Do not install the air conditioner in places such as the following:
1. Where there is mist of oil, oil spray or vapour for example a kitchen.
Resin parts may deteriorate, and cause them to fall out or water to leak.
2. Where corrosive gas, such as sulfurous acid gas, is produced.
Corrosion of copper pipings or brazed parts may cause the refrigerant to leak.
3. Where there is machinery which emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
4. Where flammable gases may leak, where carbon fibre or ignitable dust is suspended in the air or where
volatile flammables, such as thinner or gasoline, are handled.
If the gas should leak and remained around the air conditioner, it may cause ignition.
•
The air conditioner is not intended for use in a potentially explosive atmosphere.
2. BEFORE INSTALLATION
When unpacking the indoor unit or moving the unit after unpacked, hold the hangers (4 places) and
do not apply force to other parts (particularly refrigerant piping, drain piping and resin parts).
Be sure to check that the refrigerant is used according to outdoor unit specification. (If a wrong
refrigerant is charged, the unit will not properly operate.)
•
Make sure to check in advance that the refrigerant to be used for installation work is according to outdoor
unit specifications.
(The air conditioner will not properly operate if a wrong refrigerant is used.)
•
For installation of the outdoor unit, refer to the installation manual attached to the outdoor unit.
•
Do not throw away the accessories until the installation work is completed.
•
After the indoor unit is carried into the room, to avoid the indoor unit from getting damaged, take measures
to protect the indoor unit with packing materials.
(1) Determine the route to carry the unit into the room.
(2) Do not unpack the unit until it is carried to the installation location.
Where unpacking is unavoidable, use a sling of soft material or protective plates together with a rope
when lifting, to avoid damage or scratches to the indoor unit.
•
Have the customer actually operate the indoor unit while looking at the operation manual.
Instruct the customer how to operate the unit (particularly cleaning of the air filters, operation procedures,
and temperature adjustment).
•
For selection of installation location, use the installation pattern paper (used in common with the packing
case) as reference.
•
Do not use the air conditioner in salty atmosphere such as coastal areas, vehicles, vessels or areas where
voltage fluctuation is frequent such as factories.
•
Take off static electricity from the body when opening the control box cover panel and when carrying out wiring.
The electric parts may be damaged.
INFORMATION TO IDENTIFY THE MODEL TO WHICH THE INFORMATION RELATES: FUA125AVEB
Item
Symbol
Value
Unit
Item
Symbol
Value
Unit
Cooling capacity
(sensible)
P
rated, c
9.06
kW
Total electric power input
P
elec
0.15
kW
Cooling capacity
(latent)
P
rated, c
4.94
kW
Sound power level
cooling (per speed setting
if applicable)
L
WA
65
dB
Heating capacity
P
rated, h
13.50
kW
Sound power level
heating (per speed setting
if applicable)
L
WA
66
dB
Contact details
DAIKIN INDUSTRIES CZECH REPUBLIC s.r.o.
U Nové Hospody 1/1155, 301 00 Plze
ň
Skvr
ň
any, Czech Republic