Dbb01
L2
Fans control mode
1 TEMPERATURE
Dbb02
L2
Minimum Intercooler setpoint
5
Dbb02
L2
Maximum Intercooler setpoint
25
Dbb03
L2
Intercooler setpoint
25
Dbb04
L2
Fan can work only when at least one compressor work
0 NO
Dbb06
L2
ond. - Regulation type (P - P+I - PID)
0 PROPORTIONAL
Dbb06
L2
ond. - Integral time
0 s
Dbb14
L2
Intercooler neutral zone minimum complete activation time (neutral zone)
15 s
Dbb14
L2
Intercooler neutral zone maximum complete activation time (neutral zone)
90 s
Dbb15
L2
Intercooler neutral zone minimum complete deactivation time (neutral zone)
30 s
Dbb15
L2
Intercooler neutral zone maximum complete deactivation time (neutral zone)
180 s
Dbf01
L2
Number of fans
3 --
Dbf04
L2
condensing refrigerant type
10 --
Dbf05
L2
Fans rotation type
1 FIFO
Dbg01
L2
Fans modulating device type
0 NONE
Dbg02
L2
Fan inverter minimum voltage
0 V
Dbg02
L2
Fan inverter maxiimum voltage
100 V
Dbg02
L2
Fan inverter minimum activation
5 kW
Dbg02
L2
Fan inverter maxiimum activation
100 kW
Dbg13
L2
Speed-up procedure duration
0 s
Dbb05
L2
Setup for fans regulation cutoff
20
************
--
--
--
L2 - ALARMS
--
--
--
************
--
--
--
Cbe11
L2
Compressors alarm 1 delay
0 s
Cbe11
L2
Alarm1 of compressor start delay
0 s
Cbe11
L2
Compressor alarm 1 type(0.Auto 1.Manual)
0 AUT.
Cbe11
L2
Compressor alarm 1 priority (0=Light - 1=Serious)
1 SERIOUS
Cbe14
L2
Compressors alarm 2 delay
0 s
Cbe14
L2
Alarm 2 of compressor start delay
0 s
Cbe14
L2
Compressor alarm 2 type(0.Auto 1.Manual)
0 AUT.
Cbe14
L2
Compressor alarm 2 priority (0=Light - 1=Serious)
1 SERIOUS
Cbe22
L2
Compressors alarm 3 delay
0 s
Cbe22
L2
Alarm 3 of compressor start delay
0 s
Cbe22
L2
Compressor alarm 3 type(0.Auto 1.Manual)
0 AUT.
Cbe22
L2
Compressor alarm 3 priority (0=Light - 1=Serious)
1 SERIOUS
Cbe25
L2
Compressors alarm 4 delay
0 s
Cbe25
L2
Alarm 4 of compressor start delay
0 s
Cbe25
L2
Compressor alarm 4 type(0.Auto 1.Manual)
0 AUT.
Cbe25
L2
Compressor alarm 4 priority (0=Light - 1=Serious)
1 SERIOUS
Cbe28
L2
Compressors alarm 5 delay
0 s
Cbe28
L2
Alarm 5 of compressor start delay
0 s
Cbe28
L2
Compressor alarm 5 type(0.Auto 1.Manual)
0 AUT.
Cbe28
L2
Compressor alarm 5 priority (0=Light - 1=Serious)
1 SERIOUS
Cbe31
L2
Compressors alarm 6 delay
0 s
Cbe31
L2
Alarm 6 of compressor start delay
0 s
Cbe31
L2
Compressor alarm 6 type(0.Auto 1.Manual)
0 AUT.
Cbe31
L2
Compressor alarm 6 priority (0=Light - 1=Serious)
1 SERIOUS
Cbe34
L2
Compressors alarm 7 delay
0 s
Cbe34
L2
Alarm 7 of compressor start delay
0 s
Cbe34
L2
Compressor alarm 7 type(0.Auto 1.Manual)
0 AUT.
Cbe34
L2
Compressor alarm 7 priority (0=Light - 1=Serious)
1 SERIOUS
Cbe01
L2
Relative suction setpoint high alarm
0 ABSOLUTE
Cbe01
L2
High suction pressure alarm threshold
35
Cbe02
L2
High suction pressure alarm differential
1
Cbe02
L2
High suction pressure alarm delay
120 s
Cbe03
L2
Relative suction setpoint low alarm
0 ABSOLUTE
Cbe03
L2
Low suction pressure alarm threshold
5
Cbe04
L2
Low suction pressure alarm differential
1
Cbe04
L2
Low suction pressure alarm delay
30 s
Cbe07
L2
Super Heat configuration
2 ONLY ALARM
Cbe07
L2
Low superheat alarm threshold
3
Cbe07
L2
Low superheat alarm differential
1
Cbe07
--
--
--
Cbe07
L2
Superheat Alarm manual or automatic reset
0 MANUAL
Cbe07
L2
Low superheat alarm delay
30 s
Cbe35
L2
Discharge threshold setpoint
85
Cbe35
L2
Discharge threshold differential
5
Cbe35
L2
Enable the switch off of the compressor when its high discharge temperature alarm occurs
0 NO
Cbe36
L2
Relative discharge setpoint high alarm
0 °C
Cbe36
L2
High discharge pressure alarm threshold
35
Cbe37
L2
High discharge pressure alarm differential
5
Cbe37
L2
High discharge pressure alarm delay
0 s
Gcb01
L2
Common HP alarm type
0 AUT.
Gcb01
L2
High common condensing pressure delay
1 s
Gcb02
L2
Low common condensing pressure start delay
60 s
Gcb02
L2
Low common condensing pressure delay
20 s
Gcb03
L2
Time for lock compressor during low pressure
120 min
Gcb03
L2
Number of tries before become manual
5 --
Gba01
L2
Enable high condensing pressure prevent
0 NO
Gba01
--
--
--
Gba02
--
--
°C
Gba02
--
--
°C
Gba02
--
--
s
Gba06
--
--
°C
Gba06
--
--
°C
Gba06
--
--
s
************
--
--
--
EVS
--
--
--
************
--
--
--
Eia02
--
--
K
Eia02
--
--
K
Eia02
--
--
°C
Eia02
--
--
°C
Eia04
--
--
K
Eia04
--
--
K
Eia04
--
--
°C
Eia04
--
--
°C
Page 148 of 172
Copyright HPL March 2021
P4114S Rev 03
Summary of Contents for Hubbard GCU2040PXB1
Page 4: ...Page 4 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 49: ...6 Carel PR300T CO2 Controller manual Page 49 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 144: ...Page 144 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 165: ...9 Commissioning Form Page 165 of 172 Copyright HPL March 2021 P4114S Rev 03...