10-3 SETTING AIR DISCHARGE DIRECTION
•
When changing air discharge setting (2-way or 3-way discharge), set the SECOND CODE No. as shown
in the Table 5.
Table 5
10-4 SETTING FAN SPEED DURING THERMOSTAT OFF
•
Set the fan speed according to the using environment after consultation with your customer.
•
When the fan speed is changed, explain the set fan speed to your customer.
Table 6
10-5 SETTING INDOOR UNIT NUMBER OF SIMULTANEOUS OPERATION SYSTEM
•
When using in simultaneous operation system mode, change the SECOND CODE No. as shown in Table 7.
(SECOND CODE No. is factory set to “01” for pair system.)
•
When using in simultaneous operation system mode, refer to “
10-6 SIMULTANEOUS OPERATION SYS-
TEM INDIVIDUAL SETTING
” section to set master and slave units separately.
Table 7
Setting
Mode No.
FIRST CODE No.
SECOND CODE No.
4-way air discharge
13 (23)
1
01
3-way air discharge
02
2-way air discharge
03
Setting
Mode No.
FIRST CODE
No.
SECOND
CODE No.
Fan stops during thermostat
OFF (Cooling · heating)
Normal
11 (21)
2
01
Stop
02
Fan speed during cooling
thermostat OFF
LL (Extra low)
12 (22)
6
01
Setting
02
Fan speed during heating
thermostat OFF
LL (Extra low)
12 (22)
3
01
Setting
02
Setting
Mode No.
FIRST CODE No.
SECOND CODE No.
Pair system (1 unit)
11 (21)
0
01
Simultaneous opera-
tion system (2-unit)
02
Simultaneous opera-
tion system (3-unit)
03