LREQ5~20B7Y1

Air cooled refrigeration condensing unit

4PW74302-1 – 2012.06

Installation manual

6

6-1 Selection of piping material

• Make sure that the inner side and outer side of the piping used is clean and free of contaminants, such as sulphur, oxide, dust, chips, oil and fat, and water.

It is desirable that the maximum oil adhesion in the piping is 30 mg per 10 m.

• Use the following type of refrigerant piping.

Material: Seamless phosphorus deoxidized copper tube (C1220T-O for a maximum outer diameter of 15.9 mm and C1220T-1/2H for a minimum 

outer diameter of 19.1 mm)

Refrigerant piping size and wall thickness: Decide the size and thickness from the following table.

(This product uses R410A. The withstand pressure of O type may be insufficient if it is used for piping with a minimum diameter of 
19.1 mm. Therefore, be sure to use 1/2 H type with a minimum thickness of 1.0 mm.
If O type is used for piping with a minimum diameter of 19.1 mm, a minimum thickness of 1.2 mm will be required. In that case, be sure 
to perform the blazing of each joint.)

• Be sure to perform piping work within the range specified in the 

following table 

Refrigerant piping length
Max. permissible 
one-way piping 
length (equivalent 
length)

LREQ5~20

Te = –20~+10°C
a + b + c + d 

130 m (d is d1 or d2 whichever is longer)

Te = –45~–20°C
a + b + c + d 

100 m (d is d1 or d2 whichever is longer)

Max. branch piping length (actual length)

b + c + d 

30 m (d is d1 or d2 whichever is longer)

Max. difference in 
height between 
indoor and outdoor 
units

unit below outdoor 
unit

35 m (Note)

unit above outdoor 
unit

10 m 

Note: A trap is required at 5 m intervals from outdoor unit.

d1

e

B

d2

C

c

D1

F

E

f

D2

A

b

a

Outdoor unit

Showcase

Unit 

cooler

Gas piping

Liquid piping

H

Refrigerant piping size

(Unit: mm)

Outdoor unit side

Piping size
Liquid pipe

Gas pipe

50 m or less

50~130 m

LREQ5, LREQ6

Ø9.5 x 0.8 (O type)

Ø22.2 x 1.0 (1/2 H type or H type)

LREQ8, LREQ10

Ø9.5 x 0.8 (O type)

Ø12.7 x 0.8 (O type)

Ø28.6 x 1.0 (1/2 H type or H type)

LREQ12

Ø12.7 x 0.8 (O type)

Ø28.6 x 1.0 (1/2 H type or H type)

LREQ15, LREQ20

Ø12.7 x 0.8 (O type)

Ø34.9 x 1.2 (1/2 H type or H type)

Piping between 
branching areas  (B, b, 
C, c)

Select the piping from the following table in accordance with the total capacity of indoor units connected 
downstream

Total capacity of indoor units after branching

Liquid pipe size

less than 4.0 kW

Ø6.4 x 0.8 (O type)

4.0 kW over and less than 14.0 kW

Ø9.5 x 0.8 (O type)

14.0 kW or over

Ø12.7 x 0.8 (O type)

Total capacity of indoor units after branching

Gas pipe size

Medium temperature 
(not less than –20°C)

Low temperature 
(–20°C or less)

less than 1.0 kW

Ø9.5 x 0.8 (O type)

1.0 kW over and less than 6.0 kW

less than 2.3 kW

Ø12.7 x 0.8 (O type)

6.0 kW over and less than 9.9 kW

2.3 kW over and less than 4.4 kW

Ø15.9 x 1.0 (O type)

9.9 kW over and less than 14.5 kW

4.4 kW over and less than 6.4 kW

Ø19.1 x 1.0 (O type)

14.5 kW over and less than 25.0 kW

6.4 kW over and less than 10.8 kW

Ø22.2 x 1.0 (O type)

25.0 kW over and less than 31.0 kW

10.8 kW over and less than 13.4 kW

Ø28.6 x 1.0 (O type)

31.0 kW or over

13.4 kW or over

Ø34.9 x 1.2 (O type)

No size after branching can exceed the size of any upstream piping.

Piping between 
branching areas and 
each unit

Adjust the size of the piping so that it will coincide with the size of piping connecting to the indoor unit

Summary of Contents for LREQ5B7Y1

Page 1: ...INSTALLATION MANUAL LREQ5B7Y1 LREQ6B7Y1 LREQ8B7Y1 LREQ10B7Y1 LREQ12B7Y1 LREQ15B7Y1 LREQ20B7Y1 Air cooled refrigeration condensing unit...

Page 2: ...jennom positiv bed mmelse av B if lge Sertifikat C som det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jot...

Page 3: ...PS vastav k llastunud temperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksima...

Page 4: ...on manual Improper installation may result in water leakage electric shocks or fire When installing the unit in a small room take measures so that the refrigerant may not exceed the limiting concentra...

Page 5: ...ons be observed for keeping the system clean dry and tightly sealed Read the chapter 6 REFRIGERANT PIPING on page 5 carefully and follow these procedures correctly A Clean and dry Strict measures must...

Page 6: ...disturb anyone 3 The foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration and noise generation 4 The piping length between the outdoor unit and the...

Page 7: ...ary to take measures against leakage See Engineering Data for details 4 HANDLING THE UNIT 1 Decide on the transportation route 2 If a forklift is to be used pass the forklift arms through the large op...

Page 8: ...ng refrigerant piping heat exchangers Keep the following points in mind for the reuse of existing refrigerant piping heat exchangers A malfunction may result if there is deficiency Do not use the exis...

Page 9: ...oor unit H 10 m Note A trap is required at 5 m intervals from outdoor unit d1 e B d2 C c D1 F E f D2 A b a Outdoor unit Showcase Unit cooler Gas piping Liquid piping H Refrigerant piping size Unit mm...

Page 10: ...e operation manual of the dryer 6 5 Connecting the refrigerant piping CAUTION In addition to gas and liquid shutoff valves this unit has a maintenance shutoff valve see diagram below Do not operate th...

Page 11: ...dripped out in case the recovery was not complete and only then proceed with connection of the field piping 1 Service port 2 Stop valve 3 Point of pipe cutting just above brazing point or above markin...

Page 12: ...apply a screw lock agent to the screw thread Do not apply a screw lock agent for flare nut use to the sealing part Be sure to tighten the cap securely after the work Refer to Operation Method of Shuto...

Page 13: ...eriorate power factor improvement effect but also may cause capacitor abnormal heating accident due to high frequency waves Only proceed with wiring work after blocking off all power Always ground wir...

Page 14: ...eakage Be sure to connect the power wiring to the power wiring terminal block and secure it as described in 7 2 Procedure for incoming wiring on page 11 Do not connect the power supply to the terminal...

Page 15: ...EN IEC61000 3 11 1 provided that the system impedance Zsys is less than or equal to Zmax and EN IEC61000 3 12 2 provided that the short circuit power Ssc is greater than or equal to the minimum Ssc va...

Page 16: ...y the washer Otherwise the earth wire may not contact sufficiently and the earthing effect of the wire may be lost Do not finish strand wire with solder 7 4 Procedure for wiring inside units Referring...

Page 17: ...red to have passed if there is no decrease in the pressure over a period of 24 hours If there is a decrease in the pressure check for and repair leaks Vacuum drying Operate the vacuum pump for more th...

Page 18: ...of piping material on page 6 2 Make sure insulation work is done See 8 2 Thermal insulation work on page 14 3 Make sure there is no faulty refrigerant piping See 6 REFRIGERANT PIPING on page 5 9 CHEC...

Page 19: ...ling 1The cylinder s internal pressure will drop when there is little refrigerant remaining in the cylinder making it impossible to charge the unit even if the liquid shutoff valve opening is adjusted...

Page 20: ...lay The contents of a LED H2P display are as follows How to check malfunction code By operating the pushbutton switches on the PCB malfunction code items can be displayed on the condensing unit 1 Make...