SiBE04-808_B
Field Settings
Trial Operation and Field Settings
296
RKS50G2V1B
Caution
1. If the outdoor unit is installed where the outdoor heat exchanger of the unit is exposed to
direct wind, provide a windbreak wall.
2. Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and
off when using facility settings.
3. Do not place humidifiers or other items which might raise the humidity in rooms where facility
settings are being used.
A humidifier might cause dew jumping from the indoor unit outlet vent.
4. Cutting jumper sets the indoor fan tap to the highest position. (20/25/35/42 class)
5. Use the indoor unit at the highest level of airflow rate. (50 class)
4.5
Jumper and Switch Settings
For the location of the jumper, refer to the following pages.
Indoor unit; page 19
Outdoor unit; page 22, 24, 26
For the location of the switch, refer to page 28.
LED-A
SW4
ON
AB
C
D
S102
SW1
S2
(R12186)
Turn on the
switch SW4-B.
Jumper
Function
When connected
(factory set)
When cut
JB
(on indoor unit PCB)
Fan speed setting
when compressor
stops for thermostat
OFF.
(effective only at
cooling operation)
Fan speed setting ;
Remote controller
setting
Fan rpm is set to “0”
<Fan stop>
JC
(on indoor unit PCB)
Power failure
recovery function
Auto-restart
The unit does not resume
operation after recovering from
a power failure. Timer ON/OFF
settings are cleared.
J5
(on outdoor unit PCB
of 20-42 class)
Improvement of
defrost performance
Standard control
Reinforced control
(ex. The frequency increases,
the duration time of defrost
lengthens.)
Switch
Function
OFF (factory set)
ON
SW4-C
(on outdoor unit PCB
of 50 class)
Improvement of
defrost performance
Standard control
Reinforced control (ex. The
frequency increases, the
duration time of defrost
lengthens.)