65
ENG
pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
Mask index
Display description
Description
Def
.
U
.
of M
.
V
alues
Dbd01
Enable condensing setpoint
compensation
Enable setpoint compensation (condensing line 2)
NO
---
NO | YES
…
…
…
…
…
…
Dbe01
Cond.pressure
high alarm
Condensing high pressure/temperature alarm threshold type (line 2)
absolute
---
absolute
relative
Delay
Condensing high pressure/temperature alarm delay (line 2)
60
s
0…999
…
…
…
…
…
…
Dbf01
Number of fans
Number of fans (line 2)
3
---
0…16
…
…
…
…
…
…
Dbg01
Modulate speed device
Modulating condenser device type (line 2)
None
---
None
Inverter
Phase cut-off control
…
…
…
…
…
…
Tab. 7.e
Mask index
Display description
Description
Def
.
U
.
of M
.
V
alues
E.Other functions
The I/Os depend on the confi guration selected, the following are only examples. See Appendix A.1 for the complete list and position of available I/Os.
Eaaa04
---
Oil temperature probe position (line 1)
B1
---
--- | U1…U10 (****)
---
Oil temperature probe type (line 1)
4...20 mA
---
--- | NTC | PT1000
| 0...1 V | 0...10 V |
4...20 mA | 0...5 V |
HT NTC
--- (display only)
Oil temperature value (line 1)
---
…
…(**)
Max limit
Maximum oil temperature value (line 1)
30.0 barg
…
…(**)
Min limit
Minimum oil temperature value (line 1)
0.0 barg
…
…(**)
Calibration
Oil temperature probe calibration (line 1)
0.0 barg
…
…(**)
…
…
…
…
…
…
Eaaa45
DO
Oil level valve compressor 6 DO position (line 1)
03
---
---, 01…18 (****)
Status (display only)
Oil level valve compressor 6 DO status (line 1)
---
---
closed | open
Logic
Oil level valve compressor 6 DO logic (line 1)
NC
---
NC | NO
Function (display only)
Oil level valve compressor 6 function status (line 1)
---
---
not active | active
Eaab04
Enable com.cool.
Enable common oil cooling (line 1)
YES
---
NO | YES
Number of oil pumps
Number of oil pumps for common oil cooler (ine 1)
0
---
0…1 (analog. output)
0…2 (digital output)
Enable pump out.
Enable AO of common oil cooler pump (line 1)
YES
---
NO (digital output)
YES (analog. output)
Eaab15
Enable cool.
Enable oil cooling compressors (line 1)
NO
---
NO | YES
Oil cool. off with comp. off
Oil cooling functioning only when compressor functioning
NO
---
NO | YES
Eaab05
Setpoint
Common oil cooling setpoint (line 1)
0.0 °C
…
…(**)
Diff erential
Common oil cooling diff erential (line 1)
0.0 °C
…
-9,9…9,9
Eaab06
Pump start delay
Pump 2 start delay after pump 1 startup (line 1)
0
s
0…999
Eaab07
Oil pump confi g
Oil pump output confi guration: none, analog, digital
non conf.
---
not confi gurable
analogic
digital
Eaab08
Setpoint
Oil temperature setpoint (line 1)
0.0
°C/°F
…
Diff erential
Oil temperature diff erential (line 1)
0.0
°C/°F
…
Duty on time
Fan startup time in case of oil probe error (line 1)
0
s
0…9999
Duty off time
Fan shutdown time in case of oil probe error (line 1)
0
s
0…9999
Eaab09
Threshold
Common oil high temperature alarm threshold (line 1)
100.0 °C
°C/°F
…
Diff erential
Common oil high temperature alarm diff erential (line 1)
10.0 °C
°C/°F
…
Delay
Common oil high temperature alarm delay (line 1)
0
s
0…32767
Eaab10
Enable oil lev.
Enable oil level management (line 1)
NO
---
NO | YES
Num. oil level alarms
Number of compressor alarms associated with the oil level (line 1)
0
---
0…4 | 7 (*)
Eaab11
Open time
Oil level valve opening time (line 1)
0
s
0…999
Closing time
Oil level valve closing time (line 1)
0
s
0…999
Puls. start delay
Delay for oil level valve pulsation at startup (line 1)
0
s
0…999
Max. puls. time
Maximum pulsing time of the oil level valve (line 1)
0
s
0…999
Eaab12
Oil level controlled by
Type of oil level separator control: with minimum level only, with minimum and maximum
level and with compressor status (line 1)
livello min. ---
liv.min. | liv.min.&max
comp. status
Min.off valve
Minimum separator valve closing time (line 1)
0
s
0…999
Min.lev. delay
Minimum oil level detection delay (line 1)
0
s
0…999
Eaab13
Ton Activ.
Valve opening time during oil level reset (line 1)
10
s
0…999
Toff Activ.
Valve closing time during oil level reset (line 1)
0
s
0…999
Ton Deact.
Valve opening time with correct oil level (line 1)
0
s
0…999
Toff Deact.
Valve closing time with correct oil level (line 1)
10
min
0…999
Eaab14
Threshold
Oil separator diff erential pressure threshold (line 1)
1.0 barg
…
…(**)
Diff erential
Oil separator diff erential pressure (line 1)
0,5 barg
…
…(**)
Delay
Oil separator diff erential pressure delay (line 1)
0
s
0…99
Eaab16
Threshold
Oil cooler high temperature alarm threshold (line 1)
100.0 °C
°C/°F
…
Diff erential
Oil cooler high temperature alarm diff erential (line 1)
10.0 °C
°C/°F
…
Delay
Oil cooler high temperature alarm delay (line 1)
0
s
0 to 9999
Eaab20
Threshold
Oil cooler low temperature alarm threshold (line 1)
100.0 °C
°C/°F
…
Diff erential
Oil cooler low temperature alarm diff erential (line 1)
10.0 °C
°C/°F
…
Delay
Oil cooler low temperature alarm delay (line 1)
0
s
0 to 9999
Ebaa01
DO
Subcooling DO valve position (line 1)
…
---
---, 01…18 (****)
Status (display only)
Subcooling DO valve status (line 1)
---
---
closed | open
Logic
Subcooling DO valve logic (line 1)
NO
---
NC | NO
Function (display only)
Status of the subcooling valve function (line 1)
---
---
not active | active
Ebab01
Subcooling contr.
Enable subcooling function (line 1)
NO
---
NO | YES
---
Subcooling control type (line 1)
temp.
Cond&Liqu.
---
Temp. Cond&Liquid
Only Liquid Temp
Threshold
Threshold for subcooling activation (line 1)
0.0 °C
…
-9999,9…9999,9
Subcooling (display only)
Subcooling value (line 1)
0.0 °C
…
-999,9…999,9
Eeaab25
Enable Oil Pres.diff
management
Enable common diff erential oil management
NO
---
YES | NO
Manage oil press. with
dedicated settings
With dedicated parallel compression board, select whether to use the same settings as the
main board
NO
---
YES | NO
Manage oil press. with
dedicated I/O
With dedicated parallel compression board, select whether to use the same inputs and
outputs as the main board
NO
---
YES | NO
Page 114 of 172
Copyright HPL March 2021
P4114S Rev 03
Summary of Contents for Hubbard GCU2040PXB1
Page 4: ...Page 4 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 49: ...6 Carel PR300T CO2 Controller manual Page 49 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 144: ...Page 144 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 165: ...9 Commissioning Form Page 165 of 172 Copyright HPL March 2021 P4114S Rev 03...