Installation manual

13

LREQ5~20B7Y1

Air cooled refrigeration condensing unit

4PW74302-1 – 2012.06

Remote switch wiring connections

• When installing a remote switch, clamp as indicated by the 

following diagram:

X3M wire specifications

Wiring connection for low-noise mode

• Wiring connection for low-noise mode: clamp as indicated by the 

following diagram:

X1M (A5P) wire specifications

CAUTION

• For Remote switch, use non-voltage contact for microcurrent (not 

more than 1 mA, 12 V DC)

• If the remote switch will be used to start and stop the unit, set the 

operating switch to “REMOTE”.

Precautions for terminal connections

• Be sure to use ring-type crimp-style terminals provided with 

insulation sleeves.

• Use specified electric wires for the wiring and secure the wiring so 

that external force will not be imposed on the terminal block.

• Use an appropriate screwdriver to tighten the terminal screws.

Small-sized screwdriver will damage the screw heads and cannot 
tighten the screws properly.

• Do not tighten the terminal screws in excess, otherwise the screws 

may be damaged.

• Refer to the following table for the tightening torque values of the 

terminal screws.

• Take out the earth wire from the notch of the cup washer and lay 

the wire carefully so that other wires will not be caught by the 
washer. Otherwise, the earth wire may not contact sufficiently and 
the earthing effect of the wire may be lost.

• Do not finish strand wire with solder.

7-4 Procedure for wiring inside units

• Referring to the following figure, secure and wire the power and 

transmission wiring using the accessory clamp (1), (2).

• Lay the ground wire so that it will not come in contact with the lead 

wires of the compressor. Other equipment will be adversely 
affected if the ground wire comes in contact with the lead wires of 
the compressor.

• Make sure all wiring do not contact to the pipes (hatching parts in 

the figure).

• The transmission wiring must be at least 50 mm away from the 

power wiring.

• After wiring work is completed, check to make sure there are no 

loose connections among the electrical parts in the control box.

Electric wire thickness

0.75~1.25 mm

2

Max. wiring length

130 m

Electric wire thickness

0.75~1.25 mm

2

Max. wiring length

130 m

X3M

2

1

Secure remote 
switch wiring to the 
resin block using a 
clamp (field supply).

Wiring for low-noise 
mode: wiring to the 
resin block using a 
clamp (field supply).

X1A

X1M

A5P

A B C

Crimp-style terminal

Insulating sleeve

Power wire

Screw size

Tightening torque (N•m)

M8 (Power supply terminal block)

5.5 - 7.3

M8 (Earth)
M4 (X2M)

2.39 - 2.91

M3.5 (X3M)

0.79 - 0.97

Crimp-style terminal

Cup washer

Cut out section 

LREQ5, LREQ6

1

9

10

4

A1P

X3M

X2M

6

14

7

2

12

A5P

5

8

X1M

13

3

11

LREQ8~20

8

11

12

13

15

16

9

6

X1M

X1M

X3M

A5P

A1P

X2M

14

3

1

2

10

5

4

7

13

14

Summary of Contents for LREQ5B7Y1

Page 1: ...INSTALLATION MANUAL LREQ5B7Y1 LREQ6B7Y1 LREQ8B7Y1 LREQ10B7Y1 LREQ12B7Y1 LREQ15B7Y1 LREQ20B7Y1 Air cooled refrigeration condensing unit...

Page 2: ...jennom positiv bed mmelse av B if lge Sertifikat C som det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jot...

Page 3: ...PS vastav k llastunud temperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksima...

Page 4: ...on manual Improper installation may result in water leakage electric shocks or fire When installing the unit in a small room take measures so that the refrigerant may not exceed the limiting concentra...

Page 5: ...ons be observed for keeping the system clean dry and tightly sealed Read the chapter 6 REFRIGERANT PIPING on page 5 carefully and follow these procedures correctly A Clean and dry Strict measures must...

Page 6: ...disturb anyone 3 The foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration and noise generation 4 The piping length between the outdoor unit and the...

Page 7: ...ary to take measures against leakage See Engineering Data for details 4 HANDLING THE UNIT 1 Decide on the transportation route 2 If a forklift is to be used pass the forklift arms through the large op...

Page 8: ...ng refrigerant piping heat exchangers Keep the following points in mind for the reuse of existing refrigerant piping heat exchangers A malfunction may result if there is deficiency Do not use the exis...

Page 9: ...oor unit H 10 m Note A trap is required at 5 m intervals from outdoor unit d1 e B d2 C c D1 F E f D2 A b a Outdoor unit Showcase Unit cooler Gas piping Liquid piping H Refrigerant piping size Unit mm...

Page 10: ...e operation manual of the dryer 6 5 Connecting the refrigerant piping CAUTION In addition to gas and liquid shutoff valves this unit has a maintenance shutoff valve see diagram below Do not operate th...

Page 11: ...dripped out in case the recovery was not complete and only then proceed with connection of the field piping 1 Service port 2 Stop valve 3 Point of pipe cutting just above brazing point or above markin...

Page 12: ...apply a screw lock agent to the screw thread Do not apply a screw lock agent for flare nut use to the sealing part Be sure to tighten the cap securely after the work Refer to Operation Method of Shuto...

Page 13: ...eriorate power factor improvement effect but also may cause capacitor abnormal heating accident due to high frequency waves Only proceed with wiring work after blocking off all power Always ground wir...

Page 14: ...eakage Be sure to connect the power wiring to the power wiring terminal block and secure it as described in 7 2 Procedure for incoming wiring on page 11 Do not connect the power supply to the terminal...

Page 15: ...EN IEC61000 3 11 1 provided that the system impedance Zsys is less than or equal to Zmax and EN IEC61000 3 12 2 provided that the short circuit power Ssc is greater than or equal to the minimum Ssc va...

Page 16: ...y the washer Otherwise the earth wire may not contact sufficiently and the earthing effect of the wire may be lost Do not finish strand wire with solder 7 4 Procedure for wiring inside units Referring...

Page 17: ...red to have passed if there is no decrease in the pressure over a period of 24 hours If there is a decrease in the pressure check for and repair leaks Vacuum drying Operate the vacuum pump for more th...

Page 18: ...of piping material on page 6 2 Make sure insulation work is done See 8 2 Thermal insulation work on page 14 3 Make sure there is no faulty refrigerant piping See 6 REFRIGERANT PIPING on page 5 9 CHEC...

Page 19: ...ling 1The cylinder s internal pressure will drop when there is little refrigerant remaining in the cylinder making it impossible to charge the unit even if the liquid shutoff valve opening is adjusted...

Page 20: ...lay The contents of a LED H2P display are as follows How to check malfunction code By operating the pushbutton switches on the PCB malfunction code items can be displayed on the condensing unit 1 Make...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...4PW74302 1 2012 06 Copyright 2012 Daikin 4PW74302 1 00000003...

Reviews: