57
ENG
pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
Mask index
Display description
Description
Def
.
U
.
of M
.
V
alues
Ab05 (display
only)
UserSetp.
Setpoint set by the user for gas cooler regulation under pressure, proportional regulation
(line 1)
---
… …(**)
ActualSetp.
Actual setpoint for gas cooler regulation under pressure, proportional regulation (with
compensations applied, line 1)
---
… …(**)
Diff .
Gas cooler regulation under pressure diff erential, proportional regulation (line 1)
---
…
…(**)
Ab06 (display
only)
UserSetp.
Setpoint set by the user for gas cooler regulation under pressure, proportional regulation
(line 1)
---
… …(**)
ActualSetp.
Actual setpoint for gas cooler regulation under pressure, proportional regulation (with
compensations applied, line 1)
---
… …(**)
Dead zone
Dead zone for gas cooler regulation under pressure (line 1)
---
…
…(**)
Incr.Diff .
Increase diff erential for gas cooler regulation under pressure, regulation in dead zone
(line 1)
---
… …(**)
Decr.Diff .
Decrease diff erential for gas cooler regulation under pressure, regulation in dead zone
(line 1)
---
… …(**)
Ab07 (display
only)
UserSetp.
Setpoint set by the user for condensing regulation under pressure, proportional regulation
(line 2)
---
… …(**)
ActualSetp.
Actual setpoint for condensing regulation under pressure, proportional regulation (with
compensations applied, line 2)
---
… …(**)
Diff .
Condensing regulation under pressure diff erential, proportional regulation (line 2)
---
…
…(**)
Ab08 (display
only)
UserSetp.
Setpoint set by the user for condensing regulation under pressure, proportional regulation
(line 2)
---
… …(**)
ActualSetp.
Actual setpoint for condensing regulation under pressure, proportional regulation (with
compensations applied, line 2)
---
… …(**)
Dead zone
Dead zone for condensing regulation under pressure (line 1)
---
…
…(**)
Incr.Diff .
Increase diff erential for condensing regulation under pressure, regulation in dead zone
(line 2)
---
… …(**)
Decr.Diff .
Decrease diff erential for condensing regulation under pressure, regulation in dead zone
(line 2)
---
… …(**)
Ab12
Setpoint
Setpoint without compensation (suction line 1)
26.0 barg
…
…(**)
Ab13
Setpoint
Setpoint without compensation (gas cooler line 1)
12.0 °C
…
…(**)
Ab14
Setpoint
Setpoint without compensation (suction line 2)
12.0 barg
…
…(**)
Ab15
Setpoint
Setpoint without compensation (condens. line 2)
12.0 barg
…
…(**)
Ac01
Status
Unit status (display only)
OFF from
keypad
---
Wait...
Unit ON
OFF from Alarm
OFF from blackout
OFF from BMS
OFF from default
OFF from DIN
OFF from keypad
Manual Funct. work
Prevent from HP
---
On-off from keypad (line 1)
OFF
---
OFF | ON
Ac02
L1:
L2:
Unit status (display only)
OFF da
tastiera
---
… (see Ac01 above)
---
On-off from keypad (line 1)
OFF
---
OFF | ON
---
On-off from keypad (line 2)
OFF
---
OFF | ON
Ac03
Enable unit On/Off
from digital input
Enable unit On/Off from digital input (line 1)
NO
---
NO | YES
From supervisor
Enable on-off from supervisor (line 1)
NO
---
NO | YES
Due to black out
Enable on-off due to black out (line 1)
NO
---
NO | YES
Ac04
Delay unit startup after
blackout
Delay unit startup after blackout (line 1)
0
s
0…999
Ac06
Enable unit On/Off
from digital input
Enable unit On/Off from digital input (line 2)
NO
---
NO | YES
From supervisor
Enable on-off from supervisor (line 2)
NO
---
NO | YES
Due to black out
Enable on-off due to black out (line 2)
NO
---
NO | YES
Ac07
Unit startup delay after
blackout
Unit startup delay after blackout (line 2)
0
s
0…999
Tab. 7.b
Mask index
Display description
Description
Def
.
U
.
of M
.
V
alues
B.Inp./Out.
The I/Os depend on the confi guration selected, the following are only examples. See Appendix A.1 for the complete list and position of available I/Os.
Baa02
DI
Alarm 1 compressor 1 DI position(line 1)
03
---
---, 01…18,
U1…U10 (****)
Status (display only)
Status Alarm 1 compressor 1 DI (line 1)
---
---
Closed | Open
Logic
Logic alarm 1 compressor 1 DI (line 1)
NC
---
NC | NO
Function (display only)
Alarm 1 compressor 1 function status (line 1)
---
---
Not active | Active
…
…
…
…
…
…
Baacf
DI
Heat recovery from digital input DI position (line 1)
---
---
--- | 01…18 |
U1…U10 (****)
Status
Heat recovery from digital input DI status (line 1)
---
---
Closed | Open
Logic
Heat recovery from digital input DI logic (line 1)
NC
---
NC | NO
Function
Heat recovery from digital input function status (line 1)
---
---
Not active | Active
…
…
…
…
…
…
Bab01
---
Suction pressure probe position (Line 1)
B1
---
---, U1…U10 (****)
---
Suction pressure probe type (Line 1)
4...20mA
---
---
0-1V
0-10V
4...20mA
0-5V
--- (display only)
Suction pressure value (line 1)
---
…
…(**)
Max limit
Suction pressure maximum value (line 1)
44.8 barg
…
…(**)
Min limit
Suction pressure minimum value (line 1)
0.0 barg
…
…(**)
Calibrat.
Suction pressure probe calibration (Line 1)
0.0 barg
…
…(**)
Bab63
---
Common oil receiver pressure probe position (line 1)
---
---
U1…U10 (****)
---
Common oil receiver pressure probe type (line 1)
4...20mA
---
---- | 0-1V | 0-10V
4...20mA | 0-5V
--- (display only)
Common oil receiver pressure value (line 1)
---
…
…(**)
Max limit
Maximum common oil receiver pressure value (line 1)
44.8 barg
…
…(**)
Min limit
Minimum common oil receiver pressure value (line 1)
0.0 barg
…
…(**)
Calibrat.
Common oil receiver pressure probe calibration (line 1)
0.0 barg
…
…(**)
Page 106 of 172
Copyright HPL March 2021
P4114S Rev 03
Summary of Contents for Hubbard GCU2040PXB1
Page 4: ...Page 4 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 49: ...6 Carel PR300T CO2 Controller manual Page 49 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 144: ...Page 144 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 165: ...9 Commissioning Form Page 165 of 172 Copyright HPL March 2021 P4114S Rev 03...