Functions for FDMQ Series
SiUS091601EA
73
Part 4 Functions and Control
Enabling or disabling the schedule
R4003458
3.5 Drain Pump Control
Normal Operation
The float switch is ON in normal operation.
When cooling operation starts (thermostat ON), the drain pump turns ON simultaneously.
After the thermostat turns OFF, the drain pump continues to operate.
1
2
3
Display the schedule screen.
Press buttons to select
Enable / Disable
on the schedule
screen.
Press
Menu/OK
button to display the
enable/disable screen.
Press buttons to select
Enable
or
Disable
on the enable/disable
screen.
Press
Menu/OK
button after selecting
the item. The confirmation screen is
displayed.
Press buttons to select
Yes
on the
confirmation screen.
Pressing
Menu/OK
button confirms the
enable/disable setting for the schedule
and takes you back to the basic screen.
Float switch
Error display
Thermostat
(running)
OFF
OFF
ON
ON
ON
OFF
Drain pump
ON
OFF
(R24037)