63
ENG
pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
Mask index
Display description
Description
Def
.
U
.
of M
.
V
alues
Daa18
---
Gas cooler backup probe position (line 1)
B1
---
---, U1…U10 (****)
---
Gas cooler backup probe type (line 1)
4...20 mA
---
----
0-1 V
0-10 V
4...20 mA
0-5 V
--- (display only)
Gas cooler backup pressure value
---
…
…(**)
Max limit
Gas cooler backup maximum pressure value (line 1)
30.0 barg
…
…(**)
Min limit
Gas cooler backup pressure minimum value (line 1)
0.0 barg
…
…(**)
Calibration
Gas cooler backup pressure probe calibration (line 1)
0.0 barg
…
…(**)
…
…
…
…
…
…
Daa21
DO
Fan 1 DO position (line 1)
03
---
--- | 01…18 (****)
Status (display only)
Status of fan 1 DO (line 1)
---
---
closed | open
Logic
Logic of fan 1 DO (line 1)
NC
---
NC | NO
Function (display only)
Fan 1 function status (line 1)
---
---
not active | active
…
…
…
…
…
…
Daa38
AO
Inverter fan AO position (line 1)
0
---
---, 01…06 (****)
Status (display only)
Inverter fan output value (line 1)
0
%
0.0…100.0
…
…
…
…
…
…
Dab01
Regulation
Condenser regulation by temperature or pressure (line 1)
Note: with HPV valve management, only temperature regulation is enabled
temperat.
---
pressure
temperature
Regulation type
Condenser regulation Type (line 1)
proport.
band
---
Proportion. band
dead zone
Dab02
Minimum
Condenser setpoint lower limit (line 1)
…(**)
…
…(**)
Maximum
Condenser setpoint upper limit (line 1)
…(**)
…
…(**)
Dab03
Setpoint
Condenser setpoint (line 1)
…(**)
…
…(**)
Dab04
Fans work if at least one
compressor works
Enable fan operation linked to compressor operation
NO
---
NO | YES
Dab05
Cut-off enable
Enable fan cut-off
NO
---
NO | YES
Cut-off request
Cut-off value
0.0
%
0.0…100.0
Setpoint
Setpoint cut-off …(**)
…
…(**)
Diff .
Diff erential cut-off …(**)
…
…(**)
Hysteresis
Hysteresis cut-off …(**)
…
…(**)
Dab6/ Dab8 (**)
Reg. Type
Proportional regulation type (condensing line 1)
proportion. ---
proportional
pinteger
Integral time
Integral time for proportional regulation (cond. line 1)
300
s
0…999
Dab7/ Dab9 (**)
Diff erential
Diff erential for proportional regulation (cond. line 1)
…(**)
…
…(**)
Dab10/Dab11(**) DZ diff .
Dead zone regulation diff erential (line 1)
…(**)
…
…(**)
Activ.diff .
Dead zone regulation diff erential for device activation (line 1)
…(**)
…
…(**)
Deact.diff .
Dead zone regulation diff erential for device deactivation (line 1)
…(**)
…
…(**)
Dab12/Dab13
(**)
En.force off
Enable capacity immediate decreasing to 0 (line 1)
NO
---
NO | YES
Setp. force off
Threshold for capacity decreasing to 0 (line 1)
…(**)
…
…(**)
Dab14
Power to 100%
min time
Minimum time to increase capacity request to 100%, dead zone regulation
(condensing line 1)
15
s
0…9999
Power to 100%
max time
Maximum time to increase capacity request to 100%, dead zone regulation
(condensing line 1)
90
s
0…9999
Dab15
Power reduction to 0%
min time
Minimum time to decrease capacity request to 0%, dead zone regulation
(condensing line 1)
30
s
0…9999
Power reduction to 0%
max time
Maximum time to decrease capacity request to 0%, dead zone regulation
(condensing line 1)
180
s
0…9999
Dac
--
Not available
---
---
---
Dad01
Enable condensing
setpoint compensation
Enable setpoint compensation (condensing line 1)
NO
---
NO | YES
Dad02
Winter off set
Off set applied for the Winter period
0.0
…
-999,9…999,9
Closing off set
Off set applied for closing period
0.0
…
-999,9…999,9
Dad03
Enable setpoint
compensation by scheduler
Enable scheduler setpoint compensation
(condensing line 1)
NO
---
NO | YES
Dad04
TB1: --:-- -> --:--
Enabling and defi nition of time band 1: start hour and minute, end hour and minute
(condensing line 1)
---
…
…
…
…
…
…
…
TB4: --:-- -> --:--
Enabling and defi nition of time band 4: start hour and minute, end hour and minute
(condensing line 1)
---
…
…
Change
Time band change action
---
---
--- | Save changes
Load previous |
Clear all
Copy to
Copy settings to other days
---
---
MONDAY...SUNDAY;
MON-FRI;
MON-SAT;
SAT&SUN; ALL
Dad05
Enable fl oating gas cooler
setpoint
Enable fl oating gas cooler setpoint (condensing line 1)
NO
---
NO | YES
Dad06
Off set for external temp.
Setpoint variation for fl oating gas cooler setpoint (condensing line 1)
0.0
…
-9,9…9,9
Controlled by:
-Dig. input
Enable fl oating gas cooler setpoint by digital input
NO
---
NO | YES
Dad07
Change setpoint by digital
input
Enable setpoint compensation by digital input (suct/cond line 1)
NO
---
NO | YES
Dae01
Gas cooler high pressure
alarm
Type of gas cooler high pressure alarm threshold (line 1)
absolute
---
absolute | relative
Delay
Gas cooler high pressure alarm delay (line 1)
60
s
0…999
Dae02/Dae06
Gas cooler high pressure
alarm
Gas cooler high pressure alarm threshold (line 1)
24.0 barg
…
…(**)
Diff eren.
Gas cooler high pressure alarm diff erential (line 1)
1.0 barg
…
…(**)
Dae03
Gas cooler low pressure
alarm
Type of gas cooler low pressure alarm threshold (line 1)
absolute
---
absolute | relative
Delay
Gas cooler low pressure alarm delay (line 1)
30
s
0…999
Dae04/Dae07
Gas cooler low pressure
alarm
Gas cooler low pressure alarm threshold (line 1)
7.0 barg
…
…(**)
Diff eren.
Gas cooler low pressure alarm diff erential (line 1)
1.0 barg
…
…(**)
Dae05
Common fan overload
Enable common fan overload (line 1)
YES'
---
NO | YES
Delay
Common fan alarm delay
0
s
0…500
Reset
Common fan alarm reset type
automatic
---
automatic
manual
Daf01
Number of fans
Number of fans (line 1)
3
---
0…16
Daf02
Fan1, Fan2, ...
Enable fan 1...12 (line 1)
AB
---
Disabled | abled
Daf03
Fan13, Fan14, ...
Enable fan 13...16 (line 1)
AB
---
Disabled | abled
Page 112 of 172
Copyright HPL March 2021
P4114S Rev 03
Summary of Contents for Hubbard GCU2040PXB1
Page 4: ...Page 4 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 49: ...6 Carel PR300T CO2 Controller manual Page 49 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 144: ...Page 144 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 165: ...9 Commissioning Form Page 165 of 172 Copyright HPL March 2021 P4114S Rev 03...