LREQ5~20B7Y1

Air cooled refrigeration condensing unit

4PW74302-1 – 2012.06

Installation manual

12

7-3 Procedure for power supply wiring

Procedure for Power Supply Wiring

1

Power supply (3 phase 50 Hz 380~415)

2

Overcurrent circuit breaker (earth leakage circuit breaker) all pole 
disconnection switch

3

Earth wire

4

Power supply terminal block

5

Mount insulation sleeves

6

Fix the power supply wiring for phases L1, L2, L3, and N, 
respectively, with the provided clamp (1) to the resin clamp.

7

Fix the earth wire to the power supply wire (phase N) with the 
provided clamp (1).

8

Earth wire
Perform wiring so that the earth wire will not come in contact with 
lead wires of the compressor. Otherwise, noise generated may 
have a bad influence on other equipment.

9

Earth terminal

10

• When two wires are connected to a single terminal, connect 

them so that the rear sides of the crimp contacts face each 
other.

• Also, make sure the thinner wire is on top, securing the two wires 

simultaneously to the resin hook using the accessory clamp (1).

Power circuit, safety device, and cable requirements

• A power circuit (see the following table) must be provided for 

connection of the unit. This circuit must be protected with the 
required safety devices, i.e. a main switch, a slow blow fuse on 
each phase and an earth leakage circuit breaker.

• When using residual current operated circuit breakers, be sure to 

use a high-speed type (1 second or less) 200 mA rated residual 
operating current.

• Use copper conductors only.
• Use insulated wire for the power cord.
• Select the power supply cable type and size in accordance with 

relevant local and national regulations.

• Specifications for local wiring are in compliance with IEC60245.
• Use wire type H05VV when protected pipes are used.
• Use wire type H07RN-F when protected pipes are not used.

Point for attention regarding quality of the public electric power 
supply

This equipment complies with respectively:

EN/IEC61000-3-11

(1)

 provided that the system impedance Z

sys

 is 

less than or equal to Z

max

 and

EN/IEC61000-3-12

(2)

 provided that the short-circuit power S

sc

 is 

greater than or equal to the minimum S

sc

 value

at the interface point between the user’s supply and the public system. 
It is the responsibility of the installer or user of the equipment to 
ensure. by consultation with the distribution network operator if 
necessary, that the equipment is connected only to a supply with 
respectively:

Z

sys

 less than or equal to Z

max

 and

S

sc

 greater than or equal to the minimum S

sc

 value.

(1)

European/International Technical Standard setting the limits for 
voltage changes, voltage fluctuations and flicker in public 
low-voltage supply systems for equipment with rated current 

75 A

(2)

European/International Technical Standard setting the limits for 
harmonic currents produced by equipment connected to public 
low-voltage systems with input current >16 A and 

75 A per 

phase.

Warning, alarm, and operation output wiring connections

• Connect warning, alarm, and operation output wiring to the X2M 

terminal block and clamp as indicated by the following diagram:

X2M wire specifications

Note: Be sure to insulate the connecting equipment.

• Refer to the 

"7-1 Example of wiring entire system" on page 11

 by 

all means when connecting the operation output wiring.
A compressor failure may result if the operating output wiring is not 
connected.

N

L 1

L 2

L 3

B

1

2

3

4

5

6

7

9

10

8

Terminal block

Crip style terminal

Wire: narrow

Clamp (1)

Wire: thick

Resin hook

Phase and 

frequency

Voltage

Minimum 

circuit amp.

Recommended 

fuses

LREQ5

3~ 50Hz

380-415V

12.8A

15A

LREQ6

3~ 50Hz

380-415V

13.7A

15A

LREQ8

3~ 50Hz

380-415V

19.3A

25A

LREQ10

3~ 50Hz

380-415V

22.0A

25A

LREQ12

3~ 50Hz

380-415V

24.0A

25A

LREQ15

3~ 50Hz

380-415V

31.4A

40A

LREQ20

3~ 50Hz

380-415V

35.0A

40A

Z

max

 (

)

minimum  S

sc

 value

LREQ5

LREQ6

LREQ8

0.27

655 kVA

LREQ10

0.27

899 kVA

LREQ12

0.27

1097 kVA

LREQ15

0.24

761 kVA

LREQ20

0.24

945 kVA

Electric wire thickness

0.75~1.25 mm

2

Max. wiring length

130 m

C 1

W 1

C

P 2

P 1

Mount insulation sleeves

Fix the wiring with the
provided clamp (1)

X 2 M

Summary of Contents for LREQ5B7Y1

Page 1: ...INSTALLATION MANUAL LREQ5B7Y1 LREQ6B7Y1 LREQ8B7Y1 LREQ10B7Y1 LREQ12B7Y1 LREQ15B7Y1 LREQ20B7Y1 Air cooled refrigeration condensing unit...

Page 2: ...jennom positiv bed mmelse av B if lge Sertifikat C som det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jot...

Page 3: ...PS vastav k llastunud temperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksima...

Page 4: ...on manual Improper installation may result in water leakage electric shocks or fire When installing the unit in a small room take measures so that the refrigerant may not exceed the limiting concentra...

Page 5: ...ons be observed for keeping the system clean dry and tightly sealed Read the chapter 6 REFRIGERANT PIPING on page 5 carefully and follow these procedures correctly A Clean and dry Strict measures must...

Page 6: ...disturb anyone 3 The foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration and noise generation 4 The piping length between the outdoor unit and the...

Page 7: ...ary to take measures against leakage See Engineering Data for details 4 HANDLING THE UNIT 1 Decide on the transportation route 2 If a forklift is to be used pass the forklift arms through the large op...

Page 8: ...ng refrigerant piping heat exchangers Keep the following points in mind for the reuse of existing refrigerant piping heat exchangers A malfunction may result if there is deficiency Do not use the exis...

Page 9: ...oor unit H 10 m Note A trap is required at 5 m intervals from outdoor unit d1 e B d2 C c D1 F E f D2 A b a Outdoor unit Showcase Unit cooler Gas piping Liquid piping H Refrigerant piping size Unit mm...

Page 10: ...e operation manual of the dryer 6 5 Connecting the refrigerant piping CAUTION In addition to gas and liquid shutoff valves this unit has a maintenance shutoff valve see diagram below Do not operate th...

Page 11: ...dripped out in case the recovery was not complete and only then proceed with connection of the field piping 1 Service port 2 Stop valve 3 Point of pipe cutting just above brazing point or above markin...

Page 12: ...apply a screw lock agent to the screw thread Do not apply a screw lock agent for flare nut use to the sealing part Be sure to tighten the cap securely after the work Refer to Operation Method of Shuto...

Page 13: ...eriorate power factor improvement effect but also may cause capacitor abnormal heating accident due to high frequency waves Only proceed with wiring work after blocking off all power Always ground wir...

Page 14: ...eakage Be sure to connect the power wiring to the power wiring terminal block and secure it as described in 7 2 Procedure for incoming wiring on page 11 Do not connect the power supply to the terminal...

Page 15: ...EN IEC61000 3 11 1 provided that the system impedance Zsys is less than or equal to Zmax and EN IEC61000 3 12 2 provided that the short circuit power Ssc is greater than or equal to the minimum Ssc va...

Page 16: ...y the washer Otherwise the earth wire may not contact sufficiently and the earthing effect of the wire may be lost Do not finish strand wire with solder 7 4 Procedure for wiring inside units Referring...

Page 17: ...red to have passed if there is no decrease in the pressure over a period of 24 hours If there is a decrease in the pressure check for and repair leaks Vacuum drying Operate the vacuum pump for more th...

Page 18: ...of piping material on page 6 2 Make sure insulation work is done See 8 2 Thermal insulation work on page 14 3 Make sure there is no faulty refrigerant piping See 6 REFRIGERANT PIPING on page 5 9 CHEC...

Page 19: ...ling 1The cylinder s internal pressure will drop when there is little refrigerant remaining in the cylinder making it impossible to charge the unit even if the liquid shutoff valve opening is adjusted...

Page 20: ...lay The contents of a LED H2P display are as follows How to check malfunction code By operating the pushbutton switches on the PCB malfunction code items can be displayed on the condensing unit 1 Make...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...4PW74302 1 2012 06 Copyright 2012 Daikin 4PW74302 1 00000003...

Reviews: