LREQ5~20B7Y1

Air cooled refrigeration condensing unit

4PW74302-1 – 2012.06

Installation manual

10

When connected at lateral side (bottom)

Remove the knock hole on the bottom frame and route the piping 
under the bottom frame.

CAUTION

• Check that the on-site piping does not come in contact with other 

piping, the bottom frame, or side plate of the product.

Precautions for Piping

Perform piping branching with the following conditions kept in mind.

• At the time of branching the liquid piping, use a T-joint or Y-joint 

and branch it horizontally. This will prevent an uneven flow of 
refrigerant.

• At the time of branching gas piping, use a T-joint and branch it so 

that the branched piping will be located above the main piping (see 
the illustration below). This will prevent the stay of refrigerant oil in 
the indoor unit not in operation.

• Use a Y-joint for the liquid refrigerant branch and have the piping 

branch horizontally.

• Use a T-joint for the gas refrigerant branch and connect from the 

top of the main piping.

• Make sure that the horizontal portion of the gas piping slants 

downward to the outdoor unit (see the illustration above).

• If the outdoor unit is located above, make a trap on the gas pipe at 

5 m intervals from outdoor unit. This will ensure the smooth 
returning of oil in the piping slanting upward.

7. FIELD WIRING

To electric engineering contractors

• Be sure to install an earth leakage breaker. The product 

incorporates inverter equipment. In order to prevent the 
malfunctioning of the earth leakage breaker, make sure that the 
earth leakage breaker withstands harmonic interference.

• Do not operate the condensing unit until refrigerant piping work is 

completed, or otherwise the compressor will malfunction.

• Do not remove any electrical components such as thermistors or 

sensors when connecting power supply wires or transmission 
wires. The compressor may malfunction if the condensing unit is 
operated with such electrical components removed. 

CAUTION

• All field wiring and components must be installed by a licensed 

electrician and must comply with relevant local and national 
regulations.

• Be sure to use a dedicated power circuit. Never use a power supply 

shared by another appliance.

• Never install a phase advancing capacitor. As this unit is equipped 

with an inverter, installing a phase advancing capacitor will not only 
deteriorate power factor improvement effect, but also may cause 
capacitor abnormal heating accident due to high-frequency waves.

• Only proceed with wiring work after blocking off all power.
• Always ground wires in accordance with relevant local and national 

regulations.

• This machine includes an inverter device. Connect earth and leave 

charge to eliminate the impact on other devices by reducing noise 
generated from the inverter device and to prevent leaked current 
from being charged in the outer hull of the product.

• Do not connect the ground wire to gas pipes, sewage pipes, 

lightning rods, or telephone ground wires.

Gas pipes:

 can explode or catch fire if there is a gas leak.

Sewage pipes:

 no grounding effect is possible if hard plastic 

piping is used.

Telephone ground wires and lightning rods:

 dangerous when 

struck by lightning due to abnormal rise in electrical potential in the 
grounding.

• Be sure to install an earth leakage circuit breaker.

This unit uses an inverter, so install the earth leakage circuit 
breaker that be capable of handling high harmonics in order to 
prevent malfunctioning of the earth leakage circuit breaker itself.

• Earth leakage circuit breaker which are especially for protecting 

ground-faults should be used in conjunction with main switch or 
fuse for use with wiring.

• Electrical wiring must be done in accordance with the wiring 

diagrams and the description herein.

• Do not operate until refrigerant piping work is completed.

(If operated before complete the piping work, the compressor may 
be broken down.)

• Never remove thermistor, sensor or etc. when connecting power 

wiring and transmission wiring.
(If operated with thermistor, sensor or etc. removed, the 
compressor may be broken down.)

Liquid side shutoff valve

Gas side shutoff valve

Gas side 
accessory pipe (1)

Gas side 
accessory pipe (2)

Brazing

Brazing

Liquid side 
(field supply)

Gas side 
(field supply)

Liquid side 
accessory pipe (1)

Liquid side 
accessory pipe (2)

Knockout hole

Brazing

Brazing

Punch the knock hole.

LREQ5~12

Liquid side 
shutoff valve

Gas side 
shutoff valve

Gas side 
accessory pipe (2)

Gas side 
accessory pipe (1)

Brazing

Brazing

Liquid side 
(field supply)

Gas side 
(field supply)

Liquid side 
accessory pipe (2)

Liquid side 
accessory pipe (1)

Knockout hole

Punch the knock hole.

Brazing

Brazing

LREQ15, LREQ20

Horizontal 
surface

±30° or less

A-arrow view

A

Y-joint

T-joint

Main piping

Indoor unit side

Outdoor unit side

Branch piping

Make the piping 
slant downward

Branch piping

Make the piping 
slant downward

Main piping
Make the piping 
slant downward

T-joint

Summary of Contents for LREQ5B7Y1

Page 1: ...INSTALLATION MANUAL LREQ5B7Y1 LREQ6B7Y1 LREQ8B7Y1 LREQ10B7Y1 LREQ12B7Y1 LREQ15B7Y1 LREQ20B7Y1 Air cooled refrigeration condensing unit...

Page 2: ...jennom positiv bed mmelse av B if lge Sertifikat C som det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jot...

Page 3: ...PS vastav k llastunud temperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksima...

Page 4: ...on manual Improper installation may result in water leakage electric shocks or fire When installing the unit in a small room take measures so that the refrigerant may not exceed the limiting concentra...

Page 5: ...ons be observed for keeping the system clean dry and tightly sealed Read the chapter 6 REFRIGERANT PIPING on page 5 carefully and follow these procedures correctly A Clean and dry Strict measures must...

Page 6: ...disturb anyone 3 The foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration and noise generation 4 The piping length between the outdoor unit and the...

Page 7: ...ary to take measures against leakage See Engineering Data for details 4 HANDLING THE UNIT 1 Decide on the transportation route 2 If a forklift is to be used pass the forklift arms through the large op...

Page 8: ...ng refrigerant piping heat exchangers Keep the following points in mind for the reuse of existing refrigerant piping heat exchangers A malfunction may result if there is deficiency Do not use the exis...

Page 9: ...oor unit H 10 m Note A trap is required at 5 m intervals from outdoor unit d1 e B d2 C c D1 F E f D2 A b a Outdoor unit Showcase Unit cooler Gas piping Liquid piping H Refrigerant piping size Unit mm...

Page 10: ...e operation manual of the dryer 6 5 Connecting the refrigerant piping CAUTION In addition to gas and liquid shutoff valves this unit has a maintenance shutoff valve see diagram below Do not operate th...

Page 11: ...dripped out in case the recovery was not complete and only then proceed with connection of the field piping 1 Service port 2 Stop valve 3 Point of pipe cutting just above brazing point or above markin...

Page 12: ...apply a screw lock agent to the screw thread Do not apply a screw lock agent for flare nut use to the sealing part Be sure to tighten the cap securely after the work Refer to Operation Method of Shuto...

Page 13: ...eriorate power factor improvement effect but also may cause capacitor abnormal heating accident due to high frequency waves Only proceed with wiring work after blocking off all power Always ground wir...

Page 14: ...eakage Be sure to connect the power wiring to the power wiring terminal block and secure it as described in 7 2 Procedure for incoming wiring on page 11 Do not connect the power supply to the terminal...

Page 15: ...EN IEC61000 3 11 1 provided that the system impedance Zsys is less than or equal to Zmax and EN IEC61000 3 12 2 provided that the short circuit power Ssc is greater than or equal to the minimum Ssc va...

Page 16: ...y the washer Otherwise the earth wire may not contact sufficiently and the earthing effect of the wire may be lost Do not finish strand wire with solder 7 4 Procedure for wiring inside units Referring...

Page 17: ...red to have passed if there is no decrease in the pressure over a period of 24 hours If there is a decrease in the pressure check for and repair leaks Vacuum drying Operate the vacuum pump for more th...

Page 18: ...of piping material on page 6 2 Make sure insulation work is done See 8 2 Thermal insulation work on page 14 3 Make sure there is no faulty refrigerant piping See 6 REFRIGERANT PIPING on page 5 9 CHEC...

Page 19: ...ling 1The cylinder s internal pressure will drop when there is little refrigerant remaining in the cylinder making it impossible to charge the unit even if the liquid shutoff valve opening is adjusted...

Page 20: ...lay The contents of a LED H2P display are as follows How to check malfunction code By operating the pushbutton switches on the PCB malfunction code items can be displayed on the condensing unit 1 Make...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...4PW74302 1 2012 06 Copyright 2012 Daikin 4PW74302 1 00000003...

Reviews: