11
ENG
pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
2.2.6 Analogue
outputs
Y...
Type
0 to 10 V optically-isolated on Y1...Y6
Lmax
30 m
Maximum number
SMALL, MEDIUM/ BUILT-IN DRIVER
4
Y1...Y4, 0 to 10 V
LARGE
6
Y1...Y6, 0 to 10 V
Power supply
external
24 Vac (+10/-15%) or 28 to 36 Vdc on VG(+), VG0(-)
Precision
Y1...Y6
± 2% full scale
Resolution
8 bit
Settling time
Y1...Y6
from 1 s (slew rate 10 V/s) to 20 s (slew rate 0.5 V/s) selectable via SW
Maximum load
1 kΩ (10 mA)
Tab. 2.i
Warnings:
•
for lengths > 10 m, only use shielded cable, with the shield connected to earth;
•
a 0 to 10 Vdc analogue output can be connected in parallel to other outputs of the same type, or alternatively to an external source of voltage. The higher
voltage will be considered. Correct operation is not guaranteed if actuators with voltage inputs are connected;
•
power the VG-VG0 analogue outputs at the same voltage on G-G0: Connect G0 to VG0 and G to VG. This is valid for both alternating and direct current
power supplies.
2.2.7
Digital outputs NO..., NC...
Type
Relay. Minimum contact current: 50 mA.
Maximum no
8: SMALL; 13: MEDIUM/ BUILT-IN DRIVER; 18: LARGE;
Insulation distance
The relay outputs have diff erent features depending on the model of controller. The outputs can be divided into groups. The relays belonging
to the same group (individual cell in the table) have basic insulation and therefore must have the same voltage. Between groups (cells in the
table) there is double insulation and consequently these may have diff erent voltages. There is also double insulation between each terminal of
the digital outputs and the rest of the controller.
Relays with the same insulation
Group
Makeup of the
groups
Model
1
2
3
4
5
6
7
8
9
10
11
SMALL
1-3
4-6
7
8
-
-
-
-
-
-
-
Type of relay
Type A
Type A
Type A
Type A
-
-
-
-
-
-
-
MEDIUM/ BUILT-IN DRIVER
1-3
4-6
7
8
9-11
12
13
-
-
-
-
Type of relay
Type A
Type A
Type A
Type A
Type A
Type A
Type A
-
-
-
-
LARGE NO
1-3
4-6
7
8
9-11
12
13
14-15
16-18
-
-
Type of relay
Type A
Type A
Type A
Type A
Type A
Type A
Type A
Type A
Type A
-
-
LARGE NC
1-3
4-6
7
8
9-11
12
13
14-15
16-18
-
-
Type of relay
Type A
Type A
Type A
Type A
Type A
Type A
Type A
Type A
Type C
-
-
EXTRALARGE
1-3
4-6
7
8
9-11
12
13
14-16
17-20
21-24
25-29
Type of relay
Type A
Type A
Type A
Type A
Type A
Type A
Type A
Type B
Type B
Type B
Type B
Number of
changeover
contacts
1: SMALL (relay 8)
3: MEDIUM (relay 8, 12, 13)
5: LARGE NO/NC (relay 8, 12, 13, 14 e 15)
Note:
the output relays have diff erent features, depending on the model of controller.
Switchable power
Relay type A
Rated data
SPDT, 2000 VA, 250 Vac, 8A resistive
Approval
UL 873
2 A 250 Vac resistive, 2A FLA, 12 LRA, 250 Vac, C300 pilot duty (30,000 cycles)
EN 60730-1
2 A resistive, 2A inductive, cosφ=0.6, 2(2)A (100,000 cycles)
Relay type B
Relay rated data
SPST, 1250 VA, 250 Vac, 5A resistive
Approval
UL 873
1 A 250 Vac resistive, 1A FLA, 6 LRA, 250 Vac, C300 pilot duty (30,000 cycles)
EN 60730-1
1 A resistive, 1A inductive, cosφ=0.6, 1(1)A (100,000 cycles)
Relay type C
Relay rated data
SPDT, 1250 VA, 250 Vac, 5A resistive
Approval
UL 873
1 A 250 Vac resistive, 1A FLA, 6 LRA, 250 Vac, C300 pilot duty (30,000 cycles)
EN 60730-1
1 A resistive, 1A inductive, cosφ=0.6, 1(1)A (100,000 cycles)
Tab. 2.j
2.2.8
SSR outputs (in models where featured)
Maximum number
2: SMALL (outputs 7, 8);
2: MEDIUM (outputs 7, 12);
6: LARGE (outputs 7, 8, 12, 13, 14, 15)
Working voltage
24 Vac/Vdc
Load current (MAX)
1 A
Impulsive load current (MAX)
1.2 A
Tab. 2.k
Warnings:
•
if the load requires higher current, use an external SSR;
•
to power external loads, use the same power supply as the pCO (connected to terminals G/G0); this must always be dedicated and not in common with the power
supply to other devices on the electrical panel (such as contactors, coils, etc...);
•
the groups that the digital outputs are divided into have two common pole terminals to simplify wiring;
•
make sure that the current running through the common terminals does not exceed the rated current of an individual terminal, that is, 8 A.
Page 60 of 172
Copyright HPL March 2021
P4114S Rev 03
Summary of Contents for Hubbard GCU2040PXB1
Page 4: ...Page 4 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 49: ...6 Carel PR300T CO2 Controller manual Page 49 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 144: ...Page 144 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 165: ...9 Commissioning Form Page 165 of 172 Copyright HPL March 2021 P4114S Rev 03...