pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
7.2 Alarm
table
pRack pR300T can manage both alarms relating to the status of the digital inputs and to system operation, similar to the pRack pR300. For each alarm, the
following are controlled:
•
The actions on the devices, if necessary
•
The output relays (one global and two with diff erent priorities, if confi gured)
•
The red LED on the terminal and the buzzer, where present
•
The type of acknowledgement (automatic, manual, semiautomatic)
•
Any activation delay
The complete list of alarms for the pRack pR300T with the related information as described above, is reported below.
C
ode
Description
R
eset
Delay
Alarm relay
Action
ALA**
C.pCOe offl
ine n° 001 Offl
ine
Automatic
0s
R1
Outputs held in current status or according
to pattern
ALA01
Discharge temperature probe malfunction
Automatic
60 s
R2
Related functions disabled
ALA02
Discharge temperature probe malfunction
Automatic
60 s
R1
Related functions disabled
ALA03
External temperature probe malfunction
Automatic
60 s
R2
Related functions disabled
ALA04
Generic probe malfunction A, PLB1
Automatic
60 s
R2
Related functions disabled
ALA05
Generic probe malfunction B, PLB1
Automatic
60 s
R2
Related functions disabled
ALA06
Generic probe malfunction C, PLB1
Automatic
60 s
R2
Related functions disabled
ALA07
Generic probe malfunction D, PLB1
Automatic
60 s
R2
Related functions disabled
ALA08
Generic probe malfunction E, PLB1
Automatic
60 s
R2
Related functions disabled
ALA09
Generic probe malfunction A, PLB2
Automatic
60 s
R2
Related functions disabled
ALA10
Generic probe malfunction B, PLB2
Automatic
60 s
R2
Related functions disabled
ALA11
Generic probe malfunction C, PLB2
Automatic
60 s
R2
Related functions disabled
ALA12
Generic probe malfunction D, PLB2
Automatic
60 s
R2
Related functions disabled
ALA13
Generic probe malfunction E, PLB2
Automatic
60 s
R2
Related functions disabled
ALA14
Generic probe malfunction A, PLB3
Automatic
60 s
R2
Related functions disabled
ALA15
Generic probe malfunction B, PLB3
Automatic
60 s
R2
Related functions disabled
ALA16
Generic probe malfunction C, PLB3
Automatic
60 s
R2
Related functions disabled
ALA17
Generic probe malfunction D, PLB3
Automatic
60 s
R2
Related functions disabled
ALA18
Generic probe malfunction E, PLB3
Automatic
60 s
R2
Related functions disabled
ALA19
Generic probe malfunction A, PLB4
Automatic
60 s
R2
Related functions disabled
ALA20
Generic probe malfunction B, PLB4
Automatic
60 s
R2
Related functions disabled
ALA21
Generic probe malfunction C, PLB4
Automatic
60 s
R2
Related functions disabled
ALA22
Generic probe malfunction D, PLB4
Automatic
60 s
R2
Related functions disabled
ALA23
Generic probe malfunction E, PLB4
Automatic
60 s
R2
Related functions disabled
ALA24
Suction pressure probe malfunction
Automatic
60 s
R1
Related functions disabled
ALA25
Suction temperature probe malfunction
Automatic
60 s
R2
Related functions disabled
ALA26
Room temperature probe malfunction
Automatic
60 s
R2
Related functions disabled
ALA27
Condensing pressure probe malfunction, line 2
Automatic
60 s
R1
Related functions disabled
ALA28
Discharge temperature probe malfunction, line 2
Automatic
60 s
R2
Related functions disabled
ALA29
Suction pressure probe malfunction, line 2
Automatic
60 s
R1
Related functions disabled
ALA30
Suction temperature probe malfunction, line 2
Automatic
60 s
R2
Related functions disabled
ALA31
Gall cooler backup pressure probe malfunction
Automatic
60 s
R2
Related functions disabled
ALA32
Condensing pressure backup probe malfunction, line 2
Automatic
60 s
R2
Related functions disabled
ALA33
Suction pressure backup probe malfunction
Automatic
60 s
R2
Related functions disabled
ALA34
Suction pressure backup probe malfunction, line 2
Automatic
60 s
R2
Related functions disabled
ALA35
Common oil temperature probe malfunction
Automatic
60 s
R2
Related functions disabled
ALA36
Common oil temperature probe malfunction, line 2
Automatic
60 s
R2
Related functions disabled
ALA39
Discharge temperature probe malfunction, compressors 1...6
Automatic
60 s
R2
Related functions disabled
ALA40
Discharge temperature probe malfunction, compressors 1...6, line 2
Automatic
60 s
R2
Related functions disabled
ALA41
Oil temperature probe malfunction, compressors 1...6, line 1
Automatic
60 s
R2
Related functions disabled
ALA42
Oil temperature probe malfunction, compressor 1, line 2
Automatic
60 s
R2
Related functions disabled
ALA43
Gas cooler output temperature probe malfunction
Automatic
60 s
R2
Related functions disabled
ALA44
CO2 receiver pressure probe malfunction
Automatic
60 s
R2
Related functions disabled
ALA45
Gas cooler output backup temperature probe malfunction
Automatic
60 s
R2
Related functions disabled
ALA55
Discharge probe malfunction, line 1
Automatic
60 s
R2
Related functions disabled
ALA56
Discharge probe malfunction, line 2
Automatic
60 s
R2
Related functions disabled
ALA57
High/low discharge pressure, line 1
Automatic
Settable
R1
-
ALA58
High/low discharge pressure, line 2
Automatic
Settable
R1
-
ALB01
Low suction pressure from pressure switch
Semiautomatic
Confi g.
R1
Shutdown compressors
ALB02
High condensing pressure from pressure switch
Man./Autom.
Confi g.
R1
Shutdown compressors
ALB03
Low gas cooler output temperature from probe
Automatic
Settable
R1
Fan forcing at 0%
ALB04
High gas cooler output temperature from probe
Automatic
Settable
R1
Fan forcing at 100% and shutdown
compres.
ALB05
Liquid level
Automatic
Confi g.
R2
-
ALB06
Common oil diff erential
Automatic
Confi g.
R2
-
ALB07
Common fan circuit breaker
Automatic
Confi g.
Confi g.
-
ALB08
Low suction pressure from pressure switch. line 2
Semiautomatic
Confi g.
R1
Shutdown compressors, line 2
ALB09
High condensing pressure from pressure switch. line 2
Man./Autom.
Confi g.
R1
Shutdown compressors, line 2
ALB10
Low condensing pressure from probe, line 2
Automatic
Confi g.
R1
-
ALB11
High condensing pressure from probe, line 2
Automatic
Confi g.
R1
-
ALB12
Liquid level, line 2
Automatic
Confi g.
R2
-
ALB13
Common oil diff erential, line 2
Automatic
Confi g.
R2
-
ALB14
Common fan circuit breaker, line 2
Automatic
Confi g.
Confi g.
-
ALB15
High suction pressure from probe
Automatic
Confi g.
R1
-
ALB16
Low suction pressure from probe
Automatic
Confi g.
R1
-
ALB17
High suction pressure from probe, line 2
Automatic
Confi g.
R1
-
ALB18
Low suction pressure from probe, line 2
Automatic
Confi g.
R1
-
ALB21
Shutdown to prevent high pressure
Manual
Confi g.
R1
Shutdown compressors
ALB22
Shutdown to prevent high pressure, line 2
Manual
Confi g.
R1
Shutdown compressors, line 2
ALC90
L1 – Generic alarm comp.
Man./Auto
confi g
confi g
Shutdown compressor with alarm
ALC91
L1 – Compressors overload alarm
Man./Auto
confi g
confi g
Shutdown compressor with alarm
ALC92
L1 – Compressors high pressure
Man./Auto
confi g
confi g
Shutdown compressor with alarm
ALC93
L1 – Compressors low pressure
Man./Auto
confi g
confi g
Shutdown compressor with alarm
ALC94
L1 – Compressors oil alarm
Man./Auto
confi g
confi g
Shutdown compressor with alarm
ALC96
L2 – Compressors generic alarm
Man./Auto
confi g
confi g
Shutdown compressor with alarm
ALC97
L2 – Compressors overload alarm
Man./Auto
confi g
confi g
Shutdown compressor with alarm
ALC98
L2 – Compressors high pressure
Man./Auto
confi g
confi g
Shutdown compressor with alarm
ALC99
L2 – Compressors low pressure
Man./Auto
confi g
confi g
Shutdown compressor with alarm
ALC9a
L2 – Compressors oil alarm
Man./Auto
confi g
confi g
Shutdown compressor with alarm
Page 124 of 172
Copyright HPL March 2021
P4114S Rev 03
Summary of Contents for Hubbard GCU2040PXB1
Page 4: ...Page 4 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 49: ...6 Carel PR300T CO2 Controller manual Page 49 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 144: ...Page 144 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 165: ...9 Commissioning Form Page 165 of 172 Copyright HPL March 2021 P4114S Rev 03...