Forced Cooling Operation
SiUS091601EA
201
Part 7 Trial Operation and Field Settings
For FDMQ series
R7000276
FDMQ Series with Wired Remote Controller (BRC1E73)
FDMQ Series with Wireless Remote Controller (BRC082A43)
1. Set to COOL operation using the remote
controller.
2. Press and hold
Cancel
button for 4 seconds
or longer. Service settings menu is
displayed.
3. Select
in the service
settings menu, and press
Menu/OK
button.
Basic screen returns and “Test Operation”
is displayed at the bottom.
4. Press
On/Off
button within 10 seconds, and
the forced cooling operation starts.
Forced cooling operation will stop
automatically after about 15 minutes.
To stop the operation, press
On/Off
button.
1. Press
button and select the COOL
operation.
2. Press
button twice.
“
TEST
”
is
displayed.
3. Press
button within 10 seconds, and
the forced cooling operation starts.
Forced cooling operation will stop
automatically after about 15 minutes.
To stop the operation, press
button.
Test Operation
Basic screen
1.
2.
3.
4.
Service Settings
menu screen
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
Press Menu/OK button.
Press On/Off button
(within 10 seconds).
Summary of Contents for FTX-N Series
Page 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications...
Page 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter...
Page 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U...
Page 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368...
Page 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A...