Outdoor Unit - RK(X)S42G2V1B, ARXS42G2V1B
SiBE04-808_B
257
Removal Procedure
4.6
Removal of Thermistors
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
1
Release the discharge
pipe thermistor.
Be careful not to lose the clip
for the thermistor.
2
Cut the clamp and pull
out the outdoor heat
exchanger thermistor.
3
The thermistors for
outdoor temperature /
discharge pipe /
outdoor heat exchanger
are united as one
assembly.
4
The figure shows the
arrangement of the
thermistors.
(R8192)
Discharge pipe thermistor
(R12279)
Clip
(R8193)
Outdoor heat
exchanger thermistor
(R8194)