72
ENG
pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
Mask index
Display description
Description
Def
.
U
.
of M
.
V
alues
Fca01
Address
Address of the supervisory system (line 1)
196
---
0…207
Protocol
Supervisor communication protocol (line 1)
Carel slave
local
---
--, CAREL SLAVE
LOCAL
CAREL SLAVE
REMOTE
MODBUS SLAVE
pRACK MANAGER
CAREL SLAVE GSM
Baudrate
Supervisor communication speed (line 1)
19200
---
1200…19200
Fd01
Insert password
Password
0000
---
0…9999
Current password level
---
---
User | Service |
Manufacturer
Fd02
Logout
Logout
NO
---
NO | YES
Fd03
User
User password
0000
---
0…9999
Service
Service password
1234
---
0…9999
Manufacturer
Manufacturer password
1234
---
0…9999
Fda01
Enable CpCOe
Enable expansion card
NO
---
YES | NO
Offl
ine pattern
Enable output confi guration when offl
ine
Disabled
---
Abled | Disabled
Digital Output pattern 1: … 6: Digital output status when expansion card offl
ine
OFF
---
ON | OFF
Fda02
Universal Input pattern
UI01..UI10
Analogue output status when expansion card offl
ine
0
%
0…100
The following parameters refer to line 2, for details, see the corresponding parameters for line 1 above
Fcb01
Address
Address of the supervisory system (line 2)
196
---
0…207
Protocol
Supervisor communication protocol (line 2)
pRack
manager
---
---, CAREL SLAVE
LOCAL
CAREL SLAVE
REMOTE
MODBUS SLAVE
pRACK MANAGER
CAREL SLAVE GSM
Baudrate
Supervisor communication speed (line 2)
19200
---
1200…19200
Tab. 7.g
Mask index
Display description
Description
Def
.
U
.
of M
.
V
alues
G.Safeties
Gba01
Enable prevent
Enable high pressure condensing prevent (line 1)
NO
---
NO | YES
Gba02
Setpoint
High pressure condensing prevent threshold (line 1)
0.0 barg
…
… (**)
Diff erential
High pressure condensing prevent diff erential (line 1)
0.0 barg
…
0.0…99,9
Decrease compressor power
time
Decreasing compressor capacity time (line 1)
0
s
0…999
Gba03
Enable heat recov. as fi rst
prevent step
Enabling heat recovery as fi rst stage for condensing HP prevent (line 1)
NO
---
NO | YES
Off set HeatRecov
Off set between heat recovery and prevent setpoint (line 1)
0.0 barg
…
0.0…99,9
Gba04
Enable ChillB. as fi rst prevent
step
Enable ChillBooster as fi rst stage for condensing HP prevent (line 1)
NO
---
NO | YES
Chill. off set
Off set between ChillBooster and prevent setpoint (line 1)
0.0 barg
…
0.0…99,9
Gba05
Max. num prevent
Max number of prevent before locking compressors (line 1)
3
---
1…5
Prevent max number
evaluation time
Prevent max number evaluation time
60
h
0…999
Reset automatic prevent
Reset maximum number of prevent (line 1)
NO
---
NO | YES
Gca01
Common HP type
Type of reset for common HP alarm (line 1)
AUTO
---
AUTO | MAN
Common HP delay
Common high pressure delay (line 1)
10
s
0…999
Gca02
Common LP start delay
Common low pressure delay at startup (line 1)
60
s
0…999
Common LP delay
Common low pressure delay during operation (line 1)
20
s
0…999
Gca03
Time of semi-automatic
alarm evaluation
Number of LP interventions evaluation time (line 1)
120
min
0…999
Numer of retries before alarm
becomes manual (line 1)
Number of LP interventions in the period after which the alarm becomes a manual reset
(line 1)
5
---
0…999
Gca04
Liquid alarm delay
Liquid level alarm delay (line 1)
0
s
0…999
Oil alarm delay
Common oil alarm delay (line 1)
0
s
0…999
Gca05
Output relay alarm activation
with
Selection of output relay alarm activation with active alarms or alarms not reset
alarms attivi
alarms attivi
alarms no reset
The following parameters refer to line 2, for details, see the corresponding parameters for line 1 above
Gbb01
Enable prevent
Enable high pressure condensing prevent (line 2)
NO
---
NO | YES
…
…
…
…
…
…
Gcb01
Common HP type
Type of reset for common HP alarm (line 2)
AUTO
---
AUTO | MAN
Common HP delay
Common high pressure delay (line 2)
10
s
0…999
…
…
…
…
…
…
Tab. 7.h
Mask index
Display description
Description
Def
.
U
.
of M
.
V
alues
H.Info
H01 (display
only)
Ver.
Software version and date
…
---
…
Bios
Bios version and date
…
---
…
Boot
Boot version and date
…
---
…
H02 (display
only)
Board type
Hardware type
…
---
…
Size
Hardware size
…
---
…
FLASH mem
Flash memory size
---
kB
…
RAM
RAM memory size
---
kB
…
Built-in type
Built-in display type
---
---
None | pGDE
Cycle time
Number of cycles per second and cycle time software
---
cicli/s / ms …
Tab. 7.i
Page 121 of 172
Copyright HPL March 2021
P4114S Rev 03
Summary of Contents for Hubbard GCU2040PXB1
Page 4: ...Page 4 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 49: ...6 Carel PR300T CO2 Controller manual Page 49 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 144: ...Page 144 of 172 Copyright HPL March 2021 P4114S Rev 03...
Page 165: ...9 Commissioning Form Page 165 of 172 Copyright HPL March 2021 P4114S Rev 03...