pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
Mask index
Display description
Description
Def
.
U
.
of M
.
V
alues
Eib25
Threshold
Receiver high pressure threshold alarm
45.0 barg
…
… (**)
Diff .
Receiver high pressure diff erential alarm
5.0 barg
…
… (**)
Delay
Receiver high pressure alarm delay
30
s
0…9999
Reset
Receiver high pressure alarm reset type
manual
---
manual | auto
Swith-off comp.
Enable compressor shutdown when high pressure receiver alarm occurs
NO
---
NO | YES
Eib27
Enable parallel compressor:
Enable parallel compressor
NO
YES | NO
Eib28
RPRV opening:
RPRV opening to allow parallel compressor
30
%
Delay:
Delay on parallel compressor activation
10
s
0…999
Min g.c.temp.:
Minimum GC temperature to allow parallel compressor
15
°C/°F
Eib31
Receiver pressure threshold
Threshold pressure for the gas cooler when the Heat Reclaim is ON
---
---
---
Time
Time during which this threshold remains active
---
---
---
Var. delta
Allowed variation
---
---
---
Eib32
Max. HPV valve opening
percentage
HPV valve maximum opening
0
%
0.0…100.0
Max. delta
HPV valve maximum variation per second
0
%
0.0…100.0
Eib35
Min on time:
Parallel compressor by inverter, timings. Min on time
30
s
Min off time:
Parallel compressor by inverter, timings. Min off time
30
s
Min time to start same
compressor:
Parallel compressor by inverter, timings. Min time to start same compressor
60
s
Eib40
RPRV off set with par. compr.
On:
Increment of RPRV setpoint during parallel compressor regulation
2
barg
Par. Comp. ON Rising time
RPRV:
Rising time of RPRV setpoint
0
s
Par. Comp. Off Falling time
RPRV:
Falling time of RPRV setpoint
20
s
Eic01
HPV Valve
Enable EVS management of HPV valve
enable
---
enable | disable
RPPV Valve
Enable EVS management of HPV valve RPRV
enable
---
enable | disable
EVD address
Driver address managed in FBUS from pRack
198
---
0..207
Valves routing
Valve type driver association
---
---
Single A->HPV
Single A->RPRV
Twin A->RPRV
B->HPV
Twin A->HPV
B->RPRV
EVD Status
Driver connection to pRack status
---
---
connected
not connected
Eic02
HPV Valve type
HPV valve type
CAREL EXV ---
CAREL EXV,
CUSTOM, Danfoss
CCMT, Danfoss
ICMTS (0-10V)
RPRV Valve type
RPRV valve type
CAREL EXV ---
CAREL EXV, CUSTOM,
Danfoss ETS 400,
Danfoss ETS 250,
Danfoss ETS 100B,
Danfoss ETS 50B,
Danfoss ETS 12.5-25B,
Danfoss CCM 40
Danfoss CCM 10-20-30
Danfoss ICMTS
(0-10V)
Eic03
(Valvola HPV)
Min. steps
Minimum valve step number
50
step
0…9999
Max. steps
Maximum valve step number
480
step
0…9999
closing steps
Valve closing steps
500
step
0…9999
Nom. step rate
Valve nominal speed
50
step/s
1…2000
Move current
Nominal current
450
mA
0…800
Holding current
Holding current
100
mA
0…250
Eic04
(Valvola HPV)
Duty Cycle
Valve duty cycle
30
%
0…100
Opening sincre
Opening position synchronization
YES
-----
YES | NO
Closing sincre
Closing position synchronization
YES
------
YES | NO
Em. closing speed
Valve emergency closing speed
150
step/s
1…2000
Eic05
(Valvola RPRV)
Min. steps
Minimum valve step number
50
step
0…9999
Max. steps
Maximum valve step number
480
step
0…9999
closing steps
Valve closing steps
500
step
0…9999
Nom. step rate
Valve nominal speed
50
step/s
1…2000
Move current
Nominal current
450
mA
0…800
Holding current
Holding current
100
mA
0…250
Eic06
(Valvola RPRV)
Duty Cycle
Valve duty cycle
30
%
0…100
Opening sincre
Opening position synchronization
YES
-----
YES | NO
Closing sincre
Closing position synchronization
YES
------
YES | NO
Em. closing speed
Valve emergency closing speed
150
step/s
1…2000
The following parameters refer to line 2, for details, see the corresponding parameters for line 1 above
Eaba04
---
Oil temperature probe position (line 2)
B1
---
---, U1…U10 (****)
---
Oil temperature probe type (line 2)
4...20 mA
---
--- | NTC | PT1000
| 0...1 V | 0...10 V |
4...20 mA | 0...5 V |
HTNTC
--- (display only)
Oil temperature value (line 2)
---
…
…(**)
Max limit
Maximum oil temperature value (line 2)
30.0 barg
…
…(**)
Min limit
Minimum oil temperature value (line 2)
0.0 barg
…
…(**)
Calibration
Oil temperature probe calibration (line 2)
0.0 barg
…
…(**)
…
…
…
…
…
…
Eabb04
Enable com.cool.
Enable common oil cooling (line 2)
YES
---
NO | YES
Number of oil pumps
Number of oil pumps for common oil cooler (line 2)
0
---
0…1 (analog. output)
0…2 (digital outputs)
Enable pump out.
Enable AO of common oil cooler pump (line 2)
YES
---
NO (digital outputs)
YES (analog. output)
…
…
…
…
…
…
Ebba01
DO
Subcooling DO valve position (line 2)
…
---
---, 01…18 (****)
Status (display only)
Subcooling DO valve status (line 2)
---
---
closed | open
Logic
Subcooling DO valve logic (line 2)
NO
---
NC | NO
Function (display only)
Status of the subcooling valve function (line 2)
---
---
not active | active
…
…
…
…
…
…
Ebbb01
Subcooling contr.
Enable subcooling function (line 2)
NO
---
NO | YES
---
Subcooling control type (line 2)
Temp.
Cond&Liqu.
---
Temp. Cond&Liquid
only Liquid Temp.
Threshold
Threshold for subcooling activation (line 2)
0.0 °C
…
-9999,9…9999,9
Subcooling (display only)
Subcooling value (line 2)
0.0 °C
…
-999,9…999,9
Page 119 of 172
Copyright HPL March 2021
P4114S Rev 03
Summary of Contents for Hubbard GCU2040PXB1
Page 4: ...Page 4 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 49: ...6 Carel PR300T CO2 Controller manual Page 49 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 144: ...Page 144 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 165: ...9 Commissioning Form Page 165 of 172 Copyright HPL March 2021 P4114S Rev 03...