If the evaporator volume is not known, the following estimation can be used:
For GCU2040PXB1 unit: 2.9 kg refrigerant at evaporator (estimation based on full capacity load of the condensing
unit.
The following table is presententing the amount of refrigerant charge estimated for:
•
Different pipe lengths
•
Receiver up to 1
st
sight glass full
•
Evaporator to match the capacity of unit
Recommended values – Those may change from installation to installation.
The amount of oil in the system is a proportional of refrigerant charge:
Oil / Refrigerant
≥
35 (wt %)
Example of oil charge:
-
If the system is charged with 10 kg of CO2, then the recommended amount of oil is 3.5 kg.
The correct amount of oil into the system ensures the compressor reliability and increase the lifetime
of the system.
The GCU2040PXB1 unit is delivered with 1.15 kg of oil. The additional oil required for varies pipe length
is shown in table above. The additional oil can be added in the system from the valve showing below.
Pipe length (to
evaporator m)
5
8
11
14
17
20
23
26
29
32
35
Refrigerant amount
in all pipework (kg)
0.60
0.81
1.01 1.21
1.41
1.61 1.81 2.01 2.21 2.41 2.61
Refrigearnt amount
in evaporator (kg)
2.90
Refrigerant left in
receiver (kg)
3.48
Total (kg)
6.98
7.19
7.39 7.59
7.79
7.99 8.19 8.39 8.59 8.79 8.99
Oil charge (kg)
2.44
2.52
2.59 2.66
2.73
2.80 2.87 2.94 3.01 3.08 3.15
Initial charge (kg)
1.15
1.15
1.15 1.15
1.15
1.15 1.15 1.15 1.15 1.15 1.15
Oil charge (kg)
1.29
1.37
1.44 1.51
1.58
1.65 1.72 1.79 1.86 1.93 2.00
Page 24 of 172
Copyright HPL March 2021
P4114S Rev 03
Summary of Contents for Hubbard GCU2040PXB1
Page 4: ...Page 4 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 49: ...6 Carel PR300T CO2 Controller manual Page 49 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 144: ...Page 144 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 165: ...9 Commissioning Form Page 165 of 172 Copyright HPL March 2021 P4114S Rev 03...