background image

Installation manual

3

LREQ5~20B7Y1

Air cooled refrigeration condensing unit

4PW74302-1 – 2012.06

2-2 Model series

LREQ5~20

2-3 Example of system configuration

1

Operation manual 

2

Installation manual 

3

Clamps

4

Accessory pipes (Installed on bottom frame)

2-4 Indoor unit constraints

• Install an R410A mechanical thermostatic expansion valve on 

each indoor unit.

• Insulate the feeler block of the mechanical thermostatic expansion 

valve.

• Install an R410A solenoid valve (Max. operating differential 

pressure of 3.5 MPa [35 bars] or over) on the primary side of the 
mechanical thermostatic expansion valve described above for 
each indoor unit.

• Install a filter on the primary side of the solenoid valve described 

above for each indoor unit. Determine the filter mesh count based 
on the size specified by the solenoid valve and mechanical 
thermostatic expansion valve being used.

• Route the path to the indoor unit heat exchanger so that the flow of 

refrigerant is from top to bottom.

• When installing a number of indoor units, be sure to install them at 

the same level.

• Use either off-cycle defrosting or electric heater defrosting as the 

defrosting type. Hot-gas defrosting models cannot be used.

• Set the total value of the internal volume for the evaporator 

(Refrigerator/Freezer) to connect and the amount of refrigerant 
inside the evaporator that can be recovered in the condenshing 
unit by closing the liquid solenoid valve installed on the 
refrigeration-side to the below amount or lower.
LREQ5, 6: 22 l or lower
LREQ8, 10, 12: 33 l or lower
LREQ15, 20: 42 l or lower

3. SELECTION OF LOCATION

Select a location for installation that meets the following conditions. 
Get the customer’s permission.

1.

There is no danger of fire due to leakage of inflammable gas.

2.

Select the location of the unit in such a way that neither the 
discharged air nor the sound generated by the unit disturb anyone.

3.

The foundation is strong enough to support the weight of the unit 
and the floor is flat to prevent vibration and noise generation.

4.

The piping length between the outdoor unit and the indoor unit may 
not exceed the allowable piping length. 
(Refer to

 

"6. REFRIGERANT PIPING" on page 5

)

5.

Locations where the unit’s suction vent and outlet vent do not 
generally face the wind. 
Wind blowing directly into the suction or outlet vents will interfere 
with the unit’s operation.
If necessary, install some kind of obstruction to block the wind.

6.

The space around the unit is adequate for servicing and the 
minimum space for air inlet and air outlet is available. 
(See the 

"Installation Space Examples" on page 3

 for the minimum 

space requirements.)

Installation Space Examples

• The installation space requirement shown in the following figure is 

a reference for cooling operation when the outdoor temperature is 
32°C. 
If the design outdoor temperature exceeds 32°C or the heat load 
exceeds maximum capacity in all the outdoor unit, take an even 
large space on the intake shown in the following figure.

• During installation, install the units using the most appropriate of 

the patterns shown in the following figure for the location in 
question, taking into consideration human traffic and wind.

• If the number of units installed is more than that shown in the 

pattern in the following figure, install the units so there are no short 
circuits.

• As regards space in front of the unit, consider the space needed for 

the local refrigerant piping when installing the units. 

• If the work conditions in the following figure do not apply, contact 

your dealer or Daikin directly.

Name

Liquid side 

accessory 

pipe (1)

Liquid side 

accessory 

pipe (2)

Others

Quantity

1 pc.

1 pc.

1 pc. about each item

Shape

Thin

• Operation manual
• Installation manual
• “ADDITIONAL REF. 

CHARGE” label

Name

Outdoor unit

Indoor unit

Unit cooler

Showcase

Shape

Name

Indoor unit

Control panel 

(Defrost)

Warning 

panel

Unit cooler

Showcase

Shape

1, 2, 3

1, 2, 3

4

4

LREQ5, LREQ6

LREQ8, LREQ10, LREQ12

1, 2, 3

4

LREQ15, LREQ20

Summary of Contents for LREQ5B7Y1

Page 1: ...INSTALLATION MANUAL LREQ5B7Y1 LREQ6B7Y1 LREQ8B7Y1 LREQ10B7Y1 LREQ12B7Y1 LREQ15B7Y1 LREQ20B7Y1 Air cooled refrigeration condensing unit...

Page 2: ...jennom positiv bed mmelse av B if lge Sertifikat C som det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jot...

Page 3: ...PS vastav k llastunud temperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksima...

Page 4: ...on manual Improper installation may result in water leakage electric shocks or fire When installing the unit in a small room take measures so that the refrigerant may not exceed the limiting concentra...

Page 5: ...ons be observed for keeping the system clean dry and tightly sealed Read the chapter 6 REFRIGERANT PIPING on page 5 carefully and follow these procedures correctly A Clean and dry Strict measures must...

Page 6: ...disturb anyone 3 The foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration and noise generation 4 The piping length between the outdoor unit and the...

Page 7: ...ary to take measures against leakage See Engineering Data for details 4 HANDLING THE UNIT 1 Decide on the transportation route 2 If a forklift is to be used pass the forklift arms through the large op...

Page 8: ...ng refrigerant piping heat exchangers Keep the following points in mind for the reuse of existing refrigerant piping heat exchangers A malfunction may result if there is deficiency Do not use the exis...

Page 9: ...oor unit H 10 m Note A trap is required at 5 m intervals from outdoor unit d1 e B d2 C c D1 F E f D2 A b a Outdoor unit Showcase Unit cooler Gas piping Liquid piping H Refrigerant piping size Unit mm...

Page 10: ...e operation manual of the dryer 6 5 Connecting the refrigerant piping CAUTION In addition to gas and liquid shutoff valves this unit has a maintenance shutoff valve see diagram below Do not operate th...

Page 11: ...dripped out in case the recovery was not complete and only then proceed with connection of the field piping 1 Service port 2 Stop valve 3 Point of pipe cutting just above brazing point or above markin...

Page 12: ...apply a screw lock agent to the screw thread Do not apply a screw lock agent for flare nut use to the sealing part Be sure to tighten the cap securely after the work Refer to Operation Method of Shuto...

Page 13: ...eriorate power factor improvement effect but also may cause capacitor abnormal heating accident due to high frequency waves Only proceed with wiring work after blocking off all power Always ground wir...

Page 14: ...eakage Be sure to connect the power wiring to the power wiring terminal block and secure it as described in 7 2 Procedure for incoming wiring on page 11 Do not connect the power supply to the terminal...

Page 15: ...EN IEC61000 3 11 1 provided that the system impedance Zsys is less than or equal to Zmax and EN IEC61000 3 12 2 provided that the short circuit power Ssc is greater than or equal to the minimum Ssc va...

Page 16: ...y the washer Otherwise the earth wire may not contact sufficiently and the earthing effect of the wire may be lost Do not finish strand wire with solder 7 4 Procedure for wiring inside units Referring...

Page 17: ...red to have passed if there is no decrease in the pressure over a period of 24 hours If there is a decrease in the pressure check for and repair leaks Vacuum drying Operate the vacuum pump for more th...

Page 18: ...of piping material on page 6 2 Make sure insulation work is done See 8 2 Thermal insulation work on page 14 3 Make sure there is no faulty refrigerant piping See 6 REFRIGERANT PIPING on page 5 9 CHEC...

Page 19: ...ling 1The cylinder s internal pressure will drop when there is little refrigerant remaining in the cylinder making it impossible to charge the unit even if the liquid shutoff valve opening is adjusted...

Page 20: ...lay The contents of a LED H2P display are as follows How to check malfunction code By operating the pushbutton switches on the PCB malfunction code items can be displayed on the condensing unit 1 Make...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...4PW74302 1 2012 06 Copyright 2012 Daikin 4PW74302 1 00000003...

Reviews: