SiBE04-808_B
Indoor Unit
Removal Procedure
176
2. Remove the indoor heat
exchanger.
Preparation
Remove the indoor unit from
the installation plate.
1
Unfasten the hook of
the piping fixture at the
back of the indoor unit
and pull out the pipe.
2
Widen the auxiliary pipe
by about 10-20
degrees.
Caution
When dismounting or
mounting the indoor heat
exchanger, be sure to wear
gloves or wrap it with cloth
before proceeding. (You may
be injured by the fins.)
3
Remove the 2 screws
on the left side.
4
Unfasten the lower
hook on the right side
with a flat screwdriver.
Step
Procedure
Points
(R10622)
Piping
fixture
(R10543)
Unbending angle:
10-20 deg.
(R10546)
(R10326)
Lower hook