Troubleshooting for FDMQ Series
SiUS091601EA
145
Part 6 Service Diagnosis
Note
6.7 Remote Controller Thermistor Abnormality
Error Code
CJ
Method of Error
Detection
Even if remote controller thermistor is faulty, system is possible to operate by system thermistor.
Malfunction detection is carried out by the temperature detected by the remote controller
thermistor.
Error Decision
Conditions
The remote controller thermistor is disconnected or shorted while the unit is running.
Supposed
Causes
Defective room temperature thermistor in the wired remote controller
Defective wired remote controller PCB
External factor such as noise
Troubleshooting
To delete the record of error codes, press
ON/OFF
button on the remote controller for 4 seconds or
more while the error code is displayed in the inspection mode.
Replace the remote
controller.
External factor other than
equipment malfunction.
(for example, noise etc.)
NO
YES
(R23951)
Is
CJ
displayed on
the remote controller
again?
Delete the record of error
codes. (Refer to Note)
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for FTX-N Series
Page 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications...
Page 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter...
Page 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U...
Page 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368...
Page 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A...