Outdoor Unit - RK(X)S42G2V1B, ARXS42G2V1B
SiBE04-808_B
245
Removal Procedure
10
Disconnect the relay
connector for the
compressor.
11
Disconnect the 2
connectors for the
reactor.
12
Release the discharge
pipe thermistor.
Be careful not to lose the clip
for the thermistor.
13
Detach the clamp for
the thermistors from the
electrical box.
Step
Procedure
Points
(R0259)
(R0260)
(R12197)
Discharge
pipe thermistor
(R12279)
Clip
(R0262)
(R12196)