Fig.2: 80 or 90 BAR PS RATING
ALL EVAPORATORS
(Coldroom or Display Cabinet Evaporators)
COLDROOM EVAPORATORS
DISPLAY SHOWCASE EVAPORATORS
LOW PRESSURE SIDE:
All Field and Evaporator Pipework, Expansion Valves, Evaporators, Line
Components etc.
MUST
have a
MINIMUM PS rating
:
MODEL
EVAPORATOR
COIL
SUCTION
LINE
SUCTION LINE
COMPONENTS
SUCTION PRV
REQUIRED?
SUCTION
PRESSURE
RATING
HCU2020PXB1
HCU2040PXB1
GCU2020PXB1
GCU2040PXB1
90 Bar(g)
90 Bar(g)
90 Bar(g)
NO
90 Bar(g)
HCU4070PXB1
HCU5140PXB1
GCU4070PXB1
GCU5140PXB1
80 Bar(g)
80 Bar(g)
80 Bar(g)
NO
80 Bar(g)
HIGH PRESSURE SIDE:
All Field and Evaporator Pipework, Valves, etc.
MUST
have a
MINIMUM PS
rating
:
MODEL
LIQUID
LINE
*
EXPANSION
VALVE
LIQUID LINE
COMPONENTS
SUCTION PRV
REQUIRED?
SUCTION
PRESSURE
RATING
HCU2020PXB1
HCU2040PXB1
GCU2020PXB1
GCU2040PXB1
90 Bar(g)
90 Bar(g)
90 Bar(g)
NO
90 Bar(g)
HCU4070PXB1
HCU5140PXB1
GCU4070PXB1
GCU5140PXB1
80 Bar(g)
80 Bar(g)
80 Bar(g)
NO
80 Bar(g)
LIQUID LINE PRE-INSTALLED TAILS & EXPANSION VALVES
*
If the evaporator is supplied with pipework tails to connect the field pipework to the
Refrigerated Display Cabinet (i.e. the tails are installed from the ball valve connection on the
top or underside of the display cabinets). The length of liquid line pipework between the
connection point and the inlet of the expansion device MUST be the correct pressure rating.
Page 172 of 172
Copyright HPL March 2021
P4114S Rev 03
Summary of Contents for Hubbard GCU2040PXB1
Page 4: ...Page 4 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 49: ...6 Carel PR300T CO2 Controller manual Page 49 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 144: ...Page 144 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 165: ...9 Commissioning Form Page 165 of 172 Copyright HPL March 2021 P4114S Rev 03...