Discharge piping temperature
malfunction (Outdoor unit)
H3
High pressure switch failure (Outdoor unit)
H4
Low pressure switch failure
(Outdoor unit)
H7
Outdoor fan motor position signal
malfunction (Outdoor unit)
H9
Outdoor air thermistor system
malfunction (Outdoor unit)
Abnormal stop is applied depending on the
model or condition.
J1
Pressure sensor system malfunction
(batch) (Outdoor unit)
J2
Current sensor system malfunction
(Outdoor unit)
Abnormal stop is applied depending on the
model or condition.
J3
Discharge piping thermistor system
malfunction (Outdoor unit)
Abnormal stop is applied depending on the
model or condition.
J5
Suction piping thermistor system
malfunction (Outdoor unit)
J6
Outdoor heat exchanger distributor
liquid piping thermistor malfunction
(Outdoor unit)
Abnormal stop is applied depending on the
model or condition.
J7
Outdoor heat exchanger condenser /
evaporator thermistor malfunction
(Outdoor unit)
Abnormal stop is applied depending on the
model or condition.
J8
Liquid piping thermistor system
malfunction (Outdoor unit)
Abnormal stop is applied depending on the
model or condition.
J9
Gas piping thermistor malfunction
(cooling) (Outdoor unit)
JA
Discharge piping pressure sensor
system malfunction (Outdoor unit)
JC
Suction piping pressure sensor system
malfunction (Outdoor unit)
L1
Inverter system malfunction
(Outdoor unit)
L3
Reactor thermistor malfunction
(Outdoor unit)
L4
Overheated heat-radiating fin
(Outdoor unit)
Inverter cooling failure.
L5
Instantaneous overcurrent
(Outdoor unit)
The compressor engines and turbines may be
experiencing a ground fault or short circuit.
L8
Electric thermal (Outdoor unit)
The compressor engines and turbines may be
overloaded and disconnected.
L9
Stall prevention (Outdoor unit)
The compressor may be locked.
LC
Transmission malfunction between
inverter and outdoor control unit
(Outdoor unit)
P1
Open-phase (Outdoor unit)
P3
DCL sensor system malfunction
(Outdoor unit)
P4
Heat-radiating fin thermistor
malfunction (Outdoor unit)
Abnormal stop is applied depending on the
model or condition.
P6
DC output current sensor system
malfunction (Outdoor unit)