Installation manual

15

LREQ5~20B7Y1

Air cooled refrigeration condensing unit

4PW74302-1 – 2012.06

• Liquid pipe arrival minimum temperature 0°C

Gas pipe arrival minimum temperature –45°C

• Reinforce the insulation material for the refrigerant piping 

according to the environment of thermal installation. Otherwise, the 
surface of the insulation material may result in dew condensation.

• If the dew condensation water on the shutoff valves is likely to flow 

to the indoor unit side through the clearance between the insulation 
material and piping because the outdoor unit is installed above the 
indoor unit or for some other reasons, perform appropriate 
treatment such as the caulking of the joints (see the illustrations 
below).

• Attach the cover of the piping outlet with a knock hole opened. If 

there is a feature of small animals intruding through the piping 
outlet, cover the piping outlet with a blocking material (field supply) 
on completion of the steps of 

"10. REFRIGERANT 

REPLENISHMENT" on page 15

 (see the illustrations below).

Use the piping outlet for jobs required during the steps of 

"10. REFRIGERANT REPLENISHMENT" on page 15

 (e.g., a job 

of taking in the charge hose).

Note

• After knocking out the holes, we recommend you remove burrs in 

the knock holes and paint the edges and areas around the edges 
using the repair paint.

8-3 Checking of device and installation conditions

Be sure to check the followings.

For those doing electrical work

See 

"7-2 Procedure for incoming wiring" on page 11

.

1.

Make sure there is no faulty power wiring or loosing of a nut.
See 

"7-3 Procedure for power supply wiring" on page 12

.

2.

Has the insulation of the main power circuit deteriorated?
Measure the insulation and check the insulation is above regular 
value in accordance with relevant local and national regulations.

For those doing pipe work

1.

Make sure piping size is correct.
See 

"6-1 Selection of piping material" on page 6

.

2.

Make sure insulation work is done. 
See 

"8-2 Thermal insulation work" on page 14

.

3.

Make sure there is no faulty refrigerant piping.
See 

"6. REFRIGERANT PIPING" on page 5

.

9. CHECKS AFTER WORK COMPLETION

• Make sure the following works are complete in accordance with the 

installation manual.

Piping work

Wiring work

Air tight test/vacuum drying

Installation work for indoor unit

10. REFRIGERANT REPLENISHMENT

For refrigerant filling contractor

Use R410A for refrigerant replenishment.
The R410A refrigerant cylinder is painted with a pink belt.

Warning

Electric Shock Warning

• Securely close the control box lid before turning power on.
• Before turning power on, check through the inspection hole (on the 

left-hand side) of the control box lid that the operation switch is set 
to OFF.
If the operation switch is set to ON, the fan may rotate.

• Check the LED indicators on the PCB (A1P) of the outdoor unit 

through the inspection hole (on the right-hand side) of the control 
box lid after the outdoor unit is turned on (see the illustration).
(The compressor will not operate for approximately 2 minutes after 
the outdoor unit is turned on.
H2P blinks for the first five seconds when the power supply is 
turned on. If the equipment is normal, H2P will be turned off in five 
seconds. H2P lights for abnormality.)

Liquid side 
shutoff valve

Gas side 
shutoff valve

Indoor/Outdoor 
interunit piping

Insulation material

Coking, etc.

Piping lead-out 
hole lid

Gas side piping

Liquid side piping

Open a knock 
hole at

Block 

Inspection hole 
(left-hand side)

Inspection hole 
(right-hand side)

Control box

Inspection hole (left-hand side) 
(upper left-hand side of control box)

Inspection hole (right-hand side) 
(upper right-hand side of control box)

Control box lid

LED

(H1P~8P)

Lift up this tab and 
open the cover.

Inspection 
hole cover

REMOTE OFF

ON

Operation switch 

(factory set: OFF)

( )

Setting of spare parts

For details please refer to the 
INSTRUCTION FOR REPAIR 
WITH SPARE PARTS

OFF

ON

ON

OFF

The evaporation 
temperature setting

Setting by dip switches

It is not used

1

3

DS1

2

3

4

1

2

4

DS2

Summary of Contents for LREQ5B7Y1

Page 1: ...INSTALLATION MANUAL LREQ5B7Y1 LREQ6B7Y1 LREQ8B7Y1 LREQ10B7Y1 LREQ12B7Y1 LREQ15B7Y1 LREQ20B7Y1 Air cooled refrigeration condensing unit...

Page 2: ...jennom positiv bed mmelse av B if lge Sertifikat C som det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jot...

Page 3: ...PS vastav k llastunud temperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksima...

Page 4: ...on manual Improper installation may result in water leakage electric shocks or fire When installing the unit in a small room take measures so that the refrigerant may not exceed the limiting concentra...

Page 5: ...ons be observed for keeping the system clean dry and tightly sealed Read the chapter 6 REFRIGERANT PIPING on page 5 carefully and follow these procedures correctly A Clean and dry Strict measures must...

Page 6: ...disturb anyone 3 The foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration and noise generation 4 The piping length between the outdoor unit and the...

Page 7: ...ary to take measures against leakage See Engineering Data for details 4 HANDLING THE UNIT 1 Decide on the transportation route 2 If a forklift is to be used pass the forklift arms through the large op...

Page 8: ...ng refrigerant piping heat exchangers Keep the following points in mind for the reuse of existing refrigerant piping heat exchangers A malfunction may result if there is deficiency Do not use the exis...

Page 9: ...oor unit H 10 m Note A trap is required at 5 m intervals from outdoor unit d1 e B d2 C c D1 F E f D2 A b a Outdoor unit Showcase Unit cooler Gas piping Liquid piping H Refrigerant piping size Unit mm...

Page 10: ...e operation manual of the dryer 6 5 Connecting the refrigerant piping CAUTION In addition to gas and liquid shutoff valves this unit has a maintenance shutoff valve see diagram below Do not operate th...

Page 11: ...dripped out in case the recovery was not complete and only then proceed with connection of the field piping 1 Service port 2 Stop valve 3 Point of pipe cutting just above brazing point or above markin...

Page 12: ...apply a screw lock agent to the screw thread Do not apply a screw lock agent for flare nut use to the sealing part Be sure to tighten the cap securely after the work Refer to Operation Method of Shuto...

Page 13: ...eriorate power factor improvement effect but also may cause capacitor abnormal heating accident due to high frequency waves Only proceed with wiring work after blocking off all power Always ground wir...

Page 14: ...eakage Be sure to connect the power wiring to the power wiring terminal block and secure it as described in 7 2 Procedure for incoming wiring on page 11 Do not connect the power supply to the terminal...

Page 15: ...EN IEC61000 3 11 1 provided that the system impedance Zsys is less than or equal to Zmax and EN IEC61000 3 12 2 provided that the short circuit power Ssc is greater than or equal to the minimum Ssc va...

Page 16: ...y the washer Otherwise the earth wire may not contact sufficiently and the earthing effect of the wire may be lost Do not finish strand wire with solder 7 4 Procedure for wiring inside units Referring...

Page 17: ...red to have passed if there is no decrease in the pressure over a period of 24 hours If there is a decrease in the pressure check for and repair leaks Vacuum drying Operate the vacuum pump for more th...

Page 18: ...of piping material on page 6 2 Make sure insulation work is done See 8 2 Thermal insulation work on page 14 3 Make sure there is no faulty refrigerant piping See 6 REFRIGERANT PIPING on page 5 9 CHEC...

Page 19: ...ling 1The cylinder s internal pressure will drop when there is little refrigerant remaining in the cylinder making it impossible to charge the unit even if the liquid shutoff valve opening is adjusted...

Page 20: ...lay The contents of a LED H2P display are as follows How to check malfunction code By operating the pushbutton switches on the PCB malfunction code items can be displayed on the condensing unit 1 Make...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...4PW74302 1 2012 06 Copyright 2012 Daikin 4PW74302 1 00000003...

Reviews: