Installation manual

7

LREQ5~20B7Y1

Air cooled refrigeration condensing unit

4PW74302-1 – 2012.06

6-2 Protection against contamination when 

installing pipes

Protect the piping to prevent moisture, dirt, dust, etc. from entering the 
piping.

Note

Exercise special caution to prevent dirt or dust when passing piping 
through holes in walls and when passing pipe edges to the exterior.

6-3 Pipe connection

• Be sure to perform nitrogen permutation or nitrogen blow when brazing.

Brazing without performing nitrogen permutation or nitrogen blow 
into the piping will create large quantities of oxidized film on the 
inside of the pipes, adversely affecting valves and compressors in 
the refrigerating system and preventing normal operation.

• The pressure regulator for the nitrogen released when doing the 

brazing should be set to 0.02 MPa (about 0.2 kg/cm

2

:Enough to 

feel a slight breeze on your cheek).

Note

Do not use anti-oxidants when brazing the pipe joints.
Residue can clog pipes and break equipment.

6-4 Drier installation

CAUTION

This product requires that a drier be installed on liquid piping on site.
(Operating the unit without a drier installed may result in equipment 
failure.)

Select a drier from the following chart:

• Install the drier in a horizontal orientation wherever possible.
• Install the drier as close to the outdoor unit as possible.
• Remove the drier cap immediately before brazing (to prevent 

absorption of airborne moisture).

• Follow instructions in the drier instruction manual concerning drier 

brazing.

• Repair any burning of drier paint that occurs during drier brazing. 

Contact the manufacturer for more information about paint for 
repair use.

• Flow direction is specified for some type of the dryer.

Set the flow direction according to the operation manual of the 
dryer.

6-5 Connecting the refrigerant piping

CAUTION

• In addition to gas and liquid shutoff valves, this unit has a 

maintenance shutoff valve (see diagram below).

• Do not operate the maintenance shutoff valve*.

(The factory setting for the maintenance shutoff valve is “open.” 
During operation, always leave this valve in the open position. 
Operating the unit with the valve in the closed position may cause 
the compressor to fail.)

1.

Directions to bring out the pipes

The local interunit piping can be connected either forward or to the 
sides (taken out through the bottom) as shown in the following 
figure.
When passing out through the bottom, use the knock hole in the 
bottom frame.

Precautions when knocking out knock holes

• Open knock hole in the base frame by drilling the 4 concave around 

it with a 6 mm bit.

• Be sure to avoid damaging the casing
• After knocking out the holes, we recommend you remove any burrs 

and paint them using the repair paint to prevent rusting.

• When passing electrical wiring through the knock holes, protect the 

wiring with a conduit or bushings, making sure not to damage the 
wiring.

Place

Installation period

Protection method

Outdoor

More than a month

Pinch the pipe

Less than a month

Pinch or tape the pipe

Indoor

Regardless of the period

Model

Required dryer core 

(recommended type)

LREQ5
LREQ6

80 g (100% molecular sieve equivalent)
(DML083/DML083S : Danfoss made)

LREQ8
LREQ10
LREQ12

160 g (100% molecular sieve equivalent)
(DML163/DML163S : Danfoss made)

LREQ15
LREQ20

160 g (100% molecular sieve equivalent)
(DML164/DML164S : Danfoss made)

Refrigerant pipe

Regulator

Handy valve

Taping

Nitrogen

Nitrogen

Location to 
be brazed

Liquid side shutoff valve 
(provided with service port)

Gas side shutoff valve 
(provided with service port)

* Maintenance shutoff valve

(Do not operate)

(Do not operate)

* Maintenance shutoff valve

Right-side connection

Front connection

Left-side connection

Knock hole

Concave section 
(4 places)

Drill

Summary of Contents for LREQ5B7Y1

Page 1: ...INSTALLATION MANUAL LREQ5B7Y1 LREQ6B7Y1 LREQ8B7Y1 LREQ10B7Y1 LREQ12B7Y1 LREQ15B7Y1 LREQ20B7Y1 Air cooled refrigeration condensing unit...

Page 2: ...jennom positiv bed mmelse av B if lge Sertifikat C som det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jot...

Page 3: ...PS vastav k llastunud temperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksima...

Page 4: ...on manual Improper installation may result in water leakage electric shocks or fire When installing the unit in a small room take measures so that the refrigerant may not exceed the limiting concentra...

Page 5: ...ons be observed for keeping the system clean dry and tightly sealed Read the chapter 6 REFRIGERANT PIPING on page 5 carefully and follow these procedures correctly A Clean and dry Strict measures must...

Page 6: ...disturb anyone 3 The foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration and noise generation 4 The piping length between the outdoor unit and the...

Page 7: ...ary to take measures against leakage See Engineering Data for details 4 HANDLING THE UNIT 1 Decide on the transportation route 2 If a forklift is to be used pass the forklift arms through the large op...

Page 8: ...ng refrigerant piping heat exchangers Keep the following points in mind for the reuse of existing refrigerant piping heat exchangers A malfunction may result if there is deficiency Do not use the exis...

Page 9: ...oor unit H 10 m Note A trap is required at 5 m intervals from outdoor unit d1 e B d2 C c D1 F E f D2 A b a Outdoor unit Showcase Unit cooler Gas piping Liquid piping H Refrigerant piping size Unit mm...

Page 10: ...e operation manual of the dryer 6 5 Connecting the refrigerant piping CAUTION In addition to gas and liquid shutoff valves this unit has a maintenance shutoff valve see diagram below Do not operate th...

Page 11: ...dripped out in case the recovery was not complete and only then proceed with connection of the field piping 1 Service port 2 Stop valve 3 Point of pipe cutting just above brazing point or above markin...

Page 12: ...apply a screw lock agent to the screw thread Do not apply a screw lock agent for flare nut use to the sealing part Be sure to tighten the cap securely after the work Refer to Operation Method of Shuto...

Page 13: ...eriorate power factor improvement effect but also may cause capacitor abnormal heating accident due to high frequency waves Only proceed with wiring work after blocking off all power Always ground wir...

Page 14: ...eakage Be sure to connect the power wiring to the power wiring terminal block and secure it as described in 7 2 Procedure for incoming wiring on page 11 Do not connect the power supply to the terminal...

Page 15: ...EN IEC61000 3 11 1 provided that the system impedance Zsys is less than or equal to Zmax and EN IEC61000 3 12 2 provided that the short circuit power Ssc is greater than or equal to the minimum Ssc va...

Page 16: ...y the washer Otherwise the earth wire may not contact sufficiently and the earthing effect of the wire may be lost Do not finish strand wire with solder 7 4 Procedure for wiring inside units Referring...

Page 17: ...red to have passed if there is no decrease in the pressure over a period of 24 hours If there is a decrease in the pressure check for and repair leaks Vacuum drying Operate the vacuum pump for more th...

Page 18: ...of piping material on page 6 2 Make sure insulation work is done See 8 2 Thermal insulation work on page 14 3 Make sure there is no faulty refrigerant piping See 6 REFRIGERANT PIPING on page 5 9 CHEC...

Page 19: ...ling 1The cylinder s internal pressure will drop when there is little refrigerant remaining in the cylinder making it impossible to charge the unit even if the liquid shutoff valve opening is adjusted...

Page 20: ...lay The contents of a LED H2P display are as follows How to check malfunction code By operating the pushbutton switches on the PCB malfunction code items can be displayed on the condensing unit 1 Make...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...4PW74302 1 2012 06 Copyright 2012 Daikin 4PW74302 1 00000003...

Reviews: