Field Settings for FDMQ Series
SiUS091601EA
213
Part 7 Trial Operation and Field Settings
Note(s)
5.2 Overview of Field Settings
The Second Code No. is factory set to "01".
Do not use any settings not listed in the table.
For group control with a wireless remote controller, initial settings for all the indoor units of the
group are equal.
For group control, refer to the installation manual attached to the indoor unit for group control.
External Static
Pressure Settings
12 class
Mode
No.
First
Code
No.
Second Code No.
Description of setting
01
02
03
10
(20)
0
Lig
h
t
Approx.
2,500 hrs.
Heavy
Approx.
1,250 hrs.
—
Filter cleaning sign interval (used to
change filter cleaning display
interval according to filter
contamination)
Longlife filter
Approx.
200 hrs.
Approx.
100 hrs.
—
Standard
filter
3
Display
No display
—
Filter cleaning sign (used to set filter cleaning display
ON/OFF)
11
(21)
7
OFF
Air volume
adjustment
completion
Air volume
adjustment start
Air volume adjustment
Factory Setting
Mode
No.
First
Code
No.
Second Code No.
External static pressure
13
(23)
6
03
30 Pa
04
40 Pa
05
50 Pa
06
60 Pa
07
70 Pa
08
80 Pa
09
90 Pa
10
100 Pa
11
110 Pa
12
120 Pa
13
130 Pa
14
140 Pa
15
150 Pa
Factory Setting
Summary of Contents for FTX-N Series
Page 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications...
Page 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter...
Page 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U...
Page 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368...
Page 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A...