Troubleshooting for Outdoor Unit
SiUS091601EA
155
Part 6 Service Diagnosis
Note
Reference
Reference
Reference
Troubleshooting
OL (Q1L) activating temperature: 120 ~ 130°C (248 ~ 266°F)
OL (Q1L) recovery temperature: 95°C (203°F)
Check No.01
Check No.12
Check No.13
(R22997)
Caution
YES
NG
NO
OK
OK
NG
NG
OK
YES
NO
NG
OK
Refrigerant shortage
Water mixed
Stop valve
Disconnect the connector S40
from the PCB.
Disconnect the 2 terminals of
the OL (Q1L).
Resistance
f
Resistance
f
Nearly 0
:
Nearly 0
:
Insert the thermistor in
position.
Replace the discharge pipe
thermistor.
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB (main PCB).
Replace the four way valve
or the coil.
Replace the outdoor unit
PCB (main PCB).
Discharge pipe
thermistor disconnected?
Check No. 01
Check the discharge pipe
thermistor.
Check No. 13
Check the four way valve.
Check No. 14
Check the refrigerant line.
Check No. 12
Check the electronic
expansion valve.
Replace the OL (Q1L).
Replace the OL harness.
Connect the connector S40
properly.
Is the connector S40
properly connected?
Check the
resistance between the 2
terminals on connector
S40.
Check the
resistance between the 2
terminals of the OL
(Q1L).
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for FTX-N Series
Page 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications...
Page 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter...
Page 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U...
Page 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368...
Page 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A...