do not install v...

Page 11: ...stall the REFNET header so it splits horizontally Refer to figure 15 1 Horizontal surface 2 B arrow view Prohibited pattern Oil remains in the stopping outside unit Change to pattern 1 or pattern 2 Fr...

Page 12: ...0 ft Example 6 a b h 540 ft 8 a i j 540 ft Example 8 a i 540 ft Equivalent pipe length between outside unit 2 and indoor unit 620 ft Note 1 Assume eqivalent pipe length of REFNET joint to be 1 6 ft th...

Page 13: ...t total capacity index 72 72 111 111 Number of outside unit 2 units Connecting piping kit name BHFP22P100U Refrigerant branch kit name KHRP26M22H or KHRP26M33H KHRP26M33H KHRP26M72H Example for indoor...

Page 14: ...249 0 121 0 040 0 175 0 081 0 015 HEAT PUMP SYSTEM MODEL NAME THE AMOUNT OF REFRIGERANT RXYQ72 120PYDN RXYQ144 192PYDN RXYQ216 240PYDN 2 2 lb 3 3 lb REFRIGERANT AMOUNT FOR EXCEEDING CONNECTION CAPACI...

Page 15: ...ing and earth terminal If there exists the possibility of reversed phase lose phase momen tary blackout or the power goes on and off while the product is oper ating attach a reversed phase protection...

Page 16: ...d of the master unit The outside unit that connected transmission wiring to indoor unit is the master unit The others are sub unit 7 5 Power Wiring Connection Procedure Be sure to connect the power su...

Page 17: ...shipped the unit contains the refrigerant so use caution when attaching the charge hose Air tight test Pressurize the liquid pipe suction gas pipe HP LP gas pipe and equalizer pipe from the service po...

Page 18: ...d it may require additional charging For charging the additional refrigerant follow the procedure in this chapter And then carry out the check operation 11 1 Before working About the refrigerant tank...

Page 19: ...oor and outside units are turned on H2P will be lit on and the compressor will not operate Check the LED display indicate as shown below In order to ensure uniform refrigerant distribution it may take...

Page 20: ...cedure During Automatic refrigerant charging operation the system will select charging mode cooling mode or heating mode by the tem perature condition as follows When charging in cooling mode the syst...

Page 21: ...ion valve and the valve are closed when charging is finished However the valve will opened when ather operation Check operation nomal operation etc If you leave the tank connected the refrigerant will...

Page 22: ...possible if the outdoor temperature is 75 F or higher Refer to the Operation manual If a knocking sound can be heard in the liquid compression of the com pressor stop the unit immediately and then ene...

Page 23: ...y to comply 1 Calculate the amount of refrigerant lb charged to each system sep arately NOTE Where a single refrigerant facility is divided into 2 entirely indepen dent refrigerant systems then use th...

Page 24: ...20 English NOTES...

Page 25: ...3P215731 2 EM07A038 0712 FS 1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com HT...

Reviews: